Supply Voltage: 12 to 24 VDC +/- 15%, Class 2 source

INPUT VOLTAGE

12 V

24 V

Typical Power DA70A only

4 W

4.5 W

Max Power DA70A only

4.5 W

5 W

Available Power for Modules  

(Maximum of 10 modules)

43 W

45 W

Max Power DA70A, with Sleds & USB

16 W

17 W

Max Power DA70A with full accessories

59 W

62 W

2. 

BATTERY

: 3 V Lithium coin cell. Typical lifetime of 5 years, at 

nominal usage. To maintain UL rating, replacement battery 

must be: Red Lion CRA000 BT3V0 00000, Rayovac BR1225X-

BA or Panasonic BR1225A/BN.

3. 

MEMORY

:

On Board User Memory: 1 GB of non-volatile Flash memory.

Memory Card: microSD slot accepts Class 5 or better microSD 

cards up to 256 GB capacity. FAT32, industrial grade.

4. 

COMMUNICATION CAPABILITIES

:  

USB Device Port: Isolated USB 2.0 full speed, type B 

connection. USB DEVICE PORT IS FOR SYSTEM SET-UP 

AND DIAGNOSTICS AND IS NOT INTENDED FOR 

PERMANENT CONNECTION.

USB Host Port: Complies with Universal Serial Bus 

Specification Rev 2.0. Supports data transfers at high speed 

and full speed with over current protection (0.5 A max).

Ethernet Ports: Two 10BaseT/100BaseTX RJ-45 Ports, auto 

MDI/MDI-X.

Isolation from Ethernet network to Gateway: 1500 Vrms

Serial Ports: Three serial ports with individual port isolation 

available in these two configurations:

DA70A0F

2 - RS-232 ports (RJ12 connectors)  

1 - RS-485/422 port (RJ45 connector)

DA70A0G

1 - RS-232 port (RJ12 connector) 

2 - RS-485/422 ports (RJ45 connectors)

5. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -40 to 75 °C

Storage Temperature Range: -40 to 85 °C

Operating and Storage Humidity: 0 to 85% max. RH non-

condensing

Vibration to IEC 60068-2-6: Operational 5-500 Hz, 2 g

Shock to IEC 60068-2-27: Operational 15 g

Altitude: Up to 2000 meters

Installation Category II, Pollution Degree 2 as defined in IEC/

EN 60664-1.

6. 

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

ATEX Approved

 II 3 G Ex ec IIC T4 Gc

DEMKO 20 ATEX 2268X

IECEx Approved

IECEx UL 20.0007X

UL Hazardous: File # E317425

Rugged IP30 enclosure

7. 

CONNECTIONS

Power Connection: Three-pin top mounted connector

Wire Strip Length: 0.3" (7.5 mm)

Wire Gauge Capacity: 12 to 24 AWG (3.31 to 0.20 mm

2

copper wire only

Torque: 4.4-5.3 inch-lbs (0.5-0.6 N-m)

Module Connection: 8 pin connectors

Wire Strip Length: 0.3" (7.5 mm)

Wire Gauge Capacity: 14 to 24 AWG (2.08 to 0.20 mm

2

copper wire only

Torque: 2 inch-lbs (0.23 N-m)

8. 

CONSTRUCTION

: Metal and plastic enclosure with IP30 

rating. For use only in an approved enclosure.

9. 

MOUNTING REQUIREMENTS

: Mounts onto standard DIN 

style top hat (T) profile mounting rails according to EN50022 

– 35 x 7.5 mm and 35 x 15 mm.

10. 

WEIGHT

: 2 lb 2.5 oz (978.05 g)

3.45

(87.63)

6.00

(152.40)

6.02

(152.98)

3.20

(81.23)

6.84

(173.80)

1.35

(34.3)

5.17

(131.28)

6.84

(173.80)

Modules sold separately.

DIMENSIONS In Inches (mm)

Summary of Contents for DA70A

Page 1: ...esponsibility for damages either direct or consequential that result from the use of this equipment in a manner not consistent with these specifications SPECIFICATIONS 1 POWER REQUIREMENTS The DA70A m...

Page 2: ...1 RS 485 422 port RJ45 connector DA70A0G 1 RS 232 port RJ12 connector 2 RS 485 422 ports RJ45 connectors 5 ENVIRONMENTAL CONDITIONS Operating Temperature Range 40 to 75 C Storage Temperature Range 40...

Page 3: ...ery effective at reducing EMI and increasing relay contact life b If a DC inductive load such as a DC relay coil is controlled by a transistor switch care must be taken not to exceed the breakdown vol...

Page 4: ...from hazardous voltage levels generated by a mains power supply due to single faults Safety extra low voltage circuits shall exhibit voltages safe to touch both under normal operating conditions and a...

Page 5: ...ded that the Cellular Sled be installed into sled slot 1 the topmost sled slot in the carriage of the Gateway Refer to the documentation shipped with your DA 4G LTE CAT4 CAT1 Sled Ethernet Communicati...

Page 6: ...with a new battery To maintain UL rating battery must be replaced with one listed in the Specifications TX 5V 8 1 7 2 TxB TxA 130K 130K 5 TxEN OC RX 130K 5V 130K RxB 4 RxA 3 COMM 6 TxEN OC TX RX 130K...

Page 7: ...0 Group 2 3 Sled 2 RS232 ports and 1 RS485 port Protocol Gateway DA70A0FNNNNNN030 Group 3 3 Sled 2 RS232 ports and 1 RS485 port Adv IIoT Gateway DA70A0FNNNNNN040 Group 4 3 Sled 2 RS232 ports and 1 RS4...

Page 8: ...a breach of the warranty set forth in paragraph a if i the defect is a result of Customer s failure to store install commission or maintain the Product according to specifications ii Customer alters...

Reviews: