background image

POLO 15W LED 
Emergency Bulkhead with 

Microwave Sensor Corridor 

Function 

Installation Instructions 

p.2

For models: POL15LEDEMSCF

Red Arrow Trading

Elsworth House, Herries Road South, Sheffield, S6 1QS

T:

 0800 195 0006     

F:

  0870  043  3946      

E:

 [email protected]      

www.redarrowtrading.com

Further Instructions for Emergency version

 In addition to the above instructions, a secondary “un-switched” live supply should be fed to the luminaire, in line 

   with the “switched” mains supply. This “un-switched” supply MUST be taken from the same phase as the 
   “switched” supply & MUST be wired at the switchboard so that upon test, it is isolated at the same time as the 
    “switched” supply.

 Route to the terminal block & terminate, ensuring correct polarity is observed. 

 Connect the battery supply to the module by joining the connectors, ensuring correct polarity is observed.

 When power supply is reconnected, check the green LED fitted to the luminaire illuminates. This indicates that the 

   batteries are charging. 

 The batteries should be allowed to charge for at least 24 hours before carrying out a full discharge test to check 

   batteries are charging correctly & maintained duration is being achieved.  

OPERATION / MAINTENANCE

 Cleaning should be carried out at regular intervals so as not to impair photometric performance or thermal safety of 

   the luminaire. 

 Excessive & prolonged operation in emergency mode (working from battery supply) will result in lamp ends blackening 

   & reduction of life. 

 Average battery life is four years, after which time they should be replaced with a suitable equivalent. 

 This luminaire MUST be disconnected before the circuit it is installed on is subjected to any high voltage or insulation 

   resistance testing, otherwise irreparable damage will occur to luminaire components. 

 When the lamp operates from the battery supply it will be at a reduced light level, so ensure cleanliness of luminaires is 

   maintained so as not to affect performance.

 To maintain full operational status, spare lamps should be held for immediate changing in case of failure.  

TESTING FOR EMERGENCY LUMINAIRES

 Recommended routine test procedures in line with BS 5266 & BS EN 50172:

Monthly Functional Test

 Simulate a mains supply failure by isolating the circuit (ensuring if it is safe to do so) or by way of a test key switch if 

   fitted into the circuit. 

 Do this for a period of time sufficient to check that the maintained lamp illuminates. 

 Once complete, ensure the normal supply is restored & that the LED charge indicator illuminates. 

 Log result / comments in the Testing Log Book (see next page). 

Annual Discharge Test

 Simulate a mains supply failure by isolating the circuit (ensuring if it is safe to do so) or by way of a test key switch if 

   fitted into the circuit. 