Positioning 

 The luminaire with detector should be sited so that the occupants of the room fall inside the detection patterns shown 

   in the appropriate diagram below.

 The diagram is based on a ceiling mounting height of two and a half metres. Note that the lower the sensor is 

   installed, the smaller the detection range will be. 

 If wall mounted, the detection zone will vary depending on the surroundings but perpendicular reach will be at least 

   ten metres. 

 The area closest to the sensor & also the 

   area more perpendicular to the sensor will 
   have higher sensitivity. 

 The distance quoted are approximate & may 

   vary depending on surroundings. 

 Avoid direct sunlight entering the sensor. 

 Do not site within one metre of forced air 

   heating or ventilation. 

 Do not fix to a vibrating surface. 

 Avoid metallic objects directly in front of 

   the sensor head. 

 These sensor kits are capable of switching 

   / controlling more than one luminaire in a 
   ‘master & slave’ set up. This is done by 
   linking non-sensored fittings (slaves) to the 
   one with the sensor fitted (master) using the 
   live output from the sensor. 

NOTE!

 DO NOT link other fittings containing 

MW sensors together in this way, as it can 

cause false triggering of the sensors. 

Settings

 The following adjustments can be made using the three dials located on the sensor 

unit. DISTANCE, TIME and LUX are adjustable via three rotatable dials.

1.

 

DISTANCE

Rotate the dial to control the diameter of the detection pattern, from one metre 
minimum (fully anti-clockwise) to ten metres maximum (fully clockwise). The LED 
setting indicator will flash to indicate the setting selected, e.g. ten flashes = ten 
metres diameter. 

2.

 

TIME

Rotate the dial to control the length of time the luminaire will stay on after occupancy 
has ceased. From ten seconds minimum (fully anti-clockwise) to 30 minutes maximum 
(fully clockwise). 

DISTANCE  TIME      LUX

MAX MIN

MAX MIN

MAX MIN

• • • •

• •