22W LED Emergency Wilson 

Bulkhead with Microwave 

Sensor Corridor Function

Installation Instructions P.2.

For models: WIL22LEDEMSCF

Testing

The emergency light must be tested and inspected regularly in accordance with local codes of practice. Note: for safety 
reasons, tests should be carried out during daylight hours.

The minimum recommended test schedule is as follows: 
After installation, allow 36 hours to ensure full battery charge, and then 
interrupt the supply; check after 3 hours that the tube is still lighting.
1. Check that the charge indicator LED is working
2. Monthly – interrupt the power supply for a short period and check tube lights
3. Six-monthly – check one hour duration
4. At the end of 3rd year, and annually thereafter – check 3 hour duration: batteries must be replaced when they can no 
longer support 3 hour operation. 
5. Complete record sheet on installation and retain in maintenance file.
6. Update file with on-going test records for inspection by fire officer or other duly authorised person.

Installation and Maintenance Record

Month

Test

Year 1

Year 2

Year 3

Year 4

Year 5

signed

date

signed

date

signed

date

signed

date

signed

date

1

short

2

short

3

short

4

short

5

short

6

1 hour

7

short

8

short

9

short

10

short

11

short

12

short

x

x

x

x

3 hour

x

x

x

x

x

x