background image

T: 0800 195 0006     F: 0870 043 3946      

E: [email protected]      www.redarrowtrading.com

Red Arrow Trading

Elsworth House, Herries Road South 
Sheffield, S6 1QS

LED Maintained Emergency 

Recessed Fitting

Installation Instructions p.2

For models: LFACLED502F

4. 

5. 

6. 

Operation
Non-Maintained

Lamp normally off and battery on automatic charge (LED ‘on’) when A.C. supply is healthy. Solid state circuitry 

automatically switches lamp on when A.C. supply is interrupted. 

Maintained

Emergency lamp normally on, when the supply to Lsw is switched on. The battery is on automatic charge (LED ‘on’). Lamp 
will switch on or remain on if A.C. supply is interrupted. 

Monitoring

Green indicator lamp (LED) normally continuously ‘on’. Indicator lamp goes out if A.C. supply or charger fails. 

Battery

Sealed Nickel-Cadmium rechargeable battery pack. 

Temperature

Performance figures measured at 25 degrees C. 

Fault Finding and Corrective Action
Monitoring LED Not Illuminated

A.C. supply not healthy. Battery not connected. Charger failed. 

Unit Not Meeting Required Emergency Period

May need cycling: Discharge then recharge for 24 hours. Re-test, battery pack may need replacing if emergency duration still 
not met.