LED Maintained Emergency
Recessed Fitting
Installation Instructions p.2
For models: LFACLED502F
4.
5.
6.
Operation
Non-Maintained
Lamp normally off and battery on automatic charge (LED ‘on’) when A.C. supply is healthy. Solid state circuitry
automatically switches lamp on when A.C. supply is interrupted.
Maintained
Emergency lamp normally on, when the supply to Lsw is switched on. The battery is on automatic charge (LED ‘on’). Lamp
will switch on or remain on if A.C. supply is interrupted.
Monitoring
Green indicator lamp (LED) normally continuously ‘on’. Indicator lamp goes out if A.C. supply or charger fails.
Battery
Sealed Nickel-Cadmium rechargeable battery pack.
Temperature
Performance figures measured at 25 degrees C.
Fault Finding and Corrective Action
Monitoring LED Not Illuminated
A.C. supply not healthy. Battery not connected. Charger failed.
Unit Not Meeting Required Emergency Period
May need cycling: Discharge then recharge for 24 hours. Re-test, battery pack may need replacing if emergency duration still
not met.