RM-216 CB.11 Easy Line Documentation  

RDN 10000796 

18 

15.12.2014 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disclaimer 

The contents of this documentation has been verified for correctness and completeness. Nevertheless, errors can not be excluded 

so that we cannot guarantee the correctness of this information. Subject to alterations at any time. 

Summary of Contents for EasyLine RM-216 CB.11

Page 1: ...Operating and Installation Instructions Filter control system RM 216 CB 11 EasyLine ...

Page 2: ...r the replacement of the device fuse 12 7 2 Cleaning the controller 12 7 3 Manufacturing 13 8 Text messages on the display 14 9 Details on the equipment function 15 10 Glossary 16 11 Technical specifications 17 Regulations VDE 0160 EN 60 439 Part 500 EN 50178 2004 108 EC Legend Warning against physical and health hazards or damages to the product and other properties Attention make absolutely sure...

Page 3: ...able laws conditions orders and regulations governing the setting up of electrical equipment must be observed with respect to the installation site Setting of equipment with degree of protection IP00 without covers may only be performed by authorized expert staff when disconnected and whilst observing the local safety and accident prevention regulations The RM 216 C may only be operated in the per...

Page 4: ...bly Wall mounting of the filter controls is not permitted The device may only be mounted to machine parts 4 Step by step installation Supply voltage connection A UL class 2 power supply unit is recommended for the operation of the filter controller with extra low voltage ...

Page 5: ...RM 216 CB 11 Easy Line Documentation RDN 10000796 5 15 12 2014 Solenoid valve connection Connection of expansion modules RM LV8 RM LV16 ...

Page 6: ...accessible for the user and to be marked as disconnecting device for the equipment The wires and cables used for the connection of the controls must be suitable for an ambient temperature of up to 130 C Use shielded cable for all bus lines The shielding must be connected unilaterally to the protective earthing PE Signal cables must not be laid parallel to power cables Tighten all cable glands in u...

Page 7: ...ll up all following parameters P02 P11 in sequence The parameters already displayed can be accessed by repeatedly pressing the button To change the value of a displayed parameter press the ENTER button for at least one second The program then changes from parameter selection mode to parameter setting mode Press the button to increase the parameter value displayed in increments Press the button to ...

Page 8: ...RM 216 CB 11 Easy Line Documentation RDN 10000796 8 15 12 2014 ...

Page 9: ...ve test 2 Input test 3 5 For manufacturer purposes only Off 0 0 5 P09 P09 Ser run hour Service operating hours P10 P10 Ser run h AL Service operating hours alarm 0 h 0 25000 h P11 P11 Ser r h Code Service operating hours code 0 0 250 Number of all valves connected to the RM 216 CB and to the expansion modules The parameter is used by the equipment for internal monitoring purposes and need only be ...

Page 10: ...ning perform the following steps Remove the factory fitted wire jumper on input E1 E2 terminals 10 11 Connect a free auxiliary contact make contact of the fan contactor to terminals 10 and 11 The input should be operated in isolation Set parameter P05 Down time cleaning cycles to the required number of cycles see also section 5 2 Setting parameters If the fan is switched on the contact on E1 E2 cl...

Page 11: ...gnet coil faulty Replace coil No down time cleaning Parameter P05 0 down time cleaning cycles Set parameter P05 Down time cleaning cycles to a different value There is no signal from the fan control Activate signal to input I1 I2 Cleaning ineffective Interval time too long Set parameter P02 Interval time to a lower value Pressure too low Set pressure to 6 8 bar min 5 bar Set parameter P02 Interval...

Page 12: ...the cover Pull off the transparent plastic cap of the fuse holder see picture Pull the fuse from the holder Insert the new fuse into the holder Use only the UL listed fuses that are mentioned in chapter 11 Technical specifications on page 17 Shut off after one hour at 135 of the nominal current Place the transparent plastic cap of the fuse holder Position the housing cover on the bottom part of th...

Page 13: ...as manufactured by RECO Gesellschaft für Industriefilterregelung mbH Junkersring 11 D 53844 Troisdorf Germany 49 0 2241 39704 0 for Norbert Heinrich Automatisierungstechnik Feldstraße 16 32549 Bad Oeynhausen Germany Tel 49 0 5734 6002318 Please contact Norbert Heinrich Automatisierungstechnik to obtain technical support ...

Page 14: ...and I2 Stand By Val No The control has been enabled via input E1 E2 and stopped via input D1 D2 Cleaning Off Val No The control has been enabled via input E1 E2 and started via input D1 D2 Cleaning On Val No Down time cleaning active DTC Cleaning ON 000 Pcs The alarm switching point for the service hours counter has been exceeded Call Service Val No A connected O module RM LV8 or RM LV16 is out of...

Page 15: ...r elements terminals 8 9 If automatic components for dust removal extractor elements are fitted these need to be in operation during cleaning and during down time cleaning Connect the cut out for controlling these drive units to the isolated output S1 S2 Alarm relay output A1 A2 A3 terminals 5 6 7 As soon as the supply voltage is present on the RM 216 CB relay contact A1 A2 closes terminals 5 6 an...

Page 16: ...xtractor element on and off I O module Input output module module for the input and output of control signals Operation mode Status of the RM 216 CB in which the equipment is ready for operation Parameter selection mode Status of the RM 216 CB in which the equipment operator can select a parameter Parameter setting mode Status of the RM 216 CB in which the equipment operator can set a parameter Pa...

Page 17: ...pulse mode 42 Watt Outputs for expansion modules Supply voltage and pulse wires to the expansion modules Fuses F1 230 V M 0 2 A 250 V 5 x 20 mm Type Bell 5MT 200 mA ESKA UL 521 010 F2 110 V M 0 3 A 250 V 5 x 20 mm Type Bell 5MT 300 mA ESKA UL 521 012 Extra low voltage Fusing via PTC resistor Electrical connections Screw terminals Permissible wire gauge single wire 22 16 AWG 0 5 1 5 mm Flexible 22 ...

Page 18: ... 18 15 12 2014 Disclaimer The contents of this documentation has been verified for correctness and completeness Nevertheless errors can not be excluded so that we cannot guarantee the correctness of this information Subject to alterations at any time ...