7.1 Instructions for the replacement of the device fuse
Switch off the supply voltage of the device at the in-line fuse element or main switch and take
precautions against reactivation.
Check whether main supply line carries no voltage.
Unscrew the six screws of the RM-216 CB housing cover and remove the cover.
Pull off the transparent plastic cap of the fuse holder (see picture).
Pull the fuse from the holder.
Insert the new fuse into the holder.
Use only the UL listed fuses that are mentioned in chapter 11 “Technical specifications“ on page
17.
(Shut-off after one hour at 135% of the nominal current.)
Place the transparent plastic cap of the fuse holder.
Position the housing cover on the bottom part of the housing and tighten the six screws evenly.
Switch on the supply voltage again.
7.2 Cleaning the controller
Wipe only with a damp cloth if outside of device is soiled.