9
REC Indovent AB, Box 37, SE-431 21 Mölndal, Sweden
|
tel. +46 31 675500
|
www.rec-indovent.se
OPERATION & MAINTENANCE
Air handling unit RT 400S-EC
REC-E08.10
Regulation accuracy, afterheater
•. In.the.main.menu
•. Press.arrow.down.
.or.up.
.until..
. “MANUAL.SETTINGS”.appears.in.
. the.display
•. Confirm.by.pressing.
.
•. Press.arrow.down.
.once.until.
. “HTR.SPAN”.appears.in.the.display
•. Confirm.by.pressing.
.
•. The.current.setting.appears.in.the.display...
The.change.mode.lamp.
.comes.on..Use.
the.arrows.up/down. .to.change.the.value.by.
. 1-5.°C..State.the.deviation.from.set.room.temperature..
in.“SET.TEMP”.before.the.afterheater..is.activated..(4.
°C.is..
recommended,.e.g.:.you.require..
21.°C.indoors...So.you.set.this.value.to.4.)
•. Confirm.your.selected.setting.by.pressing.
.
•. Press.the.menu.button.
.to.go.back.
. to.the.main.menu.
Heat recovery on or off
•. In.the.main.menu.
•. Press.arrow.down.
.or.up.
.until
“MANUAL.SETTINGS”.appears.
•. Confirm.by.pressing.
.
•. Press.arrow.down.
.twice.until
“HEAT.REC”.appears.in.the.display.
•. Confirm.by.pressing.
.
•. The.current.setting.appears.in.the.display..
The...lamp.change.mode.lamp.
.comes.on..Use...
the.arrows.up/down.
.
to.choose.from.
on/off/auto.(ON=.heat.recovery.always.on,.
. OFF=.heat.recovery.always.off,...
.
AUTO=.optimises.the.function...
.
guided.by.selected.temperature.settings).
•. Confirm.your.selected.setting.by.pressing.
..
•. Press.the.menu.button.
.to.go.back
to.the.main.menu.
Setting summer bypass (bypass)
(Cooling.recovery:.Bypass.closes.to.reuse.subnormal..
temperature.when.the.outdoor..temperature..exceeds.
the.settings.SET.TEMP.+.REC.SPAN).
•. In.the.main.menu.
•. Press.arrow.down.
.or.up.
.until.
. “MANUAL.SETTINGS”.appears.:..
•. Confirm.by.pressing.
...
•. Press.arrow.down.
.three.times.until
. “REC.SPAN”.appears.in.the.display..
•. Confirm.by.pressing.
..
•. The.current.setting.appears.in.the.display..The...lamp.
change.mode.lamp.
.comes.on..Use.the.arrows.
up/down.
.
to.change.the.value.by.1-5.°C..Specifies.
the.deviation.from.the.set.room.temperature..in.“SET.
TEMP”.before.the.bypass.opens.
. (3.°C.is.recommended,..e.g.:.you.
. require.21.°C.indoors.
. So.you.set.this.value.to.3.)..
•. Confirm.your.selected.setting.by.pressing.
..
•. Press.the.menu.button.
.to.go.back
to.the.main.menu.
MANUAL
SETTINGS
HTR SPAN
MANUAL
SETTINGS
HEAT REC
MANUAL
SETTINGS
REC SPAN
HTR SPAN
4
HEAT REC
AUTO
REC SPAN
2