Maintenance/Servicing
Renew filter
There.are.two.filters.in.the.Temovex.unit:.an.exhaust.air.
filter.and.an.outdoor.air.(fresh.air).filter..These.filters.should.
be.replaced.once.a.year.as.a.minimum..The.filters.must.
not.be.washed.-.they.must.be.replaced.with.new.ones..
Contact.REC,.+46.31.67.55.00,.or.see.www.recvent.se..
to.order.filters..
-. Switch.off.the.power..supply.to.
the.unit.using.the.main.switch..
-. Open.the.door.on.the.unit..
-. Undo.the.long.cover..Take.hold.
of.the.filter.and.pull.the.front.
. edge.backwards.and.down..
-. Behind.the.internal.cover.is
. the.outdoor.air.(fresh.air).filter..
Remove..this.as.well..
-. If.necessary,.clean.all.
. accessible..surfaces..
-. Fit.the.new.filters.in.reverse.order..(The.blue,.exhaust.air.
filter,.is.fitted.in.the.front)
-. Refit.the.cover.
-. Close.the.door.to.the.unit
-. Switch.on.the.power..
The. unit. can. be. used. if. the. filters. are. dirty,. but. its.
performance.. will. be. impaired.. Energy. consumption. will.
increase.and.heat.recovery.will.be.reduced.
Note:.When.heat.recovery.is.reduced,.there.is.a.risk.of.
greater. energy. consumption. to. power. the. afterheater.
during..cold.periods..The.unit.must.not.be.used.without..
filters... This. may. cause. damage. to. the. fans. and. heat.
exchanger..
......
. . The.unit.must.not.be.used.without.filters..This.may
. . cause.damage.to.the.fans.and.heat.exchanger.
New. filters. can. be. ordered. from.
www.recvent.se
. or. by.
calling. REC,. +46. 31. 67. 55. 00.. REC. also. provides. a.
subscription..option.for.filters..All.you.have.to.do.is.decide.
how.often.you.want.to.replace.your.filters,.we.do.the.rest..
The.filters.will.be.sent.to.your.home.by.post.
-.It.really.couldn’t.be.easier!.
Subscribe.at.
www.recvent.se
.today!.State.the.production.
number.of.your.unit.and.we.will.give.you.your.first.batch.
of.filters.free.(subject.to.subscription.to.our.service.on.the.
website).
Resetting the filter alarm
•. In.the.main.menu...
•. Acknowledge.the.filter.alarm.by.pressing.
..The.
text.in.the.display.and.the.lamp.
.goes.out..Recurs.at.
7-day.intervals..
•. Press.arrow.down.
.or.up.
.until.
. “MANUAL.SETTINGS”.appears
. in.the.display.
•. Confirm.by.pressing.
..
•. Press.arrow.down.
.or.up.
.until
. “FILTER.RESET”.appears.in.the.display.
•. Confirm.by.pressing.
..
•. The.display.shows:.“NO”..Use.the.arrows.
.
to...
. select.“YES”.(replacement.interval.every.12.months).
•. Confirm.your.selected.setting.by.pressing.
..
•. Press.the.menu.button.
.to.go.back.to.
. the.main.menu.
MANUAL
SETTINGS
FILTER
RESET
Cleaning the fans
-. Switch.off.the.
. power.using.the.
. main.switch
-..Open.the.door.
. on.the.unit
-. Remove.both.
. covers.
-. Undo.the.quick-
. action.contact.
. on.the.fan.and.
. pull.out.the.fan
. coil..(Take.one.
. fan.at.a.time)
-. Clean.the.impeller.using.a.brush.or.compressed.air.
-. Refit.the.fans.in.reverse.order.
-. Refit.the.covers.
-. Close.the.door.to.the.unit.
-. Switch.on.the.power.using.the.main.switch.
......
. . Under.no.circumstances.must.the.motors.be
. . cleaned.under.running.water.