OPERATION & MAINTENANCE
Air handling unit RT 400S-EC
REC-E08.10
Cleaning the fans
-. Switch.off.the.power.using.the.main.switch.
-.. Open.the.door.on.
. the.unit.
-. Remove.both.covers..
-. Undo.the.quick-..
action.contact...
on.the.fan.and...
pull.out.the.fan.
coil..(Do.one.fan.
at.a.time).
-. Clean.the..
impeller.using..
a.brush.or...
compressed.air..
-. Refit.the.fans.in.
reverse.order..
-. Refit.the.covers..
-. Close.the.door.to.the.unit
-. Switch.on.the.power..
using.the.main.switch..
.......
. ..
Under.no.circumstances.
. ..
must.the.motors.be.
. ..
cleaned.under.
. ..
running.water.
Cleaning the heat exchanger
-. Switch.off.the.power.using.the.main.switch..
-. Open.the.door.on.the.unit
-. Remove.both.fans.as.described.above..
-. Open.the.service.hatch.at..
the.bottom.of.the.cabinet..
-. Remove.the.red.plug.at.the.
bottom.of.the.unit,.the.con-
densation.drain...
NB:.Remember.which.side..
it.should.be.on..
-. Flush.the.heat.exchanger...
with.hot.water...
Note: If the unit is fitted with a condensation
evaporator unit (kavk), a wet vac is used to deal
with the rinse water.
.A.degreasing.agent.may.be.
required.if.the.heat.exchanger.is.very.dirty....
.....
Must.be.of.a.type.which.is.not.aggressive.
. .
to.aluminium...
-. Where.necessary,.repeat.the.procedure.once.more..
-. Refit.the.red.plastic.plug..(This.must.be.on.the.same.
side.as.the.filters.).
-.. Refit.the.inspection.hatch.and.fan.motors.in.reverse.
order..
. .
Take.care.to.make.sure.the.fan.motors.are.not/do.
. .
not.get.wet.when.restarting.the.unit-.This.could.
. .
be.fatal!.
-. Close.the.door.to.the.unit.
-. Switch.on.the.power.using.the.main.switch.