background image

REC Peak Energy Series Installation Manual - UL 1703
Ref: NE-06-03-M 

Rev M - 03.2014

8

vii)  short side mounting using clamps

Mounting utilizing clamps on the two short sides of the panel have been found to be in compliance with ul 1703 requirements for a maximum 

design load of 33.4 lbs/ft² (1600 Pa) (fig. 9).

• 

fix the panels so that the lower short side of the frame is supported by the mounting structure (to reduce risk of damages due to sliding snow 

load).

• 

Clamps must be secured between a distance of 4.9 and 9.8 inches (125 – 250 mm) from the panel corner to the clamp edge.

• 

Tightening torque must be tightened to 16 ft-lbs (21.7 Nm).

• 

The minimum distance between the end clamp and the end of the rail is 1 in (25 mm).

• 

Mechanical load must not exceed 33.4 lbs/ft (1600 Pa).

• 

The overlap between support rail and frame must be a minimum of 1/4 in (6 mm).

In areas of snow build-up, panels can be subjected to forces in excess of the stated limit even when snow depth does not appear 

extreme, causing damage to the framework.  If the installation is likely to be affected, further suitable panel support is recommended 

on the lower row of panels.

Ensure the drainage holes are not covered by the mounting structure.

Where common grounding hardware (nuts, bolts, star washers, split-ring lock washers, flat washers and the like) are used to attach 

a listed grounding/bonding device, the attachment must be made in conformance with the grounding device manufacturer’s 

instructions.

vi) long side mounting using clamps

Mounting of reC Peak energy panels utilizing clamps on the two long sides of the panel have been found to be in compliance with ul 1703 require-

ments for a maximum design load of 75.2 lbs/ft² (3600 Pa) (fig. 8).

• 

Clamps must be secured between a distance of 

8.2 in to 16.4 in (208 mm - 416 mm)

 from the corner of the panel (measured from the mid-

point) to the clamp edge.

• 

Tightening torque must be tightened to 9 ft-lbs (12 Nm).

• 

The distance between the end clamp and the end of the rail must be minimum 1 in (25 mm).

fig. 8:  long side mounting

fig. 9:  short side mounting

8.2”-

16.4”

1”

1”

4.9”-

9.8”

viii) Grounding

a panel with exposed conductive parts is considered to be in compliance with ul 1703 only when it is electrically grounded in accordance with the 

instructions presented below and the requirements of the National electrical Code.  grounding is achieved through securement to the panel frame 

of the following ul listed grounding Clips / lugs in combination with the reC Peak energy panel(s).

• 

suitable grounding lugs must be used: listed (kDer) ilsCo, gbl-4DbT (tin plated) (e34440).

• 

grounding cable size should be between 4 - 14 awg (2.1 mm² 

 

- 21.2mm²).

• 

attach grounds to the grounding holes in the panel frames. 

• 

fix lug to the frame using a star washer (#10) and lock nut (#10), ensuring a conductive connection (fig. 10).  Tighten according to manufacturer’s 

instructions.

fig. 10: recommended grounding

Cross section [AWG]

Type Torque [in-lbs]

4 - 6

stranded

35

8

stranded

25

10 - 14

stranded / solid

2.8

To avoid galvanic corrosion, stainless steel fastening materials are preferred, however galvanized or hot dipped zinc plated fasteners 

are equally suitable. 

grounding 

cable

star washer

grounding lug dimensions and wire fastening torque for 

gbl-4DbT

Summary of Contents for REC235 Series

Page 1: ...InstallatIon manual rec Peak energy series For the installation of panels certified according to UL 1703...

Page 2: ...ireMeNTs 4 meCHanICal InstallatIon 5 fire guiDeliNes 5 orieNTaTioN 5 eNviroNMeNTal faCTors 5 PaNel HaNDliNg 5 mountInG tHe panels 6 PaNel iNsTallaTioN 6 i rail sPeCifiCaTioNs 6 ii ClaMP sPeCifiCaTioN...

Page 3: ...w icons which highlight important information or notes Indicates potential for damage to the array or property or personal safety Indicates important notes on best practice to help with the installati...

Page 4: ...requirements of the NeC the values of isC andvoC marked on the panels must be multiplied by a factor of 1 25 when determining component voltage ratings conductor ampacities overcurrent device ratings...

Page 5: ...th local authorities for applicable regulations concerning setbacks or other placement restrictions that may apply for roof mounted arrays The use of DC ground fault interrupters is recommended This m...

Page 6: ...rails fig 2 Thickness of walls for mechanical connections min 0 156 in 4 0 mm Thickness of walls exposed to buckling load min 0 08 in 2 0 mm Moment of inertia for profile area about x x min array moun...

Page 7: ...1703requirementsforamaximumdesignloadof75 2lbs ft 3600Pa fig 5 when mounting using mounting holes the frame and panel edge must be supported by two transverse rails fig 1 p 8 of aluminium or galvanize...

Page 8: ...reC Peak energy panels utilizing clamps on the two long sides of the panel have been found to be in compliance with ul 1703 require ments for a maximum design load of 75 2 lbs ft 3600 Pa fig 8 Clamps...

Page 9: ...ical integrity of the cables is intact bonding points to ground are tight secure and free from corrosion which could break the continuity between the panels and ground ReCyClInG reC has made every eff...

Page 10: ...normal operation This will help to shield the panel from direct water spray InstallatIon InstRuCtIon i system installation all cables used for the installation must have sufficient length and slack t...

Page 11: ...of the indicated values of isC voC and PMPP under standard test conditions sTC values at sTC airmass aM 1 5 irradiance 1000 w m cell temperature 25 C 77 f at low irradiance of 200 w m aM 1 5 and cell...

Page 12: ...2013 i 2 addition of low watt classes 214 230wp for ul records 04 2013 i 3 update of tightening torque for clamping and mounting holes 06 2013 i 4 update of torque rating for long side clamping and m...

Page 13: ...RECSoLaRPtE Ltd 20tuasSouthavenue14 Singapore637312 Singapore tel 6564959228 Mail post recgroup com www recgroup com...

Reviews: