COMMISSIONING PROCEDURE

Once the fire is installed and operational the installer must check for spillage. Carry out the

lighting procedure and turn the fire to high. Allow to warm up for 10 minutes and then using a

smoke match set 25mm down and 25mm inside of the fire opening run the match across the

width of the opening to check that all of the smoke is drawn away.
Repeat the test with doors and windows to the premises open and closed, and with any extractor

fans in the same room or adjacent rooms running on high. The fire should continue to clear its

combustion products. Also operate any other flued appliances in the same or neighbouring rooms

and ensure they continue to function satisfactorily as multiple flues can work against one another.
If spillage is detected during this procedure it could indicate a faulty flue or lack or ventilation. If

the problem cannot be rectified immediately, disconnect the appliance, and advise the customer

not to use the appliance until the problem has been resolved.
The customer should always be advised of the need for regular servicing and checks to ensure

the continued clearance of combustion waste products.

NOTE: 

Care must be taken to ensure that any return air register exhaust system does not

adversely affect the operation of the appliance or draught of chimney or flue.

WARNING

“DO NOT place articles on or against this appliance.“
“DO NOT use or store flammable materials near this appliance.”
“DO NOT spray aerosols in the vicinity of this appliance while it is in operation.

13

Summary of Contents for Magiglo 1000

Page 1: ...ATING MANUAL The Magiglo series of decorative fires are suitable to be installed into a masonry or approved prefabricated fireplace and are designed to operate with Natural and Propane gases only Appr...

Page 2: ...en installed in an outdoor setting 4 Limit of Liability The warranty provided under this warranty is limited to replacement or repair of the Real Flame Gas Burner only at our option To the extent perm...

Page 3: ...EGISTER OR EXHAUST SYSTEM DOES NOT ADVERSLEY AFFECT THE OPERATION OF THE APPLIANCE OR DRAUGHT OF CHIMNEY OR FLUE DO NOT MODIFY THIS APPLIANCE THIS APPLIANCE IS DESIGNED TO OPERATE WITH LUMINOUS FLAMES...

Page 4: ...g Procedure 13 Typical Type 1 Installation to existing chimney 14 Type 1 Installation into Victorian Federation grate 15 Typical Type 2 Installation of Prefabricated Fire Box into existing chimney 16...

Page 5: ...to test point 2 Adjust pilot pressure screw wind screw fully in then wind out 2 1 2 full turns for 400 540 750 models only 3 Adjust maximum burner pressure screw wind max pressure screw out 2 full tur...

Page 6: ...6 DIMENSIONS Magiglo 320 Burner PLAN RHS LHS B A C E FRONT D A B C D E 147 110 341 317 84 Magiglo 360 PLAN FRONT RHS LHS B A C D E A B C D E 199 110 210 360 155...

Page 7: ...7 DIMENSIONS Magiglo 400 Burner PLAN RHS LHS B A E FRONT D C A B C D E 201 103 433 328 148 Magiglo 540 PLAN RHS LHS B A C D E FRONT A B C D E 201 103 570 395 148...

Page 8: ...8 DIMENSIONS Magiglo 750 PLAN RHS LHS B A C D E FRONT A B C D E 201 102 783 606 148...

Page 9: ...9 DIMENSIONS Magiglo 1000 0 PLAN RHS LHS B A C D E FRONT A B C D E 201 103 1029 692 148 Magiglo 540 Double Vision Burner PLAN RHS LHS FRONT D C B A E A B C D E 283 225 540 403 148...

Page 10: ...iving area to spillage of combusted products The flue or chimney should be tested and proven to have an adequate updraught sufficient to remove all waste products of combustion Refer to Commissioning...

Page 11: ...se to the pilot position 2 Keep knob depressed and turn the knob anticlockwise toward the until you hear a click If the pilot lights continue to depress knob for 20 seconds and release If pilot goes o...

Page 12: ...n to the off position 12 LIGHTING INSTRUCTIONS Millivolt Option 1 STOP Read the safety information 2 Push in gas control knob and turn to PILOT 3 NOTE Control knob cannot be turned from OFF to PILOT u...

Page 13: ...they continue to function satisfactorily as multiple flues can work against one another If spillage is detected during this procedure it could indicate a faulty flue or lack or ventilation If the prob...

Page 14: ...products come into the room Smoke match spillage test 225mm DIA GAS COWL Minimum fireplace depth shall be 450mm for all models Maximum fireplace opening height for all models except 1000 shall be 600m...

Page 15: ...AP COAL PLACEMENT IMPORTANT ALL AIR GAPS ON THE UNDERSIDE OF THE BASE GRATE MUST BE SEALED Place base layer of coals as above and randomly stack remainder allowing for gaps Place Air Tubes 5mm behind...

Page 16: ...HIMNEY FOR INSTALLATION OF FIRE BOX REFER TO MANUFACTURER S SPECIFICATIONS This is a guide only Installation of Fire Box must be carried out to manufacturers specifications ATTENTION Existing Chimney...

Page 17: ...to be followed by the engineer can be found under Service Instructions contained within this leaflet 4 For safe operation of your Magiglo the following annual checks should be carried out Confirm that...

Page 18: ...djust burner aeration caps to fully open ULPG setting Tighten screws after adjusting 14 Remove gas pipe from injector 15 Remove injector and replace with correct size 16 Refit injector and retighten g...

Page 19: ...5 03N S I T ODS Pilot Assembly Natural Gas 03P S I T ODS Pilot Assembly Propane Gas 04 1 2 Male to 1 2 Copper Union 05 1 2 to 3 8 Hex Nipple 06 5 16 90O Union Elbow 07 1 4 Nut and Olive 08 Injector Ho...

Page 20: ...elong hotmail com au Sydney NSW Showroom 546 Pacific Highway Chatswood NSW 2067 Ph 02 8905 0189 Fax 02 8905 0192 E mail info realflame com au Miranda NSW Showroom 36 Kareena Rd Miranda NSW 2228 Ph 02...

Reviews: