ICENI/AI-04
7
FIELD WIRING TERMINATION
7.1
Terminal & Connector Layout
CHANNEL
TERMINAL
DESCRIPTION
1 R+
2 R-
3 LOOP
1
4 -
CHANNEL
TERMINAL
DESCRIPTION
5 R+
6 R-
7 LOOP
2
8 -
CHANNEL
TERMINAL
DESCRIPTION
9 -
10 LOOP
11 R-
3
12 R+
CHANNEL
TERMINAL
DESCRIPTION
13 -
14 LOOP
15 R-
4
16 R+
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
(
-
: not connected)
7.2
Wiring Schematic
R+
LOOP
RTD
ICENI/AI-04
R-
Notes:
o
For 3-wire operation, wiring for R+, R- and LOOP must be the same length and
cross sectional area (CSA).
o
For 2-wire operation, R- and LOOP should be linked at the ICENI/AI-04
module terminals. Wiring for R+ and R- must be the same length and cross
sectional area (CSA).
Pub_3645
Page 16 of 25