SAFETY CONTROL
All the control devices are tested in the factory before the equipment
is shipped. Their operation is described in the following paragraphs.
Safety check is carried out by the control unit through the values
measured by the probes:
- condenser temperature probe
- water temperature probe
- evaporator temperature probe
Activation of the dehumidification function
The dehumidification function is activated by closing the terminals
relative to the “external consent/humidistat”, see chapter
“3 -
Electrical connections”.
In the start-up phase, the unit activates the fan and, after a set
time, the compressor, in sequence. The compressor (and therefore
dehumidification) is excluded if the pre-treatment water exceeds
30°C.
COMPONENTS
Compressor
Hermetically sealed with a bipolar single-phase asynchronous
motor coupled with an alternative single cylinder compressor.
Condenser temperature probe
NTC sensor which measures the temperature of the air after the
condenser.
Water temperature probe
CONTROLLI DI SICUREZZA
Tutti i dispositivi di controllo sono collaudati in fabbrica prima
della spedizione dell’apparecchiatura. La loro funzionalità viene
descritta nei paragrafi successivi.
I controlli di sicurezza vengono effetuati dalla centralina tramite
i valori rilevati dalle sonde:
- sonda temperatura condensatore
- sonda temperatura acqua
- sonda temperatura evaporatore
Attivazione della funzionalità di deumidificazione
L’attivazione della funzionalità di deumidificazione avviene
attraverso la chiusura dei morsetti relativi al “consenso esterno/
umidostato”, vedi cap.
“3 - Collegamenti elettrici”.
In fase di avviamento, l’unità attiva in sequenza il ventilatore e
dopo un certo ritardo il compressore. Il compressore (e quindi
la deumidificazione) viene escluso se l’acqua del pretrattamento
supera i 30°C.
COMPONENTI
Compressore
Di tipo ermetico con motore asincrono monofase bipolare
accoppiato ad un compressore monocilindrico alternativo.
Sonda di temperatura condensatore
Sensore NTC che rileva la temperatura dell’aria dopo il
condensatore.
Sonda di temperatura acqua
Table G – technical characteristics
Tabella G - Caratteristiche tecniche
Technical specifications
Specifiche tecniche
Condensed humidity
Umidità condensata (26°C - 65%)
l/day
l/giorno
42
Nominal electrical power
Potenza elettrica nominale
W
515
Nominal air flow
Portata aria nominale
m
3
/h
500
Min performance (Speed 1)
Prevalenza minima (Vel.1)
Pa
12
Med performance (Speed 2)
Prevalenza media (Vel.2)
Pa
52
Max performance (Speed 3)
Prevalenza massima (Vel.3)
Pa
68
Refrigerant
Refrigerante (R134a)
gr
300
Overall dimensions
Ingombri della macchina
Height
Altezza
mm
292
Width
Larghezza
mm
635
Depth (+ switchboard)
Profondità
mm
825
Weight
Peso
kg
47
Machine packaging
Imballi macchina
Height
Altezza
mm
325
Width
Larghezza
mm
675
Depth
Profondità
mm
830
Summary of Contents for RNW 508-CS