![RDZ CHR 100 User Manual Download Page 45](http://html1.mh-extra.com/html/rdz/chr-100/chr-100_user-manual_1424652045.webp)
45
Description
Descrizione
Min
Max Step
Def.
fcs
fce
Summer Free Cooling Enabling
Abilitazione Free Cooling Estivo
NO - SI
SI
fcU
fci
Winter Free Cooling Enabling
Abilitazione Free Cooling Invernale
NO - SI
SI
fpp
fpp
Pre/Post Free Cooling set
Set Free Cooling Pre/Post
PRE - POST
POST
Ts1
Ts1
Damper Stroke Total Time (sec.)
Tempo Totale corsa serranda (sec.)
0
1000
1
35
Ts2
Ts2
Damper modulation time (sec.)
Tempo di modulazione serranda (sec.)
0
180
1
1
Ts3
Ts3
Damper waiting time (sec.)
Tempo di attesa serranda (sec.)
0
180
1
25
1Fc
1Fc
Room Hysteresis FC Activation (°C)
Isteresi Ambiente Attivazione FC (°C)
0.1
10.0
0.1
0.5
dfc
dfc
Delta Temperature Free Cooling set (°C)
Set Delta Temp. Free Cooling (°C)
0.0
20.0
0.1
6.0
IMPOSTAZIONI FREE COOLING
FREE COOLING SETTINGS
x 3
x 2
x 5
La funzionalità Free-Cooling attiva è contrassegnata
a display dalla comparsa dell’icona
.
The active Free-Cooling feature is marked on the
display by the appearance of the
icon.