Standard HVAC System 

G   Fan  

W1 Heat Stage 1 

Y1 Compressor Stage 1 

R   24VAC  Return 

C   24VAC Common 

Thermostat Connection

 

Y2  Compressor Stage 2 

W2 Heat Stage 2 

For single transformer systems 

connect R wire to either RC or RH 

terminal. 

 

For systems with separate heating 

& cooling transformers, connect 

heating R to RH and cooling R to 

RC.  

NOTE! the RC=RH jumper 

must be CUT on the thermostat 

board.

 

 

Standard Gas/Electric HVAC System Wiring 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat Setup:   

Standard Gas/Electric HVAC Systems  

For Single Stage Heat/Cool Systems: 

Go to the Menu screen by pressing and holding the FAN button for 5 seconds 

Press the down arrow to select the 

SYSTEM

 menu and press Select.   

Set the following: 

 

SYSTEM TYPE:

   Set to 

STANDARD

 

FAN TYPE:

   Set to 

GAS 

for typical gas furnace (fan is controlled by the furnace) 

 

Set to 

ELECTRIC

 for electric heat  (fan on with heat call) 

 

For Two Stage Heat/Cool Systems:  

Go to 

ADVANCED SYSTEMS SETTINGS 

menu.

 

From the 

Setup menu

 screen, press and hold the Fan and Down arrow buttons 

 for 5 seconds.  Use the Down arrow button to select the following:    

 

2ND

 

STAGE HEAT ENABLE:   

 Enable second stage heating output 

 

If a single stage heating system, leave this set to 

N

   

If a 2 stage heating system, set to 

Y

 to enable.  

2ND STAGE COOL ENABLE:  

  Enable second stage cooling output 

 

If a single stage cooling system, leave this set to 

N

 

If a two stage cooling system, set to 

Y

 to enable. 

 

 

Default Thermostat Setup: 

Type: Standard HVAC 

Fan: Gas Heat 

1 Stage heating 

1 Stage cooling 

 

No Setup change required for 

this configuration 

Thermostat back 

 

Y2

 

Y1

 

G

 

RC

 

C

 

RH

 

W1

 

W2

/O

   

Typical thermostat wiring colors.  

Caution: verify that original wiring 

matches. Colors may be different.  

Blue 

Black/Brown 

Red 

White 

Orange 

Yellow 

Green 

C wire is not required for 

battery operation. 

 

C wire is required for 24VAC 

operation. 

   

Internal RC=RH jumper 

 

DCN: 140-02121-06 

Page 5 

 

Summary of Contents for TBZ48

Page 1: ...line batteries and replace in complete sets 2 or 4 at a time with new batteries Z Wave Operation when Battery Powered Important Note If the thermostat is installed on a Z Wave network while it is batt...

Page 2: ...nd RH Connections Typical installations will have a common heating and cooling system 24VAC transformer in the HVAC system For these systems there is only one R wire and it can connect to either the R...

Page 3: ...sh all the excess wiring back into the wall RC RH JUMPER Cut jumper to allow connection of separate RC and RH wires Y2 Y1 G RC C RH W1 W2 O Y G R C Connect the wires as marked from the HVAC system to...

Page 4: ...e base Install the batteries if the thermostat is not 24VAC powered no common C wire Open the front door and install 2 or 4 AA alkaline batteries Turn on the power at the HVAC system or breaker panel...

Page 5: ...heat fan on with heat call For Two Stage Heat Cool Systems Go to ADVANCED SYSTEMS SETTINGS menu From the Setup menu screen press and hold the Fan and Down arrow buttons for 5 seconds Use the Down arr...

Page 6: ...ire to the thermostats W2 O terminal For Two Stage Heat Cool Systems Go to ADVANCED SYSTEMS SETTINGS menu From the Setup menu screen press and hold the Fan and Down arrow buttons for 5 seconds Use the...

Page 7: ...Control Screen To change the thermostats HVAC system settings select the Menu Screen and then select the SYSTEM menu Follow instructions below to access the SYSTEM menu Note To conserve battery life t...

Page 8: ...h Cooling or with Heating When SYSTEM is selected in the Menu options the following setup options will be displayed in the text line Use the UP Down arrow buttons to scroll to the desired setting Pres...

Page 9: ...ting comes on when cooling is expected or vice versa change the Change Over Type to the opposite setting Advanced System Settings Menu The Advanced System Settings Menu provides for addition system se...

Page 10: ...15C Sets the minimum cooling setpoint value Will not ramp or accept setpoints lower than this minimum Heat Blower Off Delay Range 0 90 seconds Default 0 off Sets the system blower delay off time afte...

Page 11: ...a from setpoint that stage 1 cooling stops Stage 1 turns off at setpoint Delta Stage 1 Cooling Stage 2 On Threshold Range 2 to 8 degrees Default 2 Sets the delta from setpoint that stage 2 cooling sta...

Page 12: ...em is ON and cooling blinking System is ON and heating Minimum Run Time MRT delay is active blinking System is ON and cooling Minimum Run Time MRT delay is active Temperature Setting Warmer Cooler Fan...

Page 13: ...mp Mode Emergency Heat Heat E An additional system mode Heat E for Emergency Heat will be displayed if the HVAC System Type is set to Heat Pump If there is a compressor failure with the Heat Pump syst...

Page 14: ...ee separation is maintained between the heating and cooling setpoints The same is true for raising the heating setpoint above the cooling setpoint The thermostat will push the cooling setpoint up to m...

Page 15: ...n mode Fan Modes Auto Fan automatically operated by the HVAC system normal setting On Manual Fan mode Fan stays on until mode is changed back to Auto independent of the heating or cooling system opera...

Page 16: ...ptions SETUP User preference settings SYSTEM Thermostat HVAC system settings ZWAVE Z Wave network install or remove CLOCK Setting the thermostat time and day INFO Displays thermostat version and setup...

Page 17: ...s only Select fan type GAS typical default setting or ELECTRIC CHANGE OVER TYPE Heat Pump systems only Select the Changeover type Changeover WITH COOL typical default setting Changeover WITH HEAT See...

Page 18: ...tpoint room temperature or you change the setpoint to a temperature that would satisfy the call until the MRT expires Changing the Mode to OFF will cancel the MRT and the system will turn off immediat...

Page 19: ...network while powered by 24VAC it will be enrolled as an always listening device and can act as a router node in the Z Wave network Caution Once installed in a Z Wave network if you change how the the...

Page 20: ...ick the Manage Devices button 2 In the Manage Devices Assistant click Lights Thermostats more 3 Select the RCS Battery Powered Thermostat Model TBZ48 from the drop down list then click the Continue bu...

Page 21: ...status line Press Select to install in the network Wait until SUCCESS or FAILED is shown on the status display 8 Press Done on the Thermostat to exit the ZWAVE screen 9 Press Done on the Thermostat ag...

Page 22: ...en is displayed 2 Press the UP arrow button to scroll to the ZWAVE menu 3 Press Select to select the ZWAVE screen 4 The display will show REMOVE in the text line 5 Press Select to perform the Reset De...

Page 23: ...to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment...

Reviews: