RCS Sure 49 Field Installation Instructions Download Page 1

N o t e :

SurePowr actuators can be supplied for clockwise or counter-clockwise spring driven rotation (viewed from the top of the actuator).

The spring drive rotation is noted on the actuator name tag and wiring diagram. Ensure that the actuator has been supplied with the proper
spring drive operation for the application prior to installation on the driven device.

1. The actuator is shipped in the power off (fail) position. Ensure that the driven device is oriented to its

fail position prior to installation of the actuator.

2. Care should be taken to maintain proper alignment between the actuator and the device shaft.

If the actuator is not in the correct alignment with the device shaft, repeat the procedure in Step 1.

3. Mount the actuator to the device. Ensure the actuator is centered properly with the device shaft, and

then tighten all bolts and nuts evenly.

4. Remove the cover bolts located around the actuator motor and control cover flange.
5. Terminate field wiring per the appropriate RCS wiring diagram, supplied with the actuator. Use a

minimum of #18 AWG stranded wire.

Switch adjustments for clockwise spring fail operation (viewed from the top of the actuator)

a. Ensure actuator is de-energized and positioned in the clockwise (fail) position. Loosen the setscrews on Cams 1 and 3. Rotate both

counter-clockwise until they clear the switch arm rollers of Switches 1 and 3.

b. Rotate Cam 1 clockwise until it comes in contact with Switch 1’s arm roller and the switch “breaks”. A light “click” can be heard. 

Tighten the set-screws on Cam 1.

c. Rotate Cam 3 clockwise until it comes in contact with Switch 3’s arm roller and the switch just “breaks”. A light “click” can be heard.
d. Rotate Cam 3 slightly further in the clockwise direction. (This ensures that Switch 3 will “break” just prior to the actuator reaching the 

full fail position.) Tighten the setscrews on Cam 3. Energize the actuator. This will move the actuator to the opposite end of travel.

e. Upon reaching the opposite end of travel, Cam 2 should just engage the roller on Switch 2 so that the switch just “breaks”. 

This action will stop the actuator. Check that the actuator has properly positioned the driven equipment. 

f. If actuator travel is insufficient, rotate Cam 2 slightly clockwise until the cam just clears the roller of Switch 2. As soon as the

cam clears the roller, the actuator will “bump” electrically towards the end of travel. Continue until the actuator reaches the full 
end of travel.

S U R E P O W R

TM

S E R I E S - S U R E   4 9

F I E L D   I N S T A L L A T I O N   I N S T R U C T I O N S

In the maintenance and operation of mechanical equipment, 

SAFETY

is the basic factor which must be considered at all times. Through

the use of the proper clothes, tools and methods of handling, serious accidents causing injury to you or your fellow workers can be prevented.

Throughout this manual are listed a number of safety precautions. Study them carefully and follow them; also insist that those working
for you do the same. Remember, an accident is usually caused by someone’s carelessness, neglect or oversight.

Safety First

Installation

To   p r e v e n t   i g n i t i o n   o f   h a z a r d o u s   a t m o s p h e r e s ,

d o   n o t   r e m o v e   a c t u a t o r   c o v e r   w h i l e   c i r c u i t s   a r e   l i v e .

L o a d e d   s p r i n g   i n s i d e   a c t u a t o r.   D o   n o t   a t t e m p t   t o   r e p a i r   a c t u a t o r

b e l o w   t o p   g e a r   p l a t e ,   u n l e s s   p r o p e r l y   t r a i n e d   o n   r e p a i r   m e t h o d s .

Cam 1

Cam 2

Cam 3

Cam 4

Switch 4

Switch 3

Switch 2

Switch 1

F i g u r e   1

1

Summary of Contents for Sure 49

Page 1: ...tact with Switch 3 s arm roller and the switch just breaks A light click can be heard d Rotate Cam 3 slightly further in the clockwise direction This ensures that Switch 3 will break just prior to the actuator reaching the full fail position Tighten the setscrews on Cam 3 Energize the actuator This will move the actuator to the opposite end of travel e Upon reaching the opposite end of travel Cam ...

Page 2: ...roller of Switch 1 As soon as the cam clears the roller the actuator will bump electrically towards the end of travel Continue until the actuator reaches the full end of travel If the actuator has over traveled rotate Cam 1 slightly counter clockwise then move the actuator towards the fail position electrically Stop and electrically reverse the direction of travel Move the actuator until Cam 1 ope...

Page 3: ...ll motor drive and spring hold actuator in CCW most position C Loss of power will spring drive and spring hold actuator in CCW most position SP 3 Position Snap Action Switch Stop CCW CW FIELD WIRING ACTUATOR WIRING Capacitor Thermal Overload Automatic Reset M1 M2 M3 Heater 11 12 9 7 8 Switch 3 NC NO 3 2 5 4 NC NC NO NO NC 10 Switch 4 NO Switch 2 Switch 1 L1 A C Line Neutral L2 Opt 1 t Bridge Recti...

Page 4: ...lockwise direction Unit designation is spring clockwise Optional unit The output shaft is motorized in a clockwise direction and returned counter clockwise to the original position Unit designation is spring counter clockwise Allow 5 Clearance For Cover Removal 5 11 3 4 14 N P T 18 18 Ref Control Cover Spring Housing Shock Absorber 334 7 125 3 56 875 Dia 1 998 Pilot Dia 10 09 Ref Spring CCW 2 250 ...

Page 5: ...t condensation inside or outside the actuator If there is insufficient external temperature and humidity control internal heaters must be installed and energized to protect the unit against condensation from extreme temperature variations The actuators shall be stored off the floor on suitable pallets and must be covered with an unsealed dust protector allowing side and bottom ventilation Troubles...

Page 6: ... C 3c Check duty cycle frequency of operation See above for details 3d Ensure that actuator is not continuously stalled Problem 4 Motor runs continuously in spring return direction after actuator output shaft has stopped Instructions 4a Adjust spring return side travel cam switch so that the cam trips the switch before shaft stops motion Problem 5 Motor runs continuously but output shaft does not ...