Fail Locked = Fail Secure = FL     AC = Alternating Current     DC = Direct Current

Intermittent Duty = Energized less than 1 minute with 1:5 duty ratio   Continuous Duty = Energized 1 minute or more 

I N S T A L L A T I O N

VR165

ISVR165

®

Important: Adjust strike as indicated in steps 7 & 8 to ensure proper functionality. Ensure the exit device functions as 

intended for life safety concerns by verifying electric strike and exit device compatibility. Maximum latch projection is 

essential to obtain full engagement.
This product is Fail Locked only. The local Authority Having Jurisdiction shall be consulted with regard to the use of 

selected panic hardware to ensure emergency exit from the secured area.

Installations of this Vertical Rod strike qualify as “Indoor Use Only” when not continuously exposed to an outdoor 

environment.

Catalog Specifications 

MODE

VOLTAGE CURRENT

DUTY

PEAK AMPS

OHMS

Fail Locked

12V

AC

Intermittent

0.20

22

Fail Locked

12V

DC

Continuous

0.45

22

Fail Locked

24V

AC

Intermittent

0.48

22

Fail Locked

24V

DC

Continuous

0.24

89

Fail Locked

11-16V

AC

Intermittent

0.18-0.27

22

SURFACE MOUNTED VERTICAL ROD STRIKE  

Dimensional Details 

  © 2016 RUTHERFORD CONTROLS INT’L

WWW.RUTHERFORDCONTROLS.COM • PHONE: 1.800.265.6630 • FAX: 1.800.482.9795 • E-MAIL: [email protected]

"

2 14

(57.0mm)

8 "

(41.5mm)

1 5

HOLES

MOUNTING 

HORIZONTAL
ADJUSTMENT

LOCK DOWN
CLAMP

"

1 34

(44.5mm)

"

5 12

(139.7mm)

6 18 "

(155.6mm)

3

4 "

(19.0mm)

1 58 "

(42.0mm)

M8 SCREW 

R09/16TG-2

®

UL 294 Performance Ratings:
Access Control Line Security : Level I
Destructive Attack : Level I
Endurance : Level IV
Standby Power : Level I