*931029-00*
931029-00
4-7/8”
Standard ANSI,
Sharp Corner
7-15/16” Long,
Round Corner
Figure 3
Fail-safe (FS) Mode
Fail-secure (FSE) Mode
Actuator
Actuator
Figure 2
Backbox cover
3.
Prepare frame for strike (see page 4 for dimensions).
Note: Prepare room for RCP rectifier if needed.
4.
Make sure strike operates in correct mode. Lip of fail-safe (FS) strike can be moved when strike is not powered. Lip of
fail-secure (FSE) strike cannot be moved when strike is not powered. If necessary, remove backbox cover (Figure 2) and
change strike mode by repositioning actuator (Figure 3).
1.
For lock preparation, see lock instructions.
2.
Install correct faceplate onto strike (Figure 1).
Figure 1
Wiring must
stay in slot
4-7/8”
Standard ANSI,
Round Corner
#10-24 flat head
nyloc screws
When using the electric strike in fail-secure mode, the local
authority having jurisdiction shall be consulted to assure
compliance in allowing emergency exit from the secured area.
NOTE
!
Electric Strike
5100
Installation Instructions