ViewSmart 200/2050/2150 Controller User's Manual
Document: UM-1021
Revision Level B
32
CHAN_1ALM_1
BIT0
CHAN_1ALM_2
BIT1
CHAN_1ALM_3
BIT2
CHAN_2ALM_1
BIT3
CHAN_2ALM_2
BIT4
CHAN_2ALM_3
BIT5
RELAY_1
BIT6
RELAY_2
BIT7
PIEZO
BIT7
Memory Floating Point:
Notes: Returned as 15 bit 2s complement with +- 5% over/underrange applied.. Therefore this
must be considered when scaling values to be displayed at the Workstation. The following
equation may be used to determine a value for display.
Display Value = MODBUS Value [ (Span Value -Zero Value) 1.1] + {Zero Value - [(Span Value - Zero Value) .05]}
32767
FP Value Chan 1
33001
4
NA
FP Value Chan 2
33002
4
NA
Memory Reals:
Notes: Real value represents float value without the decimal point such as 123.4 is returned as
1234. Decimal devisor is returned as 1, 10, 100, or 1000 for decimal position of 1, 2, 3, or 4,
where 123.4 would return the value 10.
Chan 1 Zero Real
41001
3
NA
Chan 1 Zero Divisor
41002
3
NA
Chan 1 Span Real
41003
3
NA
Chan 1 Span Devisor
41004
3
NA
Chan 1 Alarm 1 Real
41005
3
NA
Chan 1 Alarm 1 Devisor 41006
3
NA
Chan 1 Alarm 2 Real
41007
3
NA
Chan 1 Alarm 2 Devisor 41008
3
NA
Chan 1 Alarm 3 Real
41009
3
NA
Chan 1 Alarm 3 Devisor 41010
3
NA
Chan 2 Zero Real
41011
3
NA
Chan 2 Zero Divisor
41012
3
NA
Chan 2 Span Real
41013
3
NA
Chan 2 Span Devisor
41014
3
NA
Chan 2 Alarm 1 Real
41015
3
NA
Chan 2 Alarm 1 Devisor 41016
3
NA
Chan 2 Alarm 2 Real
41017
3
NA
Chan 2 Alarm 2 Devisor 41018
3
NA
Chan 2 Alarm 3 Real
41019
3
NA
Chan 2 Alarm 3 Devisor 41020
3
NA
Binary Cal Data:
Chan 1 A2D MIN
41021
3
NA
Chan 1 A2D MAX
41022
3
NA
Chan 1 D2A MIN
41023
3
NA
Chan 1 D2A MAX
41024
3
NA
Chan 2 A2D MIN
41025
3
NA
Chan 2 A2D MAX
41026
3
NA
Chan 2 D2A MIN
41027
3
NA