ViewSmart 200/2050/2150 Controller User's Manual
Document: UM-1021
Revision Level B
30
Figure 3.9
3.2.1
MODBUS REGISTER AND FUNCTION CODE SUMMARY
The following table identifies ViewSmart 200 Modbus register locations and function
codes.
VARIABLE
ALIAS
READ FUNCTION CODE
WRITE FUNCTION CODE
Read/Write Coils:
Alarm Ack/Reset
2001
1
5
Note: After writing a TRUE to this register, the
ViewSmart
200 will reset it to FALSE.
Read Only Discrete:
Chan 1
Alarm 1
12001
2
NA
Chan 1
Alarm 2
12002
2
NA
Chan 1
Alarm 3/Flt
12003
2
NA
Chan 2
Alarm 1
12004
2
NA
Chan 2
Alarm 2
12005
2
NA
Chan 2
Alarm 3 /Flt 12006
2
NA
Relay 1
12007
2
NA
Relay 2
12008
2
NA
Read Only Registers:
Product ID
30001
4
NA
Returns the numeric value 90 for product ID.
Firmware value
30002
4
NA
Return a numeric value for firmware value as (Version X 100).