background image

SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS

Page 14

RBI water heaters are designed to run scale free. Due
to the extreme variables of water conditions world wide
it is necessary to consider pH values and water
hardness in relationship to scaling. It is crucial to
consider these two variables when making heat
exchanger and pump selections. If local water conditions
are extreme follow the guidelines in the Heat Exchanger
Selection Table (Table 7A) and the Pumping
Performance Table (Table 7B). Scale free operation can
be achieved by using water with a hardness between 8
and 18 and by maintaining the pH between 5 and 9.
Follow the conditions listed under NORMAL in the table.
In some areas of the country additional precautions
must be observed due to unusual characteristics of the
local water supply. Call the nearest RBI representative
for details.

To properly size the pump a grain hardness and pH test
must be taken at the installation site before the order is
placed. Proper pump sizing will improve heater
performance and help ensure heater longevity.

Expansion Tank

An expansion tank or other means to control thermal
expansion must be installed in the water heating system
if back flow prevention devices are installed.

Pump Requirements

This low-mass water heater requires a continuous mini-
mum water flow for proper operation. The factory
recommended circulating pump has been sized to
overcome the head loss of the water heater plus a 30
foot piping loop under normal water conditions. Table 7B
provides the heat exchanger pressure drop chart and
temperature rise table. 

The temperature rise across the

water heater must never exceed 30

°

F, 16.7 

°

C.

CAUTION: The maximum allowable flow rate through
a Spectrum water heater is 92 GPM, 

5.8 L/s

 (2-pass

heat exchanger) and 46 GPM, 

2.9 L/s

 (4-pass heat

exchanger). The cupro-nickel heat exchanger allows
for 100 GPM, 

6.3 L/s

 (2-pass heat exchanger) and 50

GPM, 

3.2 L/s

 (4-pass heat exchanger). See Table 7B.

Cold Water Supply

The cold water supply must be piped to the storage tank
on the water heater’s outlet piping between the water
heater and the hot water storage tank. This will prevent
untempered water from entering the water heater, see
the Temperature Rise Control section. A typical water
heating system is shown in Figures 8 and 9.

Temperature Rise Control

Water returned to the water heater inlet must not be less
than 

110

°

F

43

°

C or excessive condensation of the

products of combustion will damage the water heater
voiding the warranty. The method outlined below can be
employed to prevent this condition from occurring.

A balancing valve should be installed on the outlet side
of the water heater for purposes of adjusting the flow
rate through the heat exchanger. Thermometers are
installed on both the inlet and outlet of the water heater
for determining the temperature rise through the unit.

The proper velocity through the water heater must be
maintained in accordance with Table 7B for efficient
operation and long life. If the temperature rise through
the water heater is lower than recommended, the water
velocity is too high. Premature erosion of the heat
exchanger will occur. Conversely, if the temperature rise
is higher than recommended in Table 7B the flow rate is
too low. Scaling and softening of the heat exchanger will
occur.

Thermostatic Mixing Valve - Water Above 140

°

F, 

60

°

C

Water can be stored at temperatures above 

140

°

F

,

60 

°

C provided that a thermostatically controlled mixing

valve is used to temper the hot water to an acceptable
temperature before it’s supplied for domestic use.

The mixing valve MUST be set to prevent a scald injury
from occurring, see the caution against scalding.

Storage of water for domestic use above 

140

°

F

60

°

C

will provide an increased quantity of tempered water and
help prevent the growth of water born bacteria.

Summary of Contents for SB

Page 1: ...in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the...

Page 2: ...ter To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instructions must be read understood and followed The Spectrum finned...

Page 3: ...will support the weight of the boiler water heater NOTE The Spectrum may be installed directly on combustible flooring only if RBI supplied special floor pan is used but never on carpeting see Table 2...

Page 4: ...n 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where directly communicating with the outdoor...

Page 5: ...onry chimney must be performed to ensure that the chimney is clean properly constructed lined and sized Exterior masonry chimneys should not be used unless properly lined to prevent condensation and d...

Page 6: ...ef opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe Faire fonctionner le br leur principal pendant 5 min ensuite d terminer s...

Page 7: ...INSTALLATION AND OPERATING INSTRUCTIONS Page 7 Figure 1 Vertical Venting with a Metal Chimney System and Inside Air Figure 2 Vertical Venting using a Masonry Chimney and Inside Air 10 FT 3 1m RIOM 51...

Page 8: ...flow rates see Table 7 or 8 Return water temperatures below 110 F 43 C will result in heat exchanger damage from excessive condensation voiding the manufacturer s warranty see Primary Secondary Piping...

Page 9: ...tem An expansion tank must be installed close to the boiler on the suction side of the system pump Primary Secondary Piping Boilers connected to heating systems using zone valves zone pumps or systems...

Page 10: ...Drop T 30 F T 16 7 C Note Unit equipped with 4 pass headers see Table 8 Flow Rate 100 150 200 250 300 350 400 16 4 24 6 32 4 40 5 49 8 0 34 0 94 1 92 3 46 5 89 1 0 1 6 2 0 2 6 3 1 1 0 2 8 5 7 10 2 17...

Page 11: ...lers furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied Notice These drawings show suggested piping configuration and valving Check wit...

Page 12: ...lobe Valve Balance Valve Balance Valve 1 5 H 15 Rev 2 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units NOTES 1 Boiler circuit piping must be sized lar...

Page 13: ...he boiler When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device the piping system must be equipped with flow control valves or some other aut...

Page 14: ...xchanger The cupro nickel heat exchanger allows for 100 GPM 6 3 L s 2 pass heat exchanger and 50 GPM 3 2 L s 4 pass heat exchanger SeeTable 7B Cold Water Supply The cold water supply must be piped to...

Page 15: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 15 Table 7B Spectrum Pumping Performance Requirement Table Table 7A Spectrum Heat Exchanger Selection Graph...

Page 16: ...ay locate remote aquastat well in lower 1 3 of tank Install bulb with heat sensing compound 3 Thermal expansion tank may be required check local codes 4 When using optional factory mounted pump max pi...

Page 17: ...00 9700 Maximum gas volume of pipe ft3 hr Pipe length in feet Table 9 Gas Pipe Capacity Nominal Iron Pipe Size in Maximum pipe capacity in ft3 hr based on 0 60 specific gravity gas at a pressure of 0...

Page 18: ...alled to prevent increase creep of gas pressure when the units are not operating This pressure regulator supplied by others may be installed at the service entrance to each unit or a master regulator...

Page 19: ...water pump is used adjust to maintain a minimum 12 psig 82 7 kPa system pressure Open the system bleed and drain valves one at a time to purge the air trapped in the heating system piping With the boi...

Page 20: ...kwise to PILOT 9 Push in control knob all the way and hold in Immediately light the pilot with a match Continue to hold the control knob in for about one 1 minute after the pilot is lit Re lease knob...

Page 21: ...el 6 Push in gas control knob slightly and turn clockwise to OFF 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety inf...

Page 22: ...than 5 adjust it according to steps 1 through 4 Input Rate Natural Gas Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 ft 610 m At elevations...

Page 23: ...ine silica materials that have been identified as carcinogenic or possi bly carcinogenic to humans when inhaled AVERTISSMENT Une instqallation un r glage une r paration ou un entretien non comforme au...

Page 24: ...dication of low water flow through the system 2 A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler water heater is returned to service Vent S...

Page 25: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 25 4 21 1 22 29 26 27 6 28 25 15 16 24 12 4 3 10 8 20 2 5 36 35 31 19 18 9 7 17 11 23 30 37 34 33 32 14 13 Figure 14 Replacement Parts...

Page 26: ...Front Panel 03 0894 1 03 0895 1 03 0896 1 03 0897 1 03 0898 1 03 0899 1 03 0900 1 Combustion Chamber Side Panel Left Right 03 0901 2 2 2 2 2 2 2 2 Rear Refractory Panel 05 0035 1 05 0036 1 05 0037 1 0...

Page 27: ...70 1257 1 70 1258 1 70 1259 1 70 1260 1 70 1261 1 70 1262 1 8 Jacket Rear Panel 03 0749 1 03 0750 1 03 0751 1 03 0752 1 03 0753 1 03 0754 1 03 0755 1 9 Draft Hood Assembly 70 1272 1 70 1273 1 70 1274...

Page 28: ...123 1 09 0124 1 1 09 0125 1 09 0126 1 17 Jacket Top Panel 03 0741 1 03 0742 1 03 0743 1 03 0744 1 03 0745 1 03 0746 1 03 0747 1 NS Jacket Top Panel Outdoor 70 1205 1 70 1206 1 70 1207 1 70 1208 1 70 1...

Page 29: ...ader Bronze 01 0011S 1 1 1 1 1 1 1 NS Return Header Bronze 4 Pass 01 0011 1S 1 1 1 1 1 1 1 23 Inlet Outlet Cover Outdoor 03 0734 1 1 1 1 1 1 1 24 Return Cover Outdoor 03 0737 1 1 1 1 1 1 1 NS Heat Exc...

Page 30: ...1 1 1 1 33 High Limit Operator Knob 14 0120 1 1 1 1 1 1 34 Light Package 40 0052 1 1 1 1 1 1 35 Relay 24V AC 15 0113 1 1 1 1 1 1 36 Terminal Block 2P 48 0151 1 1 1 1 1 1 Terminal Block 4P 48 0152 1 1...

Page 31: ...NS Power Venting Wiring 30 0787 1 1 1 1 1 1 NS Induced Draft Kit HS1 12 0009BK 1 1 1 1 Induced Draft Kit HS2 12 00010BK 1 1 NS Vent Termination Hood 4 09 0134 1 1 1 1 Vent Termination Hood 6 09 0112...

Page 32: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Reviews: