3. If a single combustion air opening is
provided to bring combustion air in
directly from the outdoors, the opening
must be sized based on a minimum
free area of one square inch per 3000
Btu/hr (7 cm
2
per kW). This opening
must be located within 12” (30cm) of
the top of the enclosure (see Fig.5-3).
5 - INSTALLATION - Location
Figure 5-3 Combustion Air from outside - single opening
EQUIPMENT
ROOM
AIR OPENING