background image

Finned copper tube gas boilers & water heaters – Boiler Manual

Finned copper tube gas boilers & water heaters – Boiler Manual

23

F

Figure 15 

Figure 16 

HeatNet Control Panel

17.  Close main isolation gas valve (fi eld supplied), Figure 14. 
18. Remove the manometer fi tt ing from the pilot test port and 

replace the plug. Place monitor tube on to the test port tee 
located along the 1/8 in hose piped directly off  of the manifold 
test port, Figure 15. 

MANUAL RESET 

PUMP MOTOR

RELAY

TRANSFORMER

FLAME
SAFEGUARD
MODULE

HEAT NET
CONTROL
BOARD

PROTOCESSOR
MODULE
(OPTIONAL)

LOCAL REMOTE

SWITCH

TEST RUN
SWITCH

POWER SWITCH

IGNITION STATUS

WINDOW

SELECT BUTTON

BACK

BUTTON

DISPLAY

WINDOW

UP BUTTON

DOWN BUTTON

19.  Switch the Honeywell 7800 back to “run”.

20.  Create a min input demand as before (enable Low Fire Hold 

switch). Th e boiler will begin the start sequence. 

21.  Monitor the fl ame current on the 7800. No fl ame current should 

be detected and the 7800 should lock out. If fl ame current is 
detected at any time up to the 7800 locking out, the 120V wiring 
on the ignition transformer must be reversed and the test run 
again to insure that no fl ame is detected.

Improper wiring of the ignition transformer can result 

in an explosion causing extensive property damage, 
severe personal injury or death!

22.  Open main isolation gas valve (fi eld supplied).
23.  Reset the Honeywell 7800. Th e boiler will start and will run at 

minimum input rate. 

24.  

Sett ing the low fi re:

 Allow the low fi re to sett le out for a 

few minutes and observe the combustion reading. Refer to 

“Combustion Reading” table for proper combustion readings 

and elbow pressure, Table 13.

 

Th e low fi re O

2

-CO

2

 can be adjusted in the fi eld by opening 

the low fi re adjustment door located on the forward facing side 
of the main gas valve, see Figure 15. Inserting an allen wrench 
and rotating the allen screw clock-wise will increase the CO

and lower the O

2

, rotating counter clock-wise will decrease the 

CO

2

 and increase the O

2

DO NOT LEAVE THE BURNER 

IN AN INFRA

 RED STATE.

 A few random speckles of red 

are fi ne, but large concentrations of spots or large areas of red 
are not. If large amounts of red concentrations are observed, 

verify combustion readings. 

25.  Jumper the “AA” terminals located on the HeatNet control board. 

Th e boiler input will rise to its maximum input, “Run 100%”, 

see Figure 19.

26.  Allow the boiler to reach steady state and verify supply gas 

pressure and check input rates as explained in the “Gas Supply 

Piping” section. Also, refer to “Combustion Reading” table for 

proper combustion readings and elbow pressure, Table 13.

Th e high fi re trim is located on the outlet fl ange of the gas valve, 

see Figure 15. O

2

-CO

2

 can be adjusted by inserting a screwdriver 

and rotating clock-wise to increase the CO

2

 and lower the O

2

Rotating counter clock-wise will decrease the CO

2

 and increase 

the O

2

27.  Remove jumper “AA” and allow boiler to sett le into minimum 

input. Observe the combustion readings and make any fi nal 
adjustments. When fi nished disable the Low Fire Hold switch 
and replace test ports to normal state.

28.  Boiler allows for many modes of operation and control methods. 

Reference the “HeatNet Control” manual.

Table 13 

Combustion Readings

Natural Fuel 

Propane Fuel

CO

2

 %

8.0 - 8.5 (min.)

9.4 - 9.9  (min.)

8.8 - 9.8 (100%)

10.3 - 11.5 (100%)

O

2

 %

6.6 - 5.8  (min.)

6.6 - 5.8  (min.)

5.2 - 3.5 (100%)

5.2 - 3.5 (100%)

*For factory set gas manifold (elbow) pressures see label on

inner cabinet door.

Summary of Contents for Gas boilers

Page 1: ...ction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler ca...

Page 2: ...RESSURE VESSEL CODE SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRES SURE OF 160 PSI 1103 kPa WATER BEFORE YOU START 2 RATINGS CAPACITIES 3 BOILER WATER HEATER LOCATION 3 COMBUSTION AIR VENTILATION 3 G...

Page 3: ...se to a chimney or outside wall and have adequate fresh air forcombustion Ensurethattheboiler waterheaterislevelfrom front to back and from side to side Use metal shims to level the boiler water heate...

Page 4: ...ely communicate with the outdoors must be present The upper opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 30...

Page 5: ...e building structure and not by the boiler water heater Appropriate thimbles and fire stops must be used where required Common vent systems must be properly engineered and sized please contact the fac...

Page 6: ...exceed5 ft 1 5 m they must be supported at 3 ft 0 9 m intervalswith overhead hangers Theventsystemmust bepitcheddown towardthe ventterminal 1 4 in ft 20 mm m If anypartofasinglewallmetalventsystempass...

Page 7: ...on air and venting for single or multiple units exhaust and combustion air terminalsmustbeinstalledonthesameplane outsidewall in order to prevent pressure differences due to prevailing winds Incoldcli...

Page 8: ...3 Vertical Air Intake and Venting for a Direct Vent System Locate exhaust terminal downwind to reduce flue gas recirculation Figure 4 Horizontal Air Intake and Venting for Multiple Direct Vent Systems...

Page 9: ...ng A through inspection of the masonry chimney must be performed to ensure that the chimney is clean properly constructed lined and sized Exterior masonry chimneys should not be used unless properly l...

Page 10: ...If horizontal runs exceed 5 ft 1 5 m they must be supported at 3 ft 0 9 m intervals with overhead hangers The vent connector should be sloped up toward the chimney at a minimum rate of 1 4in ft 21 mm...

Page 11: ...served 1 AcontinuousflowofwaterthroughtheunitMUSTbemaintained The pump responsible for flow through the boiler water heater must run continuously 2 An ethylene glycol water mixture suitable for the mi...

Page 12: ...the pump on each time the burner fires and runs the pump for 20 to 600 seconds after the call for heat is satisfied The maximum allowable primary heat exchanger temperature rise is 35 F 19 4 C The max...

Page 13: ...Drain Valve Typ 3 Way Mixing Valve Item Number Description 1 3 Way Valve 2 Air Purging Valves 3 Flow Switch 4 Circulator 5 Pressure Relief Valve 6 T P Gauge 7 Primary Heat Exchanger Drain Valves 8 Co...

Page 14: ...boiler is filled Use purge valves provided Purge valve may be located on pump flange On multiple boiler installations the flow switch may fail due to trapped air See manual for procedure 3 All boiler...

Page 15: ...m 3 way valve after the boiler is filled Use purge valves provided Purge valve may be located on pump flange On multiple boiler installations the flow switch may fail due to trapped air See manual for...

Page 16: ...be consulted when these water conditions are encountered See Table 8 RBI water heaters are designed to run scale free Due to the extreme variables of water conditions world wide it is necessary to con...

Page 17: ...w Rate gph t deg f Flow Rate gph t deg f Flow Rate gph t deg f 60 614 96 833 106 1050 112 1460 101 1664 106 1859 111 2118 111 80 753 76 998 86 1245 92 1768 81 2000 86 2205 91 2520 91 100 999 56 1268 6...

Page 18: ...d heater flow 5 Hot water tanks should be equipped with a combination temperature pressure relief valve 6 MA Code requires an 1 8 in hole in check valve to compensate for thermal expansion 7 Boiler an...

Page 19: ...mum combined heater flow 5 Hot water tanks should be equipped with a combination temperature pressure relief valve 6 MA Code requires an 1 8 in hole in check valve to compensate for thermal expansion...

Page 20: ...hould be used in conjunction with Table 11 to ensure that the gas supply piping has the capacity to meet the demand Figure 14 depicts the proper way to connect the boiler water heater to the gas suppl...

Page 21: ...of 14 awg Use appropriate wiring materials for units installed outdoors The wire size must be compatible with the total amp draw of the circuit Refer to the wiring diagram supplied with the boiler wa...

Page 22: ...if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water N...

Page 23: ...lbow pressure Table 13 The low fire O2 CO2 can be adjusted in the field by opening the low fire adjustment door located on the forward facing side of the main gas valve see Figure 15 Inserting an alle...

Page 24: ...setting 2 Turnoffallelectricpowertotheboilerifserviceistobeperformed 3 Close the manual main and pilot gas shut off valves COMMENT COUPER L ADMISSION DE GAZ DE L APAREIL 1 R glez le thermostat la tem...

Page 25: ...follows LP Nat Minimum in WC 2 2 Maximum in WC 14 14 Measure pressure when the boiler is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply Static and...

Page 26: ...20mA signal can be used to control HeatNet equipped boilers Method 1 A 4 20mA signal can be used to directly modulate each boiler from a remote panel or building management system On multiple boiler i...

Page 27: ...nned copper tube gas boilers water heaters Boiler Manual Finned copper tube gas boilers water heaters Boiler Manual 27 F RIOM 86 Figure 19 RBI Field Wiring to HeatNet Board BoardRevision 2 0 and Great...

Page 28: ...he display will also list faults should the unit fail to operate An explanation of each status message and fault can be locatedinHeatNetControlManualunderstatusscreenfaultdisplay section STATUS SCREEN...

Page 29: ...on or use as a field interlock The interlock is located on J11B SPARE 4 FAULT SYSTEM SET 160 F INTERLOCK SPARE 4 FLOW SWITCH ERROR Once the Futera Fusion series boiler receives a call for heat it clos...

Page 30: ...TEM SET 160 F OPEN OUTSIDE SENSOR SHORTED SENSOR If the shorted sensor fault is displayed the sensor in the position reported was originally detected but has since shorted The boiler will shut down on...

Page 31: ...l with some types of gases Black soot indicates poor combustion Green deposits indicate condensation due to low return water temperatures In either case the heat exchanger must be cleaned thoroughly a...

Page 32: ...pressure If it does contact a qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replaced 5 Theaquastathighl...

Page 33: ...k for 24 VAC on J11A J11B to identify which interlock has tripped Reset the Interlock or check for disconnected wiring or shorts The Air Pressure from UV Sensor interlock if displayed will allow the b...

Page 34: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 34 F F Figure 21 Repair Parts REPAIR PARTS 34...

Page 35: ...Finned copper tube gas boilers water heaters Boiler Manual Finned copper tube gas boilers water heaters Boiler Manual 35 F REPAIR PARTS CONTINUED...

Page 36: ...ket 06 0022 1 1 1 1 1 1 1 NS Gas Injectors NG 10 1009 1 1 1 1 Gas Injectors NG 10 1002 1 1 1 Gas Injectors LP 10 1010 1 1 1 1 1 1 1 21 Firing Valve 1 11 0456 1 1 Firing Valve 1 1 4 11 0457 1 1 Firing...

Page 37: ...on prior to 0209 must replace 70 2516 1R 1 combustion chamber top panel 36 70 2517 1R 1 70 2518 1R 1 70 2519 1R 1 70 2520 1R 1 70 2521 1R 1 Heat Exchanger Assembly Copper 70 2186 1R 1 Bronze 70 2187 1...

Page 38: ...4 Main Board HeatNet green 16 0038 1 1 1 1 1 1 1 55 Display Board HeatNet 40 0088 1 1 1 1 1 1 1 NS Ribbon Cable 40 0115 1 1 1 1 1 1 1 NS Power Switch 48 0013 1 1 1 1 1 1 1 NS Toggle Switch Remote Loca...

Page 39: ...1 1 1 1 1 Pilot Orifice LP 10 0139 1 1 1 1 1 1 1 82 Mini Peeper C7027A 16 0009 1 1 1 1 1 1 1 85 Turbo Pilot Torch 70 2559 1 1 1 1 1 1 1 86 1 2 Aluminum Tubing 62 0103 1 1 1 1 1 1 1 NS Spark Rod Assem...

Page 40: ...the bottom of the electrical panel Disable any external call for heat and toggle the remote local switch to REMOTE 1 Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignitio...

Page 41: ...F 15 TIMES THE DELTA T BETWEEN THE HEATER IN LET AND OUTLET IS CRITICAL TO PROP ER FLOW BEFORE YOU LEAVE THE JOB SITE YOU MUST RECORD THE DELTA T THIS READING SHOULD NOT EXCEED 35o F 19 4o C NOR BE LO...

Page 42: ...t terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBST...

Page 43: ...tructions for proper pump performance Chemical corrosion no corrosive chemical freon dry cleaning chemicals degreasing liquids chlorine or any chemicals that produce hydrochloric acid can be present i...

Page 44: ...ht 2012 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwaterhe...

Reviews: