Finned copper tube gas boilers & water heaters – Boiler Manual

42

F

F

NOTICE! 

Commonwealth of Massachusetts

 

 Installation 

Requirements 

 

MACODE-3

   In the Commonwealth of Massachusetts, the installa-

tion must be performed by a licensed plumber or gas 
fi tter.

1.  For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 
or in part for residential purposes, including those owned or 
operated by the commonwealth and where the side wall exhaust 
vent termination is less than seven (7) feet above fi nished grade, 
in the area of the venting, including but not limited to decks and 
porches, the following requirements shall be satisfi ed:

 

d.   INSTALLATION OF CARBON MONOXIDE DETECTORS. At the 

time of installation of the side wall horizontal vented gas 
fueled equipment, the installing plumber or gasfi tter shall 
observe that a hard wired carbon monoxide detector with an 
alarm and battery back-up is installed on the fl oor  level 
where the gas equipment is to be installed. In addition, the 
installing plumber or gasfi tter shall observe that a battery 
operated or hard wired carbon monoxide detector with an 
alarm is installed on each additional level of the dwelling, 
building or structure served by the side wall horizontal 
vented gas fueled equipment. It shall be the responsibility of 
the property owner to secure the services of qualifi ed 
licensed professionals for the installation of hard wired 
carbon monoxide detectors.

 

i.   In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, 
the hard wired carbon monoxide detector with alarm and 
battery back-up may be installed on the next adjacent 
fl oor level.

 

ii.   In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply 
with the above requirements; provided, however, that 
during said thirty (30) day period, a battery operated 
carbon monoxide detector with an alarm shall be 
installed.

 

e.   APPROVED CARBON MONOXIDE DETECTORS. Each carbon 

monoxide detector as required in accordance with the above 
provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certifi ed. 

 

f.   SIGNAGE. A metal or plastic identification plate shall be 

permanently mounted to the exterior of the building at a 
minimum height of eight (8) feet above grade directly in line 
with the exhaust vent terminal for the horizontally vented gas 
fueled heating appliance or equipment. The sign shall read, 
in print size no less than one-half (1/2) inch in size, “GAS VENT 
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

g.   INSPECTION. The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve 
the installation unless, upon inspection, the inspector 
observes carbon monoxide detectors and signage installed 
in accordance with the provisions of 248 CMR 5.08(2)(a)1 
through 4. 

  Improper venting can result in excessive levels of 

carbon monoxide which can cause severe personal 
injury or death!

2.  Exemptions — The following equipment is exempt from 

248 CMR 5.08(2)(a) 1 through 4:

a.  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition of 
NFPA 54 as adopted by the Board; and

b.  Product Approved side wall horizontally vented gas 

fueled equipment installed in a room or structure 
separate from the dwelling, building or structure used in 
whole or in part for residential purposes.

3.   MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING 

SYSTEM PROVIDED.

a.  When the manufacturer of Product Approved side wall 

horizontally vented gas equipment provides a venting 
system design or venting system components with the 
equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system 
shall include:

 

i.   Detailed instructions for the installation of the venting 

system design or the venting system components; and

 

ii.   A complete parts list for the venting system design or 

venting system. 

4.   MANUFACTURER REQUIREMENTS – GAS EQUIPMENT  VENTING 

SYSTEM NOT PROVIDED.

a.  When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not provide 
the parts for venting the fl ue gases, but identifi es “special 
venting systems”, the following requirements shall be 
satisfi ed by the manufacturer:

 

i.   The referenced “special venting system” instructions 

shall be included with the appliance or equipment 
installation instructions; and 

 ii. 

 

The 

“special venting systems” shall be Product 

Approved by the Board, and the instructions for that 
system shall include a parts list and detailed installation 
instructions.

5.   A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all 
venting instructions, all parts lists for venting instructions, 
and/or all venting design instructions shall remain with the 
appliance or equipment at the completion of the installation.

  Improper venting can result in excessive levels of 

carbon monoxide which can cause severe personal 
injury or death!

Summary of Contents for FUTERA III Series

Page 1: ...construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The b...

Page 2: ...vent this unit can cause excessive amounts of carbon monoxide resulting in severe personal injury or death DESIGNED AND TESTED ACCORDING TO A S M E BOILER AND PRESSURE VESSEL CODE SECTION IV FOR A MA...

Page 3: ...earance in mm in mm Top 6 153 30 762 Back 6 153 24 610 Left Side 6 153 12 306 Right Side 6 153 12 306 Front 6 153 30 762 2 An optimum site will be level central to the piping system close to a chimney...

Page 4: ...ning must be within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enc...

Page 5: ...tions must comply with CAN CGA B149 1 or 2 Installation Code Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death All vent systems mus...

Page 6: ...ion rated for 400 F 204 C Horizontal vent systems shall terminate at least 4 ft 1 2 m below 4 ft 1 2 mhorizontallyfromor1 ft 0 30 maboveanydoor window or gravity air inlet into any building It must no...

Page 7: ...single or multiple units exhaust and combustion air ter minals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds Incoldclimates double...

Page 8: ...s boilers water heaters Boiler Manual 8 F F Figure 3 Vertical Air Intake and Venting for a Direct Vent System Figure 4 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5...

Page 9: ...chimney system manufacturer s instructions must be followed Masonry chimneys when used must be lined with a metal liner certified for Category IV venting When more than one appliance is connected to t...

Page 10: ...rate of 1 4 in ft 21 mm m On masonry chimneys the connector must terminate flush with the inside of the chimney flue Figure 7 Fasten each single wall vent connection with at least 3 corrosion resista...

Page 11: ...ing system Scellertouteslesouverturesnonutilis esdusyst med vacuation b Visuallyinspecttheventingsystemforpropersizeand horizontal pitch and determine there is no blockage or restriction leakage corro...

Page 12: ...property damage Excessive water hardness causing scaling in the copper heat exchanger tubes is NOT covered under the manufacturer s warranty see Table 8 Excessive pitting and erosion of the internal...

Page 13: ...l expansion of the system must be considered when supporting the system A minimum system pressure of 12 psig 82 7 kPa must be maintained Heating Boiler Piping Connections Thesupplyandreturnconnections...

Page 14: ...ump An air scoop and automatic air vent must also be installed to eliminate air trapped in the system Primary Secondary Piping Boilersconnectedtoheatingsystemsusingzonevalves zonepumps or systems that...

Page 15: ...low through unit 2 Boiler pump sized to boiler design flow requirements 3 All boilers furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplie...

Page 16: ...Valve Gate Valve Globe Valve Balance Valve Backflow Prevention Device H 15 Rev 4 NOTES 1 Boiler circuit piping must be large enough to handle maximum flow through unit 2 Boiler pump sized to boiler de...

Page 17: ...ess between 8 and 18 and by maintaining the pH between 5 and 9 Follow the conditions listed under NORMAL in the table In some areas of the country additional precautions must be observed due to unusua...

Page 18: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 18 F F Table 8A Futera III Heat Exchanger Selection Graph Table 8B Futera III Pumping Performance Requirement...

Page 19: ...ing selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 hole in...

Page 20: ...nt trap at the bottom of the vertical section of the gas supply pipe upstream of the gas controls A ground joint union should be installed between the boiler gas controls and the supply piping Each of...

Page 21: ...ing materials for units installed oudoors The wire size must be compatible with the total amp draw of the circuit Refer to the wiring diagram supplied with the boiler water heater for proper wiring co...

Page 22: ...has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water N utilisez pas...

Page 23: ...ow fire O2 CO2 can be adjusted in the field by opening the low fire adjustment door located on the forward facing side ofthemaingasvalve seeFigure14 a Insertinganallenwrench and rotating the allen scr...

Page 24: ...setting 2 Turn off all electric power to the boiler if service is to be performed 3 Close the manual main and pilot gas shut off valves COMMENT COUPER L ADMISSION DE GAZ DE L APAREIL 1 R glez le ther...

Page 25: ...easure pressure when the boiler is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply Static and operating gas pressure required at the gas valve inlet...

Page 26: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 26 F F RBI FIELD WIRING TO HEATNET BOARD Figure 17...

Page 27: ...ethods in which a 4 20mA signal can be used to control HeatNet equipped boilers Method 1 A 4 20mA signal can be used to directly modulate each boiler from a remote panel or building management system...

Page 28: ...on The display will also list faults should the unit fail to operate An explanation of each status message and fault can be located in HeatNet Control Manual under status screen fault display section...

Page 29: ...ck The interlock is located on J11B SPARE 4 FAULT SYSTEM SET 160 F INTERLOCK SPARE 4 FLOW SWITCH ERROR Once the FIII series boiler receives a call for heat it closes the circulator pump relay It then...

Page 30: ...AULT SYSTEM SET 160 F OPEN OUTSIDE SENSOR SHORTED SENSOR If the shorted sensor fault is displayed thesensorinthepositionreportedwasoriginallydetected but has since shorted The boiler will shut down on...

Page 31: ...tion Green deposits indicate condensation due to low return water temperatures In either case the heat exchanger must be cleaned thoroughly and the problem resolved before the boiler water heater is r...

Page 32: ...s contact a qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replaced 5 Theaquastathighlimitcontrolsthemax...

Page 33: ...11A J11B to identify which interlock has tripped Reset the Interlock or check for disconnected wiring or shorts The Air Pressure from UV Sensor interlock if displayed will allow the boiler to function...

Page 34: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 34 F F Figure 19 Exploded View REPAIR PARTS...

Page 35: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 35 F F REPAIR PARTS CONTINUED...

Page 36: ...rt CSD 1 11 0354 1 1 1 1 1 1 1 NS Flange 1 Outlet 11 0228 1 1 1 1 NS Flange 1 Inlet 11 0231 1 1 1 1 NS Flange 1 1 4 11 0213 2 NS Flange 1 1 2 Inlet 11 0214 2 2 NS Flange 1 1 2 Outlet 11 0229 1 1 1 NS...

Page 37: ...1 1 1 NS Air Filter 09 0483 1 1 1 09 0484 1 1 1 1 45 Tridicator 30 60 psi 13 0308 1 1 1 1 1 1 1 Tridicator 75 160 psi 13 0305 1 1 1 1 1 1 1 46 Heat Exchanger Assembly Copper Cast Iron prior to 0209 mu...

Page 38: ...7 1 1 1 1 1 1 1 52 Spark Generator Q652B 16 0008 1 1 1 1 1 1 1 53 Flame Safeguard RM78957C 16 0024R 1 1 1 1 1 1 1 NS Keyboard Display Module S7800A 16 0010 1 1 1 1 1 1 1 54 Main Board HeatNet green 16...

Page 39: ...1 70 2567 1 1 1 1 84 Electrode 16 0335 1 1 1 1 1 1 1 NS Spark Rod O ring 06 0008 1 1 1 1 1 1 1 NS Silicone 66 0151 1 1 1 1 1 1 1 NS Silicone Tubing 66 0051 2 2 2 2 2 2 2 NS Vent Termination Hood 5 09...

Page 40: ...ttom of the electrical panel Disable any external call for heat and toggle the remote local switch to REMOTE 1 Toggle the LOW FIRE switch to cycle the boiler then hold at trial for pilot ignition 2 Se...

Page 41: ...THE DELTA T BETWEEN THE HEATER INLET AND OUTLET IS CRITICAL TO PROPER FLOW BEFORE YOU LEAVE THE JOBSITE YOU MUST RECORD THE DELTA T THIS READING SHOULD NOT EXCEED 35 F 19 4 C NOR BE LOWER THAN 20 F 11...

Page 42: ...terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRU...

Page 43: ...bes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemical...