background image

53

P/N HN-IOM-1  82-0331 Copyright 2009 Mestek, Inc.

Finned copper tube gas boilers & water heaters – Control manual

Situation

Suggested procedure

Unable to change the # of Boilers 

in the BOILERS menu.

In H-Net method, the control auto-detects the boilers in the system and adjusts the number of boilers 

 

accordingly.
Using H-NET, if the number of boilers is not being detected properly as the actual number of boilers in the 

 

system, check each boiler. There can only be (1) master boiler, but there can be up to 15 member boilers.
Make sure only the master boiler has a Header Sensor (SYSTEM HEADER) connected.

 

Verify that each boiler’s HeatNet cable is in place.

 

Verify that each boiler has a unique address assigned (ADVANCED SETUP | DISTRIBUTED CTRL | 

 

H-NET ADDRESS).

The BOILERS menu only indicates 

one boiler, but there are member 

boilers connected. The amber 

light blinks on all of the boilers’ 

communications jacks.

Verify that the latest version of firmware is installed on all boilers.

 

All boilers in a system must have the same firmware revision (version). 

 

Verify the proper termination is set on the Master and the last Member boiler.

 

H-Net boilers are detected but 

then lost and then detected again.

The H-Net communications cable may be receiving interference from the blower, ignition, or other form 

 

of radiated electrical noise. The communications cable must be run separate from other wires.
Termination of the jumpers may not be correct or there is more than one master. 

 

Ensure that the termination dip switches are set on the MASTER boiler and only the LAST MEM-

a. 

BER boiler. All of the other member boilers should have their termination dip switches OFF.
There may be two or more MASTER boilers. Ensure that only one header sensor is present and con-

b. 

nected to the SYSTEM HEADER input. There should be no wires or sensors connected to the SYS-

TEM HEADER input if the boiler is operating as a member.
Verify that the HNet cables are of a shielded or twisted pair type. Shielding of the cable is required.

c. 

Minimize possible electrical interference by routing the communications cables away from electrical 

d. 

noise sources, such as motors, ignition controls, contactors, etc.

Only the MASTER boiler Fires, but 

the system has many boilers and is 

using H-Net.

In order for the MASTER boiler to act as a MASTER, the header sensor must be set to TYPEZ, and there 

 

must be a header sensor present.
At power-up, the header sensor is auto detected. If the temperature of the header sensor at power-up is 

 

greater than –25 °F and less than 240 °F it is considered a valid sensor. The boiler will default to the MEM-

BER mode if the temperature is not in this range, and can only be run locally or by external inputs. 
If the LOAD FACTORY DEFAULTS has been used to restore all the default settings, the header sensor 

 

has been set to NONE. This needs to be set as stated above (TYPEZ). The header sensor will need to be 

replaced or the temperature brought into a valid range. Power cycle the boiler and the HeatNet control will 

detect the sensor (if temperature is in the range listed above).
The HNet needs a communications cable daisy-chained between boilers. Ensure that a good connection 

 

is made on the communications board and that the lights on the dual RJ45 jacks flash (roughly twice a 

second). The MASTER is the only one that should flash with no communications cables plugged in.

You get the error message – 

WATER FLOW SWITCH or WAITING 

FOR FLOW.

If the control does not sense a closed circuit at input connection, FLOW SWITCH, check to make sure 

 

the circuit for the circulator pump is correct, that the pump is being energized, and that the flow prove 

switch is working properly. 
If there is no flow prove switch, check to make sure that a jumper wire has been connected across J11B, 

 

WTR FLW interlock.

Troubleshooting 

(continued)

9

Table 12 

Troubleshooting suggestions 

(continued)

Summary of Contents for FUTERA III Series

Page 1: ...use the boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resultinginpossibleseverepersonalinjury deathorsubstantialpropert...

Page 2: ...milliamp regulation Setpoint can be determined by the HeatNet control or by a 4 20 milliamp input signal Network boilers can be operated by override commands for increased versatility Thismanualisarr...

Page 3: ...n buttons on front of control panel door see opposite page On off switch on control 3 panel see opposite page HeatNet electrical connec 4 tion panel Electrical subpanel 5 Air chamber access panel 6 ac...

Page 4: ...iveacontactclosure on the HEAT DEMAND terminals or the AA high fire terminals In addition the controls can be set up to allow priority override by a remote 4 20mA source 3 Multiple boilers BMS operati...

Page 5: ...either for dedicated DHW or combined space heating DHW This section dis cusses four alternatives referred to as Method 1 through Method 4 6 Control menus and adjustments page 29 Operating parameters a...

Page 6: ...the boiler A properly rated shut off switch should be locatedattheboiler Theboilermustbegroundedinaccordance with the authority having jurisdiction or if none the latest revision of the National Elec...

Page 7: ...ed connect terminals to remote switch Enable LOW TEMP if desired for freeze protection set temp as desired HEAT EXCHANGER ALARMTYPE EXCHR DELTAT LIM HALF RATE Select WARNING continue running or FAULT...

Page 8: ...cablelocalcodesandthelatestrevision of the National Electrical Code ANSI NFPA 70 Installation should also conform to CSA C22 1 Canadian Electrical Code Part I if installed in Canada Install power supp...

Page 9: ...dulation cont 2 Pump options Summer pump jog enable to operate the circulator 1 pump once per week at 12 01 AM on any specified day when the heater is shut down for summer shutdown System pump options...

Page 10: ...ember boiler LOCAL PUMP DELTATEMP ENABLE DELTATEMP POST PRGTIME ALWAYS ENABLED Settings for boiler pump Enable if desired requires installing a return water temp sensor Set value if enabled Set or kee...

Page 11: ...r is to lower the modulating rate of running boilers when a new boiler starts Set DROP DOWN and DELAY RELEASE as needed Not applicable to member boilers FIRING MODE FIRING MODE MASTER FIRST Select rot...

Page 12: ...able Figure 3 page 22 Connectcablestoallofthememberboilersbycablingfromonetothe 3 next Check the network Turn the power on and the on off switch to ON for all of the member 1 boilers Allow time for ea...

Page 13: ...Prove 26 Return Sensor not Present 11 Spare 4 27 Outside Air Sensor not Present 12 Operator Interlock 28 13 Water Prove Flow Interlock 29 14 Air Prove UV Sensor Interlock 30 Master Boiler 15 MainValv...

Page 14: ...iler Boilers 2 16 are member boilers 0 4294967295 seconds BACnet or LonWorks protocols Install the correct protocessor to adapt to building manage 1 ment systems using BACnet or LonWorks protocols Eac...

Page 15: ...e correct voltage phase and amperage capacity specified A properly rated shut off switch should be located at theboiler Theboilermustbegroundedinaccordancewiththe authority having jurisdiction or if n...

Page 16: ...ntrol method is designed to limit tank temperature to a specified maximum It can cause short cycling in some cases If the tank temperature can be allowed to vary above and below a setpoint temperature...

Page 17: ...boiler to the DHW tank Post purge will increase tank temperature above SETPOINT Adding additional heat to the DHW tank after the setpoint temperature is reached will increase tank temperature ABOVE se...

Page 18: ...in the OP LIM BAND the maximum firing rate decreases as the temperature rises un til it reaches minimum input at OPERATE LIM tempera ture where the boiler shuts off Set the OP LIM BAND as wide as pos...

Page 19: ...F and all boilers off above 140 F and boilers cycled on off and modulating in between based on the HeatNet control s PID methodology Method 3 post purge option WhentanktemperaturereachesOFFTEMP allac...

Page 20: ...ADER must be installed in the system supply piping for HeatNet con trolled systems Connect the header sensor ONLY to the master boiler Install the header sensor in an immersion well Locate the sensor...

Page 21: ...o the DHW Setpoint Override operation control setup MEMBER boilers must be set up with operating parameters necessary during their override local operation A HeatNet boiler will respond to overrides i...

Page 22: ...ring continued HeatNet control field wiring also see Boiler Installation Operation Instructions Verify against wiring diagram supplied Figure 3 with boiler 6 PUMPS REQUIRE RELAYS OR STARTERS DO NOT di...

Page 23: ...23 P N HN IOM 1 82 0331 Copyright 2009 Mestek Inc Finned copper tube gas boilers water heaters Control manual Wiring continued HeatNet temperature sensors Figure 4 6...

Page 24: ...24 P N HN IOM 1 82 0331 Copyright 2009 Mestek Inc Finned copper tube gas boilers water heaters Control manual Wiring continued Field wiring relays interlocks and boiler status Figure 5 6...

Page 25: ...2 DHW tank sensor when used in lieu of DHW 3 aquastat DHW tank aquastat when used in lieu of DHW 4 sensor Outdoor air temperature sensor 5 Local flow proving switch 6 System header temperature sensor...

Page 26: ...inned copper tube gas boilers water heaters Control manual Wiring continued Field wiring connections for 4 20mA remote operation Figure 7 6 If using a 0 10VDC signal multiply any references to current...

Page 27: ...7 P N HN IOM 1 82 0331 Copyright 2009 Mestek Inc Finned copper tube gas boilers water heaters Control manual Wiring continued Field wiring connections for on off and two stage firing options Figure 8...

Page 28: ...OM 1 82 0331 Copyright 2009 Mestek Inc Finned copper tube gas boilers water heaters Control manual Wiring continued Installation of optional BACnet or LonWorks bridge Protocessor for MODBUS operation...

Page 29: ...values Adjusting setpoint temperature while in Standby The local setpoint temperature LOCAL SET or system setpoint temperature 1 SYSTEMSET canbeadjustedusingtheSETUPmenusorbypressingdownthe SELECT ke...

Page 30: ...80 F OPERATE LIM 10 F OP LIM BAND 215 F SETPT SOURCE AUTO OPERATE LIMIT 215 F 45 to 230 F OP LIM BAND 20 F 1 to 50 F SETPT SOURCE AUTO AUTO 4 20MA NOTE If 4 20MA is selected the control setup menu wil...

Page 31: ...E 2 minutes 1 to 60 minutes ALWAYS ENABLED OFF ON or OFF PUMP VALVE OPTION MASTER PUMP VALVE REMAINS ON OFF ON or OFF MASTER PUMP VALVE REMAINS ON OFF FLOW PROVE 10 seconds 10 to 240 seconds FLOW PROV...

Page 32: ...that used J10 B instead of J12 for this interlock PROOFTIME 2 00 minutes 0 to 4 minutes ALARM SILENCE IN USE YES YES or NO ALARM SILENCE SWITCH IN USE YES INPUT J10B SPARE 2 INPUT J10B SPARE 2 see exp...

Page 33: ...ill show NO and addresses must be set from 2 to 16 H NET ADDRESS Master default 255 not changeable Member default 2 Range 2 to 16 MODBUS ADDRESS Default 1 Range 1 to 247 MODULAR BOILER SET ADD BOILER...

Page 34: ...HIGH make sure SETUP SETPOINTS SETPOINT SOURCE is set to AUTO PASSWORD Default AAAAAA Restore to default by pressing while turning ON OFF switch to ON Password mustbe 6characterslong the control will...

Page 35: ...SYSTEM SETPT SETPOINTS Setpoint temperature controlled by the HeatNet control Local setpoint refers to boiler supply temperature System setpoint appears if there is a sensor connected to the SYSTEM HE...

Page 36: ...Specifies where the space heating setpoint temperature comes from AUTO With AUTO selected the HeatNet control determines the setpoint using local setpoint outdoor reset or SYS DHW HEADER temperature s...

Page 37: ...e pump running for the specified time after call for heat is completed allowing distribution of residual heat to the system WARNING The system must be equipped with a bypass pressure regulator or othe...

Page 38: ...for start end TEMP SCALE OPTIONS Select Fahrenheit or Centigrade KEY CLICK OPTIONS If activated the control beeps when a key is pressed SKIP PASSWORD OPTIONS The control can be programmed such that a...

Page 39: ...DELTA AUX FUNCTIONS HEAT EXCHANGER This feature is active if LIM HALF RATE is set to YES see following explanation When the temperature rise through the boiler SUPPLY minus RETURN temperatures rises h...

Page 40: ...um fire when first starting until this amount of time has elapsed MOD MAX LAST FIRE ADVANCED SETUP MODULAR BOILER This sets the maximum firing percentage for boilers during times that some boilers are...

Page 41: ...r recommended action If the trim setting is acceptable press the SELECT key to accept The display will show TRIM VALUE SET After a slight delay the display will return to the sensors menu 4mA SETPOINT...

Page 42: ...D SETUP COMMUNICATIONS Select YES only if a modem is installed LOAD DEFAULTS ADVANCED SETUP Load the factory defaults when you want to be sure nothing has been changed or after you have loaded new fir...

Page 43: ...re does not load correctly the display will remain blank 13 Try running the firmware program again Check that the boiler performs properly 14 Downloading firmware from a flash drive Disconnectwirestot...

Page 44: ...calibrationmode and willshow CALIBRATE on 1 the display The first screen will show the following The value shown for temperature is the 2 SYSTEM or LOCAL setpoint MEMBER boilers will show LOCAL SET i...

Page 45: ...as boilers add heat to the system or demand changes The upper left of the display will show boiler condition 7 prepurge etc astheboilerbeginsitscycle Aftertheboiler begins firing the screen will show...

Page 46: ...PWM of modulation All of the boilers that are firing Master See 3 Figure 12 for an explanation of the data on the screen Noticethesnapshot Thisisalogentry ofwhichthereareupto1 000 4 As soon as you en...

Page 47: ...less than 4 5 VDC OUTDOOR RESET This message indicates that warm weather shutdown is in effect HIGH DELTA TEMP This message occurs when the temperature across the heat exchanger is greater than 40 F L...

Page 48: ...SOR DHW SENSOR This indicates a sensor was detected to be shorted AIR SWITCH BLOWER If the ignition control is called to start and the HeatNet control detects blower operation but no pilot within two...

Page 49: ...a restart every 10 minutes INDEPENDENT damper operation a damper for each boiler The individual boiler is shut down until the fault is corrected and the ON OFF switch is cycled The display continues s...

Page 50: ...R or other temperature whichever had been selected for display The temperature shown is the value detected at the sensor listed FAULT SUPPLY IGNITION CTRL ALARM 168 F Automatically resets control afte...

Page 51: ...ver had been selected for display The temperature shown is the value detected at the sensor listed FAULT SUPPLY OPEN ________ SENSOR 168 F The name of the sensor appears where the _____ is above Autom...

Page 52: ...for the damper Also check to make sure the prove switch is working properly If you are using SPARE 1 and you continue to get the error message after the steps above check the sensor TYPEspecifiedinthe...

Page 53: ...connected to the SYS TEM HEADER input if the boiler is operating as a member Verify that the HNet cables are of a shielded or twisted pair type Shielding of the cable is required c Minimize possible...

Page 54: ...e by routing the communications cables away from electrical d noise sources such as motors ignition controls contactors etc Only the MASTER boiler Fires but the system has many boilers and is using H...

Page 55: ...EMP AT HIGH OA TEMP 140 F 70 F WATER TEMP AT LOW OA TEMP 180 F 10 F PUMP OPTIONS SYSTEM PUMP POST PURGE TIME 2 minutes ALWAYS ENABLED OFF SUMMER PUMP JOG OFF OVR ENAB IN WWS OFF LOCAL PUMP DELTA TEMP...

Page 56: ...SAFE MODES RUN IN LOCAL IF H NET COMM LOST ON SETUP MENU Menu item Default Value LOW TEMP OFF TEMP LESS THAN 40 F HEAT EXCHANGER ALARM TYPE WARNING EXCHR DELTA T 40 F LIM HALF RATE YES DOMESTIC HOT WA...

Page 57: ...tory set not adjustable FIRING MODE FIRING MODE TRUE ROTATION MASTER FIRST OFF SENSORS SENSOR OUTSIDE TYPE TYPE Z CALIBRATED SENSOR SUPPLY TYPE TYPE Z CALIBRATED SENSOR RETURN TYPE TYPE Z CALIBRATED S...

Page 58: ...58 P N HN IOM 1 82 0331 Copyright 2009 Mestek Inc Finned copper tube gas boilers water heaters Control manual Notes...

Page 59: ...59 P N HN IOM 1 82 0331 Copyright 2009 Mestek Inc Finned copper tube gas boilers water heaters Control manual Notes...

Page 60: ...nput Control Inputs AA Heat Demand 4 20ma Enable OA override T1 T2 dry contact inputs Dimensions 9 wide 6 high 2 deep Temperature Sensors NTC thermistor 10K 77 F 335 67K 40 F 185 150 F 1 F Environment...

Reviews: