RBI FUTERA II Series Manual Download Page 19

19

FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS

HEATING SYSTEM PIPING

General Piping Requirements

 

All heating system piping must be installed by a qualified 
technician in accordance with the latest revision of the 
ANSI/ASME Boiler and Pressure Vessel Code, Section IV, 
and ANSI/ASME CSD-1, Standard for Controls and Safety 
Devices for Automatically Fired Boilers. All applicable local 
codes and ordinances must also be followed. A minimum 
clearance of 

1 in

,  25 mm must be maintained between 

heating system pipes and all combustible construction. All  
heating system piping must be supported by suitable 
hangers not the boiler. The thermal expansion of the 
system must be considered when supporting the system. 
A minimum system pressure of 

12 psig

,  82.7 kPa must  

be maintained.

Heating Boiler Piping Connections

The supply and return connections should be sized to suit 
the system, see Table 6.

 

Table 6 – Supply & Return Pipe Sizing

     Model Size             Supply Size  

Return Size  

   500 thru 1000               2" NPT    

    2" NPT 

 1250 thru 1950            2 1/2" NPT             2 1/2" NPT

Pump Requirements

This low mass boiler requires a continuous minimum water 
flow for proper operation. The system pump must be sized 
to overcome the head loss of the boiler and the heating 
system in order to achieve the required temperature rise. 
Table 7 provides the heat exchanger pressure drop and 
temperature rise figures. The temperature rise across the 
boiler must never exceed 

35°F

,  19.4°C. The adjustable 

pump delay turns the pump on each time the burner fires 
and runs the pump for 6 to 600 seconds after the call for 
heat is satisfied.

CAUTION: A temperature rise outside of the range  
listed in Table 7 indicates that the flow rate through 
the heat exchanger is incorrect which will damage  
the heat exchanger voiding the warranty! The 
maximum allowable temperature rise is 35°F, 

19.4°C

.

 

 

The maximum allowable flow rate through a Futera II 

boiler is 97 GPM, 

6.1 L/s

 on 500 through 1000 models 

and 136 GPM, 

8.6 L/s

 for 1250 through 1950 models. 

The Cupro-Nickel heat exchanger allows for 108 GPM, 

6.8 L/s

 on 500 through 1000 models and 151 GPM, 

 

9.5 L/s

 on 1250 through 1950 models.

Table 7 - Temperature Rise 

  

T = 20°F 

 

T = 11.1°C 

 Model 

Flow Rate  Pres. Drop 

Flow Rate 

Pres. Drop

 Number 

GPM Ft 

L/s kPa

 500 

42.5 0.53

 

2.7 1.5

 750 

63.8 1.57

 

4.0 4.6

 1000 

85.0 3.44

 

5.4 10.1

 1250 

106.3 2.11

 

6.7 6.2

 1500 

127.5 3.57

 

8.0 10.5

  

T = 25°F 

 

T = 13.9°C 

 Model 

Flow Rate  Pres. Drop 

Flow Rate 

Pres. Drop

 Number 

GPM Ft 

L/s kPa

 500 

34.0 0.35

 

2.1 1.0

 750 

51.0 1.04

 

3.2 3.1

 1000 

68.0 2.27

 

4.3 6.7

 1250 

85.0 1.40

 

5.4 4.1

 1500 

102.0 2.36

 

6.4 7.0

 1750 

119.0 3.67

 

7.5 10.8

 1950 

132.6 5.14

 

8.4 15.1

  

T = 30°F 

 

T = 16.7°C 

 Model 

Flow Rate  Pres. Drop 

Flow Rate 

Pres. Drop

 Number 

GPM Ft 

L/s kPa

 750 

42.5 0.70

 

2.7 2.2

 1000 

56.7 1.60

 

3.6 4.8

 1250 

70.8 1.00

 

4.5 2.9

 1500 

85.0 1.70

 

5.4 5.0

 1750 

99.2 2.60

 

6.3 7.7

 1950 

110.5 3.70

 

7.0 10.8

  

T = 35°F 

 

T = 19.4°C 

 Model 

Flow Rate  Pres. Drop 

Flow Rate 

Pres. Drop

 Number 

GPM Ft 

L/s kPa

 750 

36.4 0.60

 

2.3 1.6

 1000 

48.6 1.20

 

3.1 3.6

 1250 

60.7 0.70

 

3.8 2.2

 1500 

72.9 1.30

 

4.6 3.7

 1750 

85.0 2.00

 5.4 

5.8

 1950 

94.7 2.80

 6.0 

8.1

Summary of Contents for FUTERA II Series

Page 1: ...uction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be op...

Page 2: ...as Fired Low Pressure Steam and Hot Water Boilers ANSI Z21 56 CSA 4 7 Gas Fired Pool Heaters Canada Only Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160...

Page 3: ...er heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater...

Page 4: ...st be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized p...

Page 5: ...the horizontal combustion air pipe on installations that used the Direct Vent option is 60 ft 18 3 m The maximum equivalent length for the horizontal combustion air pipe on installations that use the...

Page 6: ...61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter re...

Page 7: ...3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertical clearance...

Page 8: ...or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z...

Page 9: ...meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air in...

Page 10: ...10 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 1 Air Intake Vertical or Thru Wall Figure 2 Venting Thru Wall Vertical...

Page 11: ...gle or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wal...

Page 12: ...AND OPERATION INSTRUCTIONS Figure 5 Vertical Air Intake and Venting for Direct Vent System Figure 6 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Page 13: ...venter for the boiler water heater see Table 4 Follow the power venter manufacturer s installation instructions Table 4 Power Venter Sizes VERTICAL CHIMNEY VENT NEGATIVE PRESSURE CATEGORY I The Futer...

Page 14: ...ingle wall vent connection with at least 3 corrosion resistant sheet metal screws Always provide a minimum clearance of 6 in 152 mm between single wall vent pipe and any combustible materials Type B1...

Page 15: ...15 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 8 Vertical Venting with a Metal Chimney System...

Page 16: ...r window or gravity air inlet into any building and at least 3 ft 1 m from any overhang unless local codes dictate differently Avoid locations where wind deflection off of adjacent walls buildings or...

Page 17: ...marche Suivre les instructions d allumage R gler le thermostat de fa on que l appareil fonctionne de fa on continue e Test for spillage at the draft hood relief opening after 5 minutes of main burner...

Page 18: ...water mix that prevents foaming Air entrapped within foam significantly decreases heat transfer and can result in damage to the heat exchanger Products such as DOWFROST DOWTHERM UCARTHERM or an equiva...

Page 19: ...4 C The adjustable pump delay turns the pump on each time the burner fires and runs the pump for 6 to 600 seconds after the call for heat is satisfied CAUTION A temperature rise outside of the range...

Page 20: ...econdary systems In order to prevent boiler s short cycling the system flow must be equal to or higher than the boiler s local flow Low Return Water Temperatures To prevent the problems associated wit...

Reviews: