background image

13

FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS

SIDE WALL VENT, 

POSITIVE PRESSURE, CATEGORY III

In this configuration the boiler/water heater blower is used 
to push the flue products horizontally to the outdoors, see 
Figure 7. The air for combustion is taken from the space  
in which the unit is installed. The applicable instructions 
under the “COMBUSTION AIR & VENTILATION” section 
must be followed! The vent guidelines under the Horizontal 
Direct Vent Systems section must also be followed.

HORIZONTAL VENT, 

NEGATIVE PRESSURE, CATEGORY I

 

In this configuration a wall-mounted power venter must be 
used to pull the flue products horizontally from the unit and 
vent them to the outdoors, see Figures 3, 4 & 7A. The air 
for combustion is taken from the space in which the unit is 
installed, or from the outdoors. The applicable instructions 
under the “COMBUSTION AIR & VENTILATION” section 
must be followed!

To maximize the performance of single wall sheet metal 
vent systems locate 90° elbows as far from the boiler as 
possible and from one another. For best results, horizontal 
vent systems should be as short and straight as possible.
 
When horizontal vent runs exceed 

5 ft,

  1.5 m they  

must be supported at 

3 ft,

 0.9 m intervals with overhead 

hangers. The vent system must be pitched down, toward 
the vent terminal, 

1/4 in/ft,

 21 mm/m. If any part of a single 

wall metal vent system passes through an unheated space 
it must be insulated with insulation rated for 

400°F,

 204°C.

Horizontal vent systems shall terminate at least 

4 ft,

  

1.2 m below, 

4 ft,

  1.2 m horizontally from or 

1 ft,

  

0.30 m above any door, window or gravity air inlet  
into any building. It must not terminate less than 

 

4 ft,

  1.2 m horizontally from, and in no case above  

or below, unless a 

4 ft,

  1.2 m horizontal distance  

is maintained, from electric meters, gas meters, regulators 
and relief equipment and not less than 

7 ft,

  2.1 m from  

any adjacent public walkway.The bottom of the vent 
terminal(s) shall be located at least 

5 ft,

  1.5 m above 

the air intake terminal(s) unless there is a minimum 

5 ft,

  

1.5 m horizontal separation between them. Avoid terminal 
locations likely to be affected by winds, snowdrifts, people 
and pets. Protect building materials and vegetation from 
degradation caused by the flue gases.

To determine the appropriate power venter for the  
boiler/water heater, see Table 4. Follow the power venter 
manufacturer’s installation instructions.

Table 4 - Power Venter Sizes

VERTICAL/CHIMNEY VENT, 

NEGATIVE PRESSURE, CATEGORY I

The Futera II is listed as a Category I appliance when 
vented vertically into a listed metal chimney system or 
properly sized masonry chimney, Figures 8 & 9. The 
chimney must provide a 

negative

 pressure of 

0.01 to 0.08 

in

0.25 to 2.0 mm WC at the boiler/water heater flue collar  

with the unit running. A barometric damper must be 
attached directly to the flue collar increaser as shown. 

Multiple Futera II’s can be vented into a single vertical 
chimney provided that the breeching and chimney are 
properly sized  per the latest revision of the National Fuel 
Gas Code, ANSI Z223.1.

When more than one appliance is connected to the same 
chimney flue, the flue must be large enough to safely vent 
the combined output of all of the appliances.

WARNING: If an appliance using any type of a 

mechanical draft system operating under positive 

pressure is connected to a chimney flue, never 

connect any other appliances to this flue.  Doing  

so can result in excessive levels of carbon 

monoxide which can cause severe personal injury 

or death!

Chimney Inspection & Sizing 

A thorough inspection of the masonry chimney must be 
performed to ensure that the chimney is clean, properly 
constructed and properly sized. Exterior masonry 
chimneys should not be used unless properly lined to 
prevent condensation and draft problems. Table 5 lists the 
mimimum riser connection diameters, negative pressure 
required for the boiler/water heater.

Table 5 - Minimum Riser Connection, Negative 

Pressure

 

Model Size  

Pipe Diameter  

  

in

 mm

 500 

 

 8

   203

 

  750, 1000 

10

 

254

 

1250, 1500 

12

 

305

 

1750, 1950 

14

 

356

Note: Vent system must be sized per tables contained in NFPA 54 or 
an engineered system

.

Vent Connections

Locate the boiler/water heater as close to the chimney as  
possible. Use the shortest, straightest vent connector 
possible for the installation. If horizontal runs exceed 

5 ft

1.5 m they must be supported at 

3 ft

,

 

0.9 m intervals with 

overhead hangers. Use a type B, single wall stainless or 
single wall galvanized steel vent pipe the same diameter 
as the flue collar to connect the boiler/water heater to a 
masonry chimney, see Figure 2. When using a listed metal 
chimney system use the appropriate vent connector.

  Futera II 

Power Venter 

Max. Pipe Length

  Model  

Model 

FT  

m

  500 - 750 

HS-3 

100

 

31

 1000-1250 

HS-4 

100

 

31

 1500-1950 

HS-5 

100

 

31

Summary of Contents for FUTERA II Series

Page 1: ...uction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be op...

Page 2: ...as Fired Low Pressure Steam and Hot Water Boilers ANSI Z21 56 CSA 4 7 Gas Fired Pool Heaters Canada Only Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160...

Page 3: ...er heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater...

Page 4: ...st be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized p...

Page 5: ...the horizontal combustion air pipe on installations that used the Direct Vent option is 60 ft 18 3 m The maximum equivalent length for the horizontal combustion air pipe on installations that use the...

Page 6: ...61 cm from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter re...

Page 7: ...3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 4 ft 1 2 m below or to side of opening 1 ft 300 mm above opening C Clearance to permanently closed window D Vertical clearance...

Page 8: ...or balcony is fully open on a minimum of two sides beneath the floor NOTES 1 In accordance with the current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z...

Page 9: ...meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent terminal s shall be located at least 5 ft 1 5 m above the air in...

Page 10: ...10 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 1 Air Intake Vertical or Thru Wall Figure 2 Venting Thru Wall Vertical...

Page 11: ...gle or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wal...

Page 12: ...AND OPERATION INSTRUCTIONS Figure 5 Vertical Air Intake and Venting for Direct Vent System Figure 6 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT...

Page 13: ...venter for the boiler water heater see Table 4 Follow the power venter manufacturer s installation instructions Table 4 Power Venter Sizes VERTICAL CHIMNEY VENT NEGATIVE PRESSURE CATEGORY I The Futer...

Page 14: ...ingle wall vent connection with at least 3 corrosion resistant sheet metal screws Always provide a minimum clearance of 6 in 152 mm between single wall vent pipe and any combustible materials Type B1...

Page 15: ...15 FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS Figure 8 Vertical Venting with a Metal Chimney System...

Page 16: ...r window or gravity air inlet into any building and at least 3 ft 1 m from any overhang unless local codes dictate differently Avoid locations where wind deflection off of adjacent walls buildings or...

Page 17: ...marche Suivre les instructions d allumage R gler le thermostat de fa on que l appareil fonctionne de fa on continue e Test for spillage at the draft hood relief opening after 5 minutes of main burner...

Page 18: ...water mix that prevents foaming Air entrapped within foam significantly decreases heat transfer and can result in damage to the heat exchanger Products such as DOWFROST DOWTHERM UCARTHERM or an equiva...

Page 19: ...4 C The adjustable pump delay turns the pump on each time the burner fires and runs the pump for 6 to 600 seconds after the call for heat is satisfied CAUTION A temperature rise outside of the range...

Page 20: ...econdary systems In order to prevent boiler s short cycling the system flow must be equal to or higher than the boiler s local flow Low Return Water Temperatures To prevent the problems associated wit...

Reviews: