Fi
d
b
b il
&
h
B il
M
l
Finned copper tube gas boilers & water heaters – Boiler Manual
28
F
F
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
POUR VOTRE SÉCURITÉ LISEZ AVANT DE
METTRE EN MARCHE
A. Th is appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by
hand.
Cet appareil est muni d'un dispositif d'allumage qui allume
automatiquement la veilleuse. Ne tentez pas d'allumer la veilleuse
manuellement.
B. BEFORE OPERA
TING smell all around the appliance area
for gas. Be sure to smell next to the fl oor because some gas
is heavier than air and will sett le on the fl oor.
Propane gas may not always be detected by smell.
Propane gas is heavier than air and can collect in low
areas.
Propane gas can ignite or explode if an ignition source is
present and result in death, serious injury and property
damage!
FOR YOUR SAFETY
• Have only qualifi ed licensed professionals install, service and
maintain this appliance and your gas system in accordance with
all applicable codes.
• Install a nationally listed combustible gas detector(s) in your
home.
• If you suspect a leak:
1. Have everyone leave the building immediately.
2. Do not att empt to light any appliance.
3. Do not touch any electrical or electronic switches in the
building.
4. Do not use any phone in the building.
5. Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the fi re department.
AVANT DE FAIRE FONCTIONNER, renifl ez tout autour de
l'appareil pour déceler une odeur de gaz. Renifl ez près du plancher,
car certains gaz sont plus lourds que l'air et peuvent s'accumuler au
niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones
se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un
voisin. Suives les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur, appelez le service de
incendies.
C. Do not use this appliance if any part has been under water.
Immediately call a qualifi ed service technician to inspect the
appliance and to replace any part of the control system and any
gas control that has been under water.
N'utilisez pas cet appareil s'il a été plongé dans l'eau, même
partiellement. Faites inspecter l'appareil par un tecnicien qualifi é
et remplacez toute partie du système de contrôle et toute
commande qui ont été plongés dans l'eau.
To prevent being burned, stand clear of the boiler
during ignition and don’t touch any hot metal parts!
Operating Instructions
1.
STOP!
Read the safety information above. If, at any time,
the appliance will not operate properly, follow the instructions
“TO TURN OFF GAS TO APPLIANCE”.
2. Set the operating control or thermostat to off or its lowest sett ing.
3. Turn off all electric power to the appliance.
4. Close the main manual gas shut-off valve, Figure 16.
5. Make sure that the gas supply piping has been purged of air
and that all gas joints up to the gas valve have been thoroughly
checked for leaks.Wait fi ve (5) minutes to clear out any gas. Th en
smell for gas, including near the fl oor. If you smell gas,
STOP!
Follow “B” in the safety information above (to the left ) on this
label. If you don’t smell gas, go to the next step.
6. Remove the upper front jacket panel.
7. Turn the knob on the pilot valve to off .
8. Turn the knob on the main gas valve to off , 300 & 400 models,
Figure 18. On 600 through 2100 models close the manual shutoff
valve located in the control compartment, Figure 19.
9. Locate pilot and manifold pressure taps in the upper compartment.
Remove the 1/8" screw plugs.
10. Connect a
20 in
,
508 mm
W.C. manometer to each tapping,
see Figure 19.
Figure 18
Pilot Valve (All Models)
Main Valve (300 & 400 Models)