background image

DOMINATOR INSTALLATION AND OPERATION INSTRUCTIONS

Page 30

CHECKING & ADJUSTMENTS

1.   With the burners in operation, close the manual 

shutoff valve in the gas supply line. As soon as the 
main burner fl ames go out, open the manual shutoff 
valve. A normal ignition sequence should take place. 
If the burners fail to light, the gas valves will close 
and the system will go into a 5-minute lock out 
period. The ignition module will then make a second 
ignition attempt. If the unit won't light ensure that the 
gas piping is fully purged of air. Inspect the ignition 
system and ensure that it is operating properly.

2.   To test the ignition safety shutoff device, close the 

manual shutoff valve in the gas supply line. Within 5 
seconds of main burner fl ame extinction, the main 
gas valve solenoid should close with an audible noise.
The pilot light on the display board should be lit while 
the ignition module tries to relight the pilot. After 10 
seconds the module should lockout and the trial for
ignition end. After 5 minutes a second trial for ignition 
should occur. Open the manual shutoff valve in the 
gas supply line and reset the ignition control system. 
A normal ignition sequence should take place.

3.   With the burners in operation, interrupt the power to 

the control circuit by reducing the target temperature 
of the staging controller or turning down the 
thermostat. The boiler/water heater should stage 
down and shut down. Reset the operating control or 
thermostat. A normal ignition sequence should follow.

Input Rate, Natural Gas

Gas appliances are rated based on sea level operation 
with no adjustment required at elevations up to 

5000 ft

1524 m

. At elevations above 

5000 ft

1524 m

, input 

ratings should be reduced by 4% for each additional 

1000 ft

305

 

m

.

Check the input rate as follows:
1.   Turn off all other gas appliances that use the same 

gas meter as the boiler/water heater.

2.   Call your gas supplier and ask for the heating value 

of the gas.

3.  Connect a fl ue gas analyzer to the vent pipe.
4.   Start the boiler/water heater and let it run for 15 

minutes.

5.   Using the gas meter and a stopwatch, clock the time 

that it takes to burn 

10 ft

3

0.28 m

3

 of gas and divide 

this time by 10. 

6.   Insert the heating value and the time, in seconds, 

into the formula below.

7.   Input = (heating value, Btu/hr)(3600)/(time, seconds)

8.   If the computed rate deviates by more than 5% from 

the rated input value of the unit adjust the manifold 
pressure accordingly. DO NOT adjust the manifold 
pressure by more than 5%. If a proper rate cannot 
be maintained without adjusting the manifold 
pressure beyond the 5% limit, the main burner 
orifi ces must be replaced. If the input rate is too low, 
go to the next larger size of main burner orifi ces. If 
the input rate is too high, go to the next smaller size.

9.  

At full input the CO

2

 should be between 7.5% 

and 8.5% with a CO reading of less than 50 ppm. 
See Table  20. 

CAUTION: Never increase the input of the boiler/
water heater above that for which it is rated. Doing 
so can cause premature failure of the unit! 

Pilot Adjustment

The pilot burner is actually an isolated main burner that 
stages with the other burners. It is controlled by a 
separate pilot valve. Pilot pressure settings are as shown 
in Table 19. These pressures are measured at the pilot 
pressure valve, see Figure 19. See Tables 12 and 13 to 
determine the fi ring mode that is associated with each 
stage.

To view the pilot without main burner operation, take the 
following steps:

For D300-D400:

1.   Remove the upper front jacket panel.
2.   Turn off main burner gas fl ow by turning the main 

burner gas valve knob to the off position, Figure 18.

3.   Observe the pilot fl ame through the observation port 

located at the left end of the unit.

For D600-D2100:

1.   Remove the upper front jacket panel.
2.   Turn off main burner gas fl ow by turning the manual 

gas valve(s) in the control compartment to the off 
position, see Figure 19. 

3.   Observe the pilot fl ame through the observation port 

located at the left end of the unit.

Pilot pressures will be set at the factory. However, if it 
is necessary to adjust the pilot pressure to match those 
in Table 19, take the following steps:
1.   Remove the upper front jacket panel.
2.   Remove the 1/8" plug from the pilot pressure test 

port and connect a 

20 in

508 mm

 W.C. manometer 

to it, see Figure 18.

3.   Remove the gas pressure regulator cap from the 

pilot valve. See Figure 18 for the location of the 
regulator and cap.

Summary of Contents for DB series

Page 1: ...gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not us...

Page 2: ...tallation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 In Canada the installation must be in accordance with the requirements of CSA B14...

Page 3: ...ed directly on combustible flooring but never on carpeting 4 Locate the boiler water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine mai...

Page 4: ...the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Figure 1 Vertical Venting with a Metal Chimney System and Inside Air CAUT...

Page 5: ...ical Venting using a Masonry Chimney and Inside Air Figure 3 Horizontal Venting using Inside Air 1 5 FT 0 5 m 1 4 IN PER F00T 20 mm m Table 2 305 TO 457 127 TO 254 VENT PIPE DIAMETER 5 TO 10 12 TO 18...

Page 6: ...2 per 7 000 Btuh 310 mm2 per kW up to and including 1 million Btuh plus 1 in2 per 14 000 Btuh 155 mm2 per kW in excess of 1 million Btuh Intake Air Option General Guidelines This configuration provide...

Page 7: ...ts exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wall or insulated inle...

Page 8: ...d Venting Metal Chimney System Shown Locate exhaust terminal downwind from air intake to reduce potential for flue gas recirculation Figure 7 Combination Air Intake And Venting Masonry Chimney Shown 1...

Page 9: ...ied by installer All venting material must be approved for the application Consult the vent manufacturer s product literature GENERAL VENTING GUIDELINES WARNING The vent installation must be in accord...

Page 10: ...chimneys the connector must terminate flush with the inside of the chimney flue Figure 2 Fasten each single wall vent connection with at least 3 corrosion resistant sheet metal screws WARNING Never i...

Page 11: ...ow unless a 4 ft 1 2 m horizontal distance is maintained from electric meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the...

Page 12: ...zontale qui conviennent et s assurer que le syst me est exempt d obstruction d tranglement de fruite de corrosion et autres d faillances qui pourraient pr senter des risques c Insofar as is practical...

Page 13: ...r supplies MUST be shut off and the unit and its pump completely drained CAUTION Improper outdoor installation of this boiler water heater can cause boiler failure voiding the manufacturer s warranty...

Page 14: ...t L s kPa 300 34 0 0 22 2 1 0 6 400 45 4 0 49 2 9 1 5 600 68 1 1 30 4 3 3 8 750 85 1 2 35 5 4 6 9 900 102 1 3 84 6 4 11 3 1050 119 1 6 23 7 5 18 4 T 20 F T 11 1 C Model Flow Rate Pres Drop Flow Rate P...

Page 15: ...must be used to prevent the chilled water from entering the boiler When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device the piping system m...

Page 16: ...int T1 Temp Min 110 For Atmospheric T1 Temp Min 125 Sealed Combusion 1 Turn heater on and open valves A B 2 After steady state operation if T1 is less than Temp Min slowly close valve B until T1 climb...

Page 17: ...y mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units Notice...

Page 18: ...exceeding 350 ppm Water having a hardness less than 8 grains can cause excessive errosion of the heat exchanger Water that has a hardness greater than 18 grains per gallon and or a level of dissolved...

Page 19: ...DOMINATOR INSTALLATION AND OPERATION INSTRUCTIONS Page 19 Table 8A Dominator Heat Exchanger Selection Graph Table 8B Dominator Pumping Performance Requirement...

Page 20: ...he warranty The method outlined below can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting th...

Page 21: ...ion 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 hole in check val...

Page 22: ...tom of the vertical section of the gas supply pipe upstream of the gas controls A ground joint union should be installed between the boiler gas controls and the supply piping Each of these items are n...

Page 23: ...hecked to ensure that the correct water level in the tank is maintained The tank should be less than half full of water with the system full and adjusted to the correct operating pressure WARNING Neve...

Page 24: ...trapped in the heating system piping Close the make up water valve and check and clean the strainers and make up water pressure reducing valve Open the make up water valve and adjust the system pressu...

Page 25: ...for as long as the call for heat exists The blower pump and power venter will remain for as long as a call for heat exists On the four stage units the left low fire and high fire switches will interr...

Page 26: ...ls 2 A powered alarm contact 2A max 24 VAC is available to provide an audio or visual indication of faults related only to the staging control s operation This contact is wired to the junction box for...

Page 27: ...be switched or turned off as required Stage 1 will be on first last and whenever the boiler operates NOTE For a change from stage 2 to 3 or 3 to 4 10 second DOM time delays were added to the pressure...

Page 28: ...hones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suives les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur appelez le service...

Page 29: ...cific job site requirements Table 19 Pilot Manifold Settings Table 20 Combustion Readings Instructions De Mise En Marche 1 ARR TEZ Lisez les instructions de s curit sur la portion sup rieure de cette...

Page 30: ...me that it takes to burn 10 ft3 0 28 m3 of gas and divide this time by 10 6 Insert the heating value and the time in seconds into the formula below 7 Input heating value Btu hr 3600 time seconds 8 If...

Page 31: ...ow Adjustment 1 Remove the upper front jacket panel 2 Connect both sides of a manometer to the pressure switch tee Figure 18 going to one of the pressure switches 3 With the unit operating at high fir...

Page 32: ...r flow These time delays are set within the separate time delay board connected to the relay board Gas Pressure Switch An optional low and or high gas pressure switch will shut down the 24V circuit if...

Page 33: ...wired to these terminals In this case the control will temporarily override outdoor reset and increase the target temperature to 180 F 82 C to provide sufficient heat to satisfy the DHW requirement M...

Page 34: ...d impair the boiler water heater s performance Refer to page 39 for component identification CAUTION Improper burner servicing can result in premature burner failure voiding the warranty Burner Inspec...

Page 35: ...eat exchanger out of the unit 10 Remove the V baffle straps and V baffles 11 Thoroughly inspect the heat exchanger for signs of damage If there is no damage clean the heat exchanger with water from a...

Page 36: ...ter at normal system pressure If it does contact a qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replac...

Page 37: ...Venter Power venter contact not wired Wire power venter contact to J box Power venter not wired to Wire power venter as shown in external power connection diagram Relay fault Replace relay Power vente...

Page 38: ...just as necessary Main valve s malfunctioning Replace main valve s Insufficient Heating Target temperature too low Increase stage control target temperature Primary safety high limit set Increase limi...

Page 39: ...DOMINATOR INSTALLATION AND OPERATION INSTRUCTIONS Page 39 Figure 28 Replacement Parts RIOM 22 REV B...

Page 40: ...06 1 1 70 2707 1 1 70 2708 1 1 70 2709 1 1 70 2710 1 1 70 2711 1 1 70 2712 1 1 70 2713 1 1 70 2714 1 1 70 2715 1 1 3 Jacket Left Side Panel 03 1822 1 1 1 1 1 1 1 1 1 1 Jacket Left Side Panel SS 03 182...

Page 41: ...09 1 03 1810 1 Jacket Top Panel SS 03 1801 1 1 03 1802 1 1 03 1803 1 1 03 1804 1 1 03 1805 1 1 03 1806 1 1 03 1807 1 1 03 1808 1 1 03 1809 1 1 03 1810 1 1 Jacket Top Panel Outdoor 70 2969 1 70 2970 1...

Page 42: ...1 1 1 1 1 Comb Chamber Lower Right Side Panel 70 2773 1 1 1 1 1 1 1 1 1 1 18 Comb Chamber Upper Left Side Panel 70 2770 1 1 1 1 1 1 1 1 1 1 Comb Chamber Upper Right Side Panel 70 2771 1 1 1 1 1 1 1 1...

Page 43: ...11 13 17 19 25 27 Main Orifice LP 10 0088 3 7 9 11 13 17 19 25 27 Main Orifice NG 10 0115 5 Main Orifice LP 10 0116 5 NS Pilot Orifice NG 10 0089 1 1 1 1 1 1 1 1 1 Pilot Orifice LP 10 0090 1 1 1 1 1 1...

Page 44: ...0 2863 1 70 2864 1 70 2865 1 32 Tube Bundle Copper 70 2901 1 70 2902 1 70 2903 1 70 2904 1 70 2905 1 70 2906 1 70 2907 1 70 2908 1 70 2909 1 70 2910 1 Tube Bundle Cupronickel 70 2911 1 70 2912 1 70 29...

Page 45: ...1 1 1 1 51 Flame Sensor UTC 1003 Ignition Module 16 0059 1 1 1 1 1 1 1 1 1 1 NS Alarm Board CSD 1 16 0023 1 1 1 1 1 1 1 1 1 1 52 Spark Generator Q652B 16 0008 1 1 1 1 1 1 1 1 1 1 53 Transformer 50 VA...

Page 46: ...1 1 1 1 1 1 NS Silicone 66 0151 1 1 1 1 1 1 1 1 1 1 Vent Termination Hood 6 09 0112 1 1 Vent Termination Hood 7 09 0140 1 Vent Termination Hood 8 09 0113 1 Vent Termination Hood 10 09 0115 1 1 Vent Te...

Page 47: ...R PROVIDED VENT STACK CONNECTED PROPER SERVICE CLEARANCE PROVIDED IS VENT VERTICAL THROUGH THE ROOF OUTDOOR AIR SENSOR INSTALLED WIRED IS VENT THROUGH THE WALL ARE UNITS RACKED IS POWER VENT INSTALLED...

Page 48: ...Temp CO PPM Stack Draft Must Be Negative Pilot Signal SAFETY CONTROL CHECK Low Water Cut Off PPM Factory Flow Switch Operating Control High Limit Differential Air Switch STG 1 2 Differential Air Switc...

Page 49: ...izontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS g INSPECTION...

Page 50: ...DOMINATOR INSTALLATION AND OPERATION INSTRUCTIONS Page 50...

Page 51: ...nd erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump per...

Page 52: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Reviews: