SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 22

Shut the boiler off and open the bleed valves to purge
the air trapped in the heating system piping. Close the
make-up water valve and check and clean the strainers
and make-up water pressure reducing valve.

Open the make-up water valve and adjust the system
pressure if necessary. The system should be checked
and bled after three days of operation.

OPERATING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE OPERATING

POUR VOTRE SÉCURITÉ LISEZ AVANT DE
METTRE EN MARCHE

A. This appliance is equipped with an ignition device

which automatically lights the pilot. Do 

not try to light

the pilot by hand.

Cet appareil est muni d’un dispositif d’allumage qui
allume automatiquement la veilleuse. Ne tentez pas
d’allumer la veilleuse manuellement.

B.

BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor.

DANGER: Propane gas may not always be
detected by smell. Propane gas is heavier than
air and can collect in low areas.

Propane gas can ignite or explode if an ignition
source is present and result in death, serious
injury and property damage!

FOR YOUR  SAFETY

•Have only qualified licensed professionals install,

service and maintain this appliance and your gas
system in accordance with all applicable codes.

•Install a nationally listed combustible gas

detector(s) in your home.

• If you suspect a leak:

1. Have everyone leave the building immediately.
2. Do not attempt to light any appliance.
3. Do not touch any electrical or electronic switches

in the building.

4. Do not use any phone in the building.
5. Call your gas supplier from a phone outside of

the building.

6. If you cannot reach your gas supplier call the fire

department.

AVANT DE FAIRE FONCTIONNER, reniflez tout autour
de l’appareil pour déceler une odeur de gaz. Reniflez
près du plancher, car certains gaz sont plus lourds que
l’air et peuvent s’accumuler au niveau du sol.

QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:

• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir

des téléphones se trouvant dans le bâtiment.

• Appelez immédiatement votre fournisseur de gaz

depuis un voisin. Suives les instructions du
fournisseur.

• Si vous ne pouvez rejoindre le fournisseur, appelez

le service de incendies.

C. Do not use this appliance if any part has been under

water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of
the control system and any gas control that has
been under water.

N’utilisez pas cet appareil s’il a été plongé dans
l’eau, même par tiellement. Faites inspecter
l’appareil par un tecnicien qualifié et remplacez
toute par tie du système de contrôle et toute
commande qui ont été plongés dans l’eau.

CAUTION: To prevent being burned, stand clear of
the boiler during ignition and do not touch any hot
metal parts!

OPERATING INSTRUCTIONS

1.

STOP!

 Read the safety information above. If, at any

time, the appliance will not operate properly, follow
the instructions “TO TURN OFF GAS TO
APPLIANCE.”

2.

Set the operating control or thermostat to off or its
lowest setting.

3.

Turn off all electric power to the appliance.

4.

This appliance is equipped with an ignition device
which automatically lights the pilot. Do 

not try to light

the pilot by hand.

5.

Close the manual main and pilot gas shut-off valves.

6.

Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas, 

STOP!

 Follow “B” in the safety information

above. If you don’t smell gas go to next step.

7.

Connect a manometer having a minimum capacity of

20 in

508 mm W.C. to the outlet pressure port of the

gas valve. Make sure that the gas supply piping has
been purged of air and that all gas joints up to the gas
valve have been thoroughly checked for leaks.

8.

Open the manual pilot valve.

9.

Turn on all electric power to the boiler.

10. Set the operating control or thermostat to the

desired setting.

11. The pilot(s) should automatically light. Do not try to

light the pilot(s) by hand!

12. With the pilot(s) lit, open the main gas shut-off valve.
13. The bur ners should light with proper boiler

operation.

14. The pilot and manifold pressures should match

those listed in Table 10. To adjust the manifold gas
pressure see the Gas Pressure Adjustment
instructions in the “CHECKING AND ADJUSTMENTS”
section.

Summary of Contents for 8800 Series

Page 1: ...e or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch...

Page 2: ...8800 and 8900 finned copper heating boiler water heater pool heater To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instru...

Page 3: ...imum site will be level central to the piping system close to a chimney and have adequate fresh air for combustion Ensure that the boiler water heater is level from front to back and from side to side...

Page 4: ...a confined space minimum clearances listed in Table 1 or 1A must be maintained between the boiler water heater and any combustible construction When installed in a confined space Figures 1 2 3 4 and 5...

Page 5: ...he free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of...

Page 6: ...age 6 Figure 2 Vertical Venting Using A Masonary Chimney And Inside Air 8900 8800 Series Figure 3 Dual Flue Outlets And Inside Air 8900 8800 Series 10 FT 3 1 m 3 FT 1 m 5 FT 1 52 m 3 FT 1 m 10 FT 3 4...

Page 7: ...0FT 3 1 m 3 FT 1 m 5 FT 1 52 m PITCH PIPE DOWN TOWARDS TERMINAL CAP 1 4 IN PER FOOT 20MM M OF RUN TO ALLOW FOR CONDENSATE DRAINAGE BUILDING OVERHANG 4 FT 1 2 M MAX 3 FT 9 m 1 5 FT 0 5m MINIMUM DISTANC...

Page 8: ...large enough to safely vent the combined output of all the appliances WARNING If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney f...

Page 9: ...ord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisin re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse ma...

Page 10: ...ly piping adjacent to the boiler outlet connection CAUTION Failure to properly install the flow switch may result in damage to the boiler water heater heat exchanger voiding the warranty HEATING SYSTE...

Page 11: ...ow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop Flow Rate Press Drop GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa GPM Ft L s kPa 4 0 4 3 4 7 5 0...

Page 12: ...ow Return Water Temperatures To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary secondary piping system with a bypass and...

Page 13: ...erature slowly close valve A to adjust to lower desired temperature above Temp Min 4 Check after system operating temperature has stabilized Make final adjustments 5 Follow same adjustment procedure f...

Page 14: ...e diameter must be sized large enough to handle maximum flow through all units NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2 Boiler pump sized to boile...

Page 15: ...tion of the pump size and temperature rise A cupro nickel heat exchanger may also be required The manufacturer should be consulted when these water conditions are encountered See Table 7A CAUTION The...

Page 16: ...elow can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exch...

Page 17: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17 Table 7B 8900 Pumping Performance RequirementTable...

Page 18: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 18 Table 7B 8800 Pumping Performance RequirementTable...

Page 19: ...rformance Table before making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Co...

Page 20: ...type of gas available at the installation site call the nearest RBI representative to resolve the problem NOTE A minimum gas supply presssure of 6 in 152 mm W C natural or 11 in 279 mm W C propane and...

Page 21: ...diagram supplied with the boiler water heater for proper wiring connections GENERAL OPERATION WARNING Before proceeding read and fully understand the instructions contained in this manual Do not attem...

Page 22: ...n interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suives les instructions du fournisseur Si vous ne pouvez r...

Page 23: ...reil ne se met pas en marche suivez les instructions intitul es Comment couper l admission de gaz de l appareil et appelez un technicien qualifi ou le fournisseur de gaz inches W C mm W C Natural 3 5...

Page 24: ...screw cap and manifold pressure tap plug CAUTION Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur PROPANE GAS Optimum results are obtained when t...

Page 25: ...water is 130 F 54 C The operating control should be set to the lowest setting that will satisfy the consumer s needs WARNING Setting the thermostat or operation control too high can result in scaldin...

Page 26: ...at exchanger and burner tray components for sign of corrosion and or deterioration 4 Clean or replace components as required CAUTION Improper burner servicing can result in premature burner failure vo...

Page 27: ...ter cutoff operate properly If not replace them 3 The flow switch contacts must be open when water flow is not present 4 The relief valve should not weep or discharge water at normal system pressure I...

Page 28: ...ose or broken wire between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused...

Page 29: ...f valve is properly sized for the system never exceed 160 psi Expansion tank is waterlogged Ensure expansion tank is properly sized for the system Expansion tank is isolated Ensure valve between expan...

Page 30: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 30 PARTS LIST MODELS 420 1900 36 33...

Page 31: ...t 03 0113 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 RH Lower Front Corner Post 03 0114 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5 24 Jacket End Panels Upper Lower 72 0016 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6 Inlet Outlet Header...

Page 32: ...17 19 21 23 25 27 29 31 33 35 Burner Tube w Bracket 70 0635 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NS Burner Spacers 70 0363 1 70 0364 1 70 0365 1 70 0366 1 70 0367 1 70 0368 1 70 0369 1 70 0370 1 70 0371 1 7...

Page 33: ...1 1 1 1 Main Gas Valve V4944B 1 1 2 120V 11 0168 1 1 17 A Valve 1 11 0465 1 1 1 1 1 1 A Valve 1 1 4 11 0466 1 1 1 1 1 1 1 A Valve 1 1 2 11 0467 1 1 NS Bracket Refractory Upper End 03 0306 2 2 2 2 2 2...

Page 34: ...70 0189 1 70 0190 1 70 0191 1 NS Upper Rear Refractory Channel 70 0162 1 70 0163 1 70 0164 1 70 0165 1 70 0166 1 70 0167 1 70 0168 1 70 0169 1 70 0170 1 70 0171 1 70 0172 1 70 0173 1 70 0174 1 70 0175...

Page 35: ...0057 1 27 Jacket Top Panel 03 0001 1 03 0002 1 03 0003 1 03 0004 1 03 0005 1 03 0006 1 03 0007 1 03 0008 1 03 0009 1 03 0010 1 03 0011 1 03 0012 1 03 0013 1 03 0014 1 03 0015 1 27a Jacket Top Panel Du...

Page 36: ...1 70 0086 1 NS Heat Exchanger Assembly Cupronickel 70 0087 1 70 0088 1 70 0089 1 70 0090 1 70 0091 1 70 0092 1 70 0093 1 70 0094 1 70 0095 1 70 0096 1 70 0097 1 70 0098 1 70 0099 1 70 0100 1 70 0101...

Page 37: ...1 1 1 1 1 1 1 Solenoid Valve w Regulator LP 120V 11 0374 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NS Pilot Valve H91WG 24V prior to 0905 11 0017 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Pilot Valve V4046C 120V prior to 09...

Page 38: ...30 32 34 36 Orifice 47 LP 10 0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 49 2 000 3 999 LP 10 0010 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 51 4 000 5 999 LP 10 0099 8 10 12 14...

Page 39: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 39 PARTS LIST MODELS 2000 4000 22 7 36 33 30 8 6 39 42 18 21 25 19...

Page 40: ...n Headers 57 0226 24 24 24 24 24 24 NS Nut Inlet Outlet Return Headers 57 0492 24 24 24 24 24 24 NS Heat Exchanger V Baffle 03 1147 15 03 1148 30 03 1149 30 03 1150 30 03 1151 30 03 1152 30 12 Base Fr...

Page 41: ...2 FM Only 11 0455 1 1 18 End Refractory Panel Left Right 05 0050 2 2 2 2 2 2 19 Center Refractory Panel 853413 4 4 6 8 8 10 20 Corner Refractory Panel 05 0052 4 05 0053 4 05 0054 4 05 0055 4 05 0056 4...

Page 42: ...0V 70 9014 1 1 1 1 1 1 Ignitor PSE NA29 LP 24V 70 0631 1 1 1 1 1 1 Ignitor PSE NA185 LP 120V 70 0632 1 1 1 1 1 1 33 Solenoid Valve w Regulator NG 24V 11 0373 1 1 1 1 1 1 Solenoid Valve w Regulator LP...

Page 43: ...28 32 36 40 Orifice 19 2 000 3 999 NG 10 0007 20 24 28 32 36 40 Orifice 22 4 000 5 999 NG 10 0095 20 24 28 32 36 40 Orifice 25 6 000 7 999 NG 10 0097 20 24 28 32 36 40 Orifice 34 LP 10 0021 20 24 28...

Page 44: ...the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next ad...

Page 45: ...led instructions for the installation of the venting system design or the venting system components and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREME...

Page 46: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 46...

Page 47: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 47...

Page 48: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Reviews: