Components Supplied by Others
• 40mm Trap
• Stop valve
• Electrical outlet
• Mounting fixings
Hydraulic Requirements
Operating pressure:
200-500kPa
Inlet:
G1/2B
Outlet:
40mm BSP Waste
Water Temp:
4o - 32o
Provide 102mm minimum clear space on fixture sides to allow for proper ventilation through cabinet louvers.
Due to cold waste water, we recommend the trap supplied by installer be insulated to prevent excessive condensation.
Rough-in and Dimensions
Prior to roughing-in consult with local, state, and federal codes for proper mounting height. Installation to be done in
accordance with AS/NZS3500.1 and AS/NZS3500.2
12
7
33
8
46
5
235
235
470
FFL
73
162
162
73
470
45
4
77
8
CL
108
34
55
146
201
34
51
ø6.5
ø1
0
40
3
G1/2" INLET
TRAP OUTLET
TO SUIT 40mm WASTE
15
2
33
8
83
8
35
470
Pipe Installation [with bottle filler option]