8
www.raytecled.com
UK / Europe Tel: +44 (0) 1670 520055
Americas Tel: +1 613 270 9990
Notes
•
The luminaire will switch off momentarily (<0.5sec) during the transition between a
test and normal operation.
•
If a test was interrupted by a mains failure, the test will be halted, and the unit will
enter emergency mode. Once the mains supply is back, the unit will allow 24 hours
to recharge the battery before continuing the tests.
•
The self-test is carried out at a random time to eliminate the possibility of having more
than one unit undergoing the test at the same time.
LED indication
c. Self-test
•
Carried out at a random time every 3 months.
•
Checks the battery’s capacity and lamp’s condition.
•
Performs self-recovery for the battery if not at peak capacity.
•
Is carried out at 100% load
•
Discharges only 2/3 of the battery’s capacity.
LED Indication
Condition
Static Amber
Commissioning in progress
Flashing Amber
Discharge cycle in progress
LED will flash in relevant colour while discharging
Static Red
Battery defective/Fuse blown
PSU error
Battery not at peak capacity
Light engine failure
No light
Emergency mode activated
Static Green
Commissioning completed