45
Troubleshooting—Pumps
Failure To Pump
1. Pump not properly primed.
2. Wrong direction of rotation.
3. Speed too low.
4. Total head too high.
Reduced Capacity and/or Head
1. Air pockets or leaks in suction line.
2. Clogged impeller.
3. Foot valve strainer too small or clogged.
4. Excessive suction lift (over 15 feet).
5. Insufficient positive suction head (for hot water).
6. Total head more than that for which pump is
intended.
7. Excessively worn impeller and wearing rings.
Rapid Wear of Coupling
1. Misalignment or a bent shaft.
2. Sagging motor mounts (over-oiling).
Pump Loses Prime
1. Air leaks in suction line.
2. Excess air in water.
3. Water seal in stuffing box not functioning.
4. Excessive suction lift and pump operating too near
shut-off point.
Overloaded Driving Unit
1. Head much lower than that for which pump is
designed.
2. Speed too high or higher than that contemplated.
Mechanical Troubles and Noise
1. Misalignment.
2. Excessive suction lift or vapor binding (hot water).
3. Bent shaft and/or damaged bearings.
4. Suction and discharge piping not properly support-
ed and anchored.
SERVICE AND
MAINTENANCE
PROCEDURES
Tube Cleaning
Establish a regular inspection schedule, the frequency
depending on the local water condition and severity of
service. Do not let the tubes clog up solidly. Clean out
deposits over 1/16" in thickness.
The heater may be cleaned from the side opposite the
water connections as shown, without breaking pipe
connections. It is preferable, however, to remove both
headers for better visibility through the tubes and to be
sure the residue does not get into the system. Note
that you do not remove the top pan or the heat
exchanger generally. After reaming with the auger,
mount the wire brush and clean out the debris remain-
ing in the tubes. Another method is to remove the heat
exchanger, ream tubes and immerse heat exchanger
in noninhibited de-scale solvent.
RAYPAK TUBE CLEANING KIT
Extension Pieces (5)
Auger with Carbide Tip
Wire Brush
P/N 052871F - 5/8 DIA.
P/N 052870F - 7/8 DIA.
Fig. 37: Raypak Tube Cleaning Procedure
Summary of Contents for RAYTHERM 133
Page 15: ...15 Fig 9 Indoor Top Installation...
Page 24: ...24 Piping Diagram Type WH Unitemp 80 System...
Page 28: ...28 Location of Controls 0400 WH1 WH2 WH3 0181 LOW NOx WH1...
Page 29: ...29 Location of Controls 0824...
Page 38: ...38 WIRING DIAGRAMS Wiring Diagram W2 WH2 133...
Page 39: ...39 Wiring Diagram WH1 0181 0261...
Page 40: ...40 Wiring Diagram WH1 0331 0401...
Page 41: ...41 Wiring Diagram WH1 0514 0724...
Page 42: ...42 Wiring Diagram WH1 0824 1826...
Page 43: ...43 Wiring Diagram WH1 2100 2500...
Page 44: ...44 Wiring Diagram WH1 3001 4001...
Page 51: ...51...