13
NOTE:
If louvers, grills or screens are used on the
openings, obtain the net free area from their suppli-
er or manufacturer. If the design free area of a louver
is not known nor available, it shall be assumed that
wood
louvers will have
20-25
percent free area and
metal
louvers will have
60-75
percent free area as
specified in the National Fuel Gas Code.
Venting
Outdoor Installations
Model 0133
1. Remove the front (4) screws.
2. Line up outdoor top vent opening over heater vent
opening.
3. Lower outdoor top onto unit lining up slots in the
outdoor top with screws holes in jacket top.
4. Reinstall (5) screws to secure jacket top and out-
door top to unit.
Fig. 4: Outdoor Top Installation
Models 0181-0401 and 0182-0400
Vent Terminal (Outdoor) Stackless Top
Installation
1. Insert tabs into keyhole (4 places).
2. Snap tabs into keyholes so as not to pull out.
Outdoor Top
8-3/8"
OUTDOOR
FLOOR BASE
Fig. 5: Outdoor Top Installation
Pagoda Top (Shipped Loose with Heater)
Fig. 6: Outdoor Top Installation
WARNING:
Examine the venting system at least
once a year. Check all joints and vent pipe
connections for tightness, corrosion or deterioration.
Summary of Contents for RAYTHERM 133
Page 15: ...15 Fig 9 Indoor Top Installation...
Page 24: ...24 Piping Diagram Type WH Unitemp 80 System...
Page 28: ...28 Location of Controls 0400 WH1 WH2 WH3 0181 LOW NOx WH1...
Page 29: ...29 Location of Controls 0824...
Page 38: ...38 WIRING DIAGRAMS Wiring Diagram W2 WH2 133...
Page 39: ...39 Wiring Diagram WH1 0181 0261...
Page 40: ...40 Wiring Diagram WH1 0331 0401...
Page 41: ...41 Wiring Diagram WH1 0514 0724...
Page 42: ...42 Wiring Diagram WH1 0824 1826...
Page 43: ...43 Wiring Diagram WH1 2100 2500...
Page 44: ...44 Wiring Diagram WH1 3001 4001...
Page 51: ...51...