background image

57

(b) EXEMPTIONS: The following equipment is exempt from

248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment

Not Required To Be Vented" in the most current edition of

NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled

equipment installed in a room or structure separate from the

dwelling, building or structure used in whole or in part for res-

idential purposes.

(c)  MANUFACTURER  REQUIREMENTS  -  GAS  EQUIP-

MENT  VENTING  SYSTEM  PROVIDED.  When  the

manufacturer  of  Product  Approved  side  wall  horizontally

vented gas equipment provides a venting system design or

venting system components with the equipment, the instruc-

tions  provided  by  the  manufacturer  for  installation  of  the

equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting sys-

tem design or the venting system components; and

2. A complete parts list for the venting system design or vent-

ing system.

(d)  MANUFACTURER  REQUIREMENTS  -  GAS  EQUIP-

MENT  VENTING  SYSTEM  NOT  PROVIDED.  When  the

manufacturer  of  a  Product Approved  side  wall  horizontally

vented gas fueled equipment does not provide the parts for

venting  the  flue  gases,  but  identifies  "special  venting  sys-

tems",  the  following  requirements  shall  be  satisfied  by  the

manufacturer:

1. The referenced "special venting system" instructions shall

be  included  with  the  appliance  or  equipment  installation

instructions; and

2. The "special venting systems" shall be Product Approved

by  the  Board,  and  the  instructions  for  that  system  shall

include a parts list and detailed installation instructions.

(e)  A  copy  of  all  installation  instructions  for  all  Product

Approved  side  wall  horizontally  vented  gas  fueled  equip-

ment,  all  venting  instructions,  all  parts  lists  for  venting

instructions,  and/or  all  venting  design  instructions  shall

remain with the appliance or equipment at the completion of

the installation.

GAS PRESSURE SUPERVISION

The  Commonwealth  of  Massachusetts  requires  listed  high

and low gas pressure switches (manual reset) for any model

with a maximum firing input greater than 1,000,000 Btu/Hr in

accordance with 248 CMR 7.04(11)(d).  

A gas  pressure  regulator  (field  supplied)  is  required  in  the

gas train ahead of the heater, for heaters having input rates

greater than 1,000,000 Btu/Hr, in accordance with 248 CMR

7.04 Figure 3B requirements.

The Commonwealth of Massachusetts requires compliance

with  regulation  248  CMR  4.00  and  5.00  for  installation  of

through – the – wall vented gas appliances as follows:

(a) For all side wall horizontally vented gas fueled equipment

installed  in  every  dwelling,  building  or  structure  used  in

whole  or  in  part  for  residential  purposes,  including  those

owned  or  operated  by  the  Commonwealth  and  where  the

side wall exhaust vent termination is less than seven (7) feet

above finished grade in the area of the venting, including but

not limited to decks and porches, the following requirements

shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter shall

observe that a hard wired carbon monoxide detector with an

alarm  and  battery  back-up  is  installed  on  the  floor  level

where the gas equipment is to be installed. In addition, the

installing  plumber  or  gasfitter  shall  observe  that  a  battery

operated  or  hard  wired  carbon  monoxide  detector  with  an

alarm  is  installed  on  each  additional  level  of  the  dwelling,

building or structure served by the side wall horizontal vent-

ed gas fueled equipment. It shall be the responsibility of the

property owner to secure the services of qualified licensed

professionals  for  the  installation  of  hard  wired  carbon

monoxide detectors

a.  In  the  event  that  the  side  wall  horizontally  vented  gas

fueled equipment is installed in a crawl space or an attic, the

hard wired carbon monoxide detector with alarm and battery

back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can

not be met at the time of completion of installation, the owner

shall  have  a  period  of  thirty  (30)  days  to  comply  with  the

above  requirements;  provided,  however,  that  during  said

thirty (30) day period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each

carbon  monoxide  detector  as  required  in  accordance  with

the  above  provisions  shall  comply  with  NFPA  720  and  be

ANSI/UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be

permanently mounted to the exterior of the building at a min-

imum height of eight (8) feet above grade directly in line with

the  exhaust  vent  terminal  for  the  horizontally  vented  gas

fueled heating appliance or equipment. The sign shall read,

in print size no less than one-half (1/2) inch in size, "GAS

VENT  DIRECTLY  BELOW.  KEEP  CLEAR  OF  ALL

OBSTRUCTIONS".

4. INSPECTION. The state or local gas inspector of the side

wall  horizontally  vented  gas  fueled  equipment  shall  not

approve the installation unless, upon inspection, the inspec-

tor  observes  carbon  monoxide  detectors  and  signage

installed  in  accordance  with  the  provisions  of  248  CMR

5.08(2)(a)1 through 4.

Important Instructions for the Commonwealth of Massachusetts

Summary of Contents for MVB 1104A

Page 1: ...apors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any applianc...

Page 2: ...page 22 Table K on page 28 High Limits on pages 36 37 Wiring Diagram on page 44 Blower Check on page 47 Table U on page 47 Filter Maintenance on page 55 Additions Motorized Combustion Air Dampers or L...

Page 3: ...r 17 Pool Heating 19 Gas Supply 21 Electrical Power Connections 22 Field Wiring Connection 24 Venting 27 Venting Installation Tips 30 Venting Configurations 30 Outdoor Installation 35 Controls 36 User...

Page 4: ...cause cancer birth defects or other reproductive harm WARNING Risk of electrical shock More than one disconnect switch may be required to de energize the equipment before servicing CAUTION This heater...

Page 5: ...andard war ranties Model Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel of the heater The model num...

Page 6: ...y Fig 4 Component Locations Top Fig 3 Component Locations Rear Panels omitted for clarity Fig 2 Component Locations Front Model No MBTUH Input Water Conn NPT Gas Conn NPT Vent Size in Max Min N P Flue...

Page 7: ...To determine the water temperature being delivered turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer NOTE When this water heater is supplying general...

Page 8: ...n in front 1 in on the side at least 24 in on the rear and 10 in above the top of the heater is required This will allow 8 Table C Clearances Indoor Installations INSTALLATION Installation Codes Insta...

Page 9: ...rdering the unit and is shipped loose for field installation The intake air elbow MUST be Combustion and Ventilation Air Indoor Units This heater must be supplied with sufficient quantities of non con...

Page 10: ...t 91 cm K Clearance to mechanical air supply inlet 3 ft 91 cm above if within 10 ft 3m horizontally 6 ft 1 83m L Clearance above paved sidewalk or paved driveway located on public property 7 ft 2 13m...

Page 11: ...operation See Field Wiring Connection section of this manual for proper wiring instructions using Fan Damper dry contacts and external interlock TruSeal Combustion Air In addition to the 3 previous st...

Page 12: ...l be provided by an opening s for ventilation air at the highest practical point communicating with the outdoors The total cross sectional area of such an opening s shall be at least 10 of the area re...

Page 13: ...antable failure When required Raypak recommends the boil er be isolated from the system piping prior to flushing or cleaning with any cleaning agent Cold Water Operation This heater is equipped with a...

Page 14: ...Fig 9 Cold Water Start Maximum 4 times the pipe diameter or 12 whichever is less water is kept in a narrow temperature range of no more than 10 F 5 C a permanent manual bypass can be employed and man...

Page 15: ...al codes Piping All high points should be vented A heater installed above radiation level must be provided with a low wa ter cut off device sales order option F 10 This heater when used in connection...

Page 16: ...are high recovery low mass heaters which are not subject to thermal shock Applications Modes The VERSA IC Control system is designed for a wide range of applications The installer design engineer shou...

Page 17: ...lled by the Supply sensor S3 whenever the indirect call for heat is not active The DHW Supply sensor S5 determines the indirect call tank setpoint During an indirect call for heat the boiler firing ra...

Page 18: ...el tubes are recommended for water softened below 5 grains per gallon Table G Domestic Water Heater Flow Rate Requirements 3 4 Grains Per Gallon 5 15 Grains Per Gallon 16 25 Grains Per Gallon T F GPM...

Page 19: ...talled outdoors as pool heaters in freezing climate areas should be shut down for the winter To shut down the heater turn off manual main gas valve and main gas shut off Close isolation valves Drain t...

Page 20: ...pool equip ment it is essential that your water be chemically balanced The following levels must be used as a guide for balanced water Occasional chemical shock dosing of the pool or spa should not da...

Page 21: ...pressures in excess of 1 2 psi 3 45 kPa Gas Supply Pressure A minimum of 4 0 in WC upstream gas pressure under full load and a maximum gas supply pressure setpoint of 10 5 in WC under load and no loa...

Page 22: ...er for pumps larger than 3 4 HP must be a sepa rate circuit wired through the pump contactor Power to the MVB heater should be connected to terminals 1 2 and 3 as noted in Fig 20 All low voltage wirin...

Page 23: ...Connected Controllers It is strongly recommended that all individually pow ered control modules and the heater should be supplied from the same power source NOTE Field supplied isolation relays should...

Page 24: ...eet 4 Mount the outdoor sensor on an exterior surface of the building preferably on the north side in an area that will not be affected by direct sunlight and that will be exposed to varying weather c...

Page 25: ...installation 2 When the Indirect DHW call for heat is active the PIM communicates this to the VERSA The VERSA calculates the optimal operation and sends the firing rate and pump output requests to th...

Page 26: ...nnections are dry contacts rated for pilot duty only 5A maxi mum 2 Connect the boiler pump enable wires to the termi nal block at the rear of their unit The connections are dry contacts rated for pilo...

Page 27: ...lose during fault or lockout conditions and the maximum voltage across the contacts is 30 VAC or 30 VDC See the Field Wiring as shown in Fig 25 In a cascade system the alarm output of the master boile...

Page 28: ...s any question about the appliance categorization and suitability of a vent material for application on a Category I or III vent system Using improper venting materials can result in personal injury d...

Page 29: ...ove any door window or gravity air inlet to the building 2 The vent must not be less than 7 ft above grade when located adjacent to public walkways 3 Terminate vent at least 3 ft above any forced air...

Page 30: ...te a thermal driving head that expels the exhaust gases from the flue The nega tive draft must be within the range of 01 to 08 in WC as measured 12 in above the appliance flue out let to ensure proper...

Page 31: ...proper sizing of the manifold and the chimney At no time should the area of the common vent be less than the area of the largest heater exhaust outlet Common venting systems may be too large once an e...

Page 32: ...ined above return doors windows exhaust fans fireplace dampers and other gas burning appliances to their previous conditions of use 7 Any improper operation of the common venting system should be corr...

Page 33: ...equivalent ft in length If horizontal run exceeds 75 equivalent ft an appropri ately sized variable speed extractor must be used Each elbow used is equal to 10 ft of straight pipe This will allow ins...

Page 34: ...steel flue direct vent cap must be used sales order option D 15 The vent terminal must be located NO CLOSER than 12 off the wall Direct Vent Vertical Installation These installations utilize the heate...

Page 35: ...elbow are provided in accor dance with CSA requirements These must be installed directly on the vent pipe as illustrated in Fig 36 Care must be taken when locating the heater out doors because the fl...

Page 36: ...here is a call for heat and all safeties are closed then the combustion air blower starts to purge air from the combustion chamber After the pre purge the igniter is energized The standard ignition mo...

Page 37: ...or air pockets Fig 41 Low Water Cut Off High Low Gas Pressure Switches Optional The optional low gas pressure switch mounts upstream of the gas valve on the inlet flange to the gas valve and is access...

Page 38: ...IC Control I O Manual Catalog 5000 72 Adjusting the MVB Setpoint To adjust the setpoint on the MVB Use the MENU key to scroll to the SETUP ADJUST menu then use the ITEM key to scroll to the SET POINT...

Page 39: ...rature 220 F TARGET MIN H MODE 1 2 3 OFF 50 F to 190 F Minimum target system temperature 50 F TARGET DIFF H MODE 1 2 3 2 F to 42 F Differential for target system temperature 10 F DHW SENSOR H MODE 1 2...

Page 40: ...fset OPERATOR All Operator Limit Potentiometer PIM setting AUTO DIFF H MODE 1 2 3 Current auto differential PUMP PREPt All Duration of pump prepurge BLOW PREPt All Duration of blower prepurge BLOW PRE...

Page 41: ...oiler outlet temperature Press UP DOWN for 1 sec to clear INLET HI All Records the highest boiler inlet temperature Press UP DOWN for 1 sec to clear INLET LO All Records the lowest boiler outlet tempe...

Page 42: ...degree the outdoor temperature drops the tempera ture of the heating water will increase one degree With the VERSA both ends of the slope are adjustable It is factory set at 70 F water temperature Bo...

Page 43: ...nual temperature where the building is located This temperature is used when completing heat loss calculations for the building Boiler Design Boil DESIGN The Boil DESIGN temperature is the water tempe...

Page 44: ...44 WIRING DIAGRAM Models 504A 2004A...

Page 45: ...ne Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to turn the gas control valve handle Never use tools If the handle will not...

Page 46: ...pproximately 15 seconds after the blower starts the igniter should start to glow observable through the observation port located at the front below the gas valve Look into the sight glass located just...

Page 47: ...the user test function USER TEST is displayed in the Title Field UP keystrokes are used to advance through the user test The Boil MIN MAX steps for burner operation are only run for enabled boilers Lo...

Page 48: ...point B bleedle valve and open the upstream manual gas valve Make sure that test point A B bleedle valves have been opened so as to allow gas to flow This will bring gas pressure to the second valve s...

Page 49: ...allow one time operation of the limit and then must be returned to normal operation by turning dip switch 8 back to the OFF position Power to the unit must then be cycled off then on to return to nor...

Page 50: ...ater temperature or manual reset high limit is not tripped c Enable Disable circuit is closed d Gas is on at the meter and the heater e Incoming dynamic gas pressure to the gas valve is NOT less than...

Page 51: ...replace control DELTA T Temperature difference between the inlet and outlet exceeded the set point Check water flow LOW 24VAC Low 24 VAC power Check power supply wiring and transformer BLOW SPEED Blow...

Page 52: ...the gas supply See table for more information 4 flashes N A N A 5 flashes Low Voltage Fault Check the 24 VAC input voltage The voltage must be above 18 0 VAC 6 flashes N A N A 7 flashes Hi Limit Fault...

Page 53: ...c tion deterioration or leakage 4 Visually inspect for proper operation of the con densate drain in the venting If leaks are observed repair at once 5 Check air vents for leakage Yearly Beginning Of E...

Page 54: ...see light blue flame at full input rate Weekly For low pressure heaters test low water cut off device With heater in pre purge depress the low water cut off test button Appliance should shut off and i...

Page 55: ...y safety relief valves in accordance with ASME Heater and Pressure Vessel Code Section IV Filter Maintenance Inspect quarterly Replace when tracking pressure exceeds 0 5 in WC at 100 fan speed Filter...

Page 56: ...tion air spray cans containing chloro fluorocarbons permanent wave solutions chlorinated waxes cleaners chlorine based swimming pool chemicals calcium chloride used for thawing sodium chloride used fo...

Page 57: ...wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth...

Page 58: ...58...

Page 59: ...utes Vent Size _____________ Stack Height _______ Low Water Cutoff _______________Test Category _________ sketch vent on reverse side Number of Tanks and Size Qty____ _______Gallons Vent Material ____...

Page 60: ...el must be between 7 2 and 7 8 and total alkalinity between 100 and 150 PPM Total Dissolved Solids TDS must be no greater than 2500 PPM PARTS REPLACEMENT Under this Warranty Raypak will furnish a repl...

Page 61: ...EMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid and all applicable war...

Page 62: ...62...

Page 63: ...63...

Page 64: ...64 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...

Reviews: