For resetting energy parameters user will be prompted for password. If correct password is
entered, the user will be able to reset parameters. This password will be greater
than the configuration password by 1.
99
99
FRONT VIEW
53.30
5.70*
SIDE VIEW
90.50
90.50
BACK VIEW
MECHANICAL INSTALLATION / DIMENSIONS
(in mm)
Max Page Auto
21
1 to 21
PROGRAMMING MENU
Function
Range or Selection
Config.
page.
Factory Setting
Password
Change Password
New Password
1000
0000
No
0000 to 9998
No / Yes
0000 to 9998
Network Selection
3P4W
3P4W 1P2W-P1
,
CT Secondary
330mV
1
330mV
CT Primary
PT Secondary
350
1A to 6,000A
173V to 415V
1
PT primary
Slave Id
350
100V to 600V
1 to 255
1
Baud Rate
Parity
Stop Bit
Back Light
9600
None
0000
300, 600, 1200, 2400,
4800, 9600 and 19200
None, Even, Odd
1 or 2
0 to 7200 sec.
1
Demand interval method
Sliding
Demand interval duration
15
15
1
1.1
2
3
4
5
6
7
8
9
10
11
12
13
14
Demand interval length
Sliding / Fixed
1 to 30
1 to 30 min
Factory Default
Reset Energy and Max Demand
Reset Active Energy
Reset Reactive Energy
Reset Apparent Energy
Reset Max Power
Reset Run Hour
19
20
20.01
20.02
20.03
20.04
20.05
No
No
No
No
No
No
No
No / Yes
No / Yes
Password
20.1
0000
0001 To 9999
No / Yes
No / Yes
No / Yes
No / Yes
No / Yes
Pulse duration
Pulse Resolution
18
17
Page sequence 14
Page sequence 15
14
15
16.14
16.15
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page sequence 16
Page sequence 17
16.16
16.17
16
17
Page sequence 7
Page sequence 8
Page sequence 9
Page sequence 10
Page sequence 11
Page sequence 12
Page sequence 13
10
9
8
7
6
5
4
3
2
1
11
12
13
16.13
16.01
Page sequence 1
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page 1 to 21
Page sequence 2
Page sequence 3
Page sequence 4
Page sequence 5
Page sequence 6
16.02
16.03
16.04
16.05
16.06
16.07
16.08
16.09
16.10
16.11
16.12
Change Page Sequence
16
No
No / Yes
Page sequence 18
Page sequence 19
Page sequence 20
Page sequence 21
16.18
16.19
16.20
16.21
18
19
20
21
200
0.10
50
300
to
00.01 to 99.99
Doc. name : OP INST RI-F 00 OP
-V01(Page 3 of 6)
3
300
*8.50 with
rubber
gasket fitted
There are 6 dedicated keys with symbols marked as , , , , , use
these 6 keys to enter into
configuration menu
change
.
the
and to
values
NOTE :
The settings should
after
only be modified by a competent person
having read
s
fully
.
this user manual
and having understood the application
(Please refer
configuration lock
before entering in
to
note on Page 1
to
configuration mode)
Key functions:
Press
+ keys for 3 sec to enter or exit from the configuration menu.
Use or keys to move curser left or right by one digit each time.
Use or keys for increasing or decreasing parameters value.
Use
key to go back to previous page
.
Use key to save the setting and move on to next page.
91.5
Panel Cutout
91.5
MECHANICAL INSTALLATION
Installation:
1. Prepare the panel cutout with dimensions s shown
a
above. Ensure any burrs
are removed.
2.Push the meter into the panel cutout. Secure the meter using the provided
ratchet fixings.
A
P
PPLICATION OF
ULSE OUTPUT
TERMINAL CONNECTIONS
V2
V3
N
V1
V3
V1
N
Voltage
Input
Voltage Output
V2
CT Input
(RJ45)
RS485
+
-
+
-
PULSE
O/P
INSTALLATION NOTES
CT INPUT -
Only Rayleigh Instruments RI-CTxxxEW Easywire Current transformers may be used with
this meter.
VOLTAGE INPUT -
This meter is self-supplied from all three phases L-N. The Neutral conductor
must be present.
VOLTAGE OUTPUT -
This output is used to ‘Daisy chain
’
additional meters so they can be supplied
from one supply. Maximum 32 meters total.