Error message
Execution process
Cause of error
Angle sensor x defective #
The angle sensor value in
volts is not valid (if < 1 volt
or > 4 volts).
1) The Accelerometer or the
12 bits converter is
defective.
Length x out of range #
A
0xFFFF
code is sent by
angle/length card to indicate
that length sensor is not
present.
1) The Length sensor is not
installed
2) A wire is cut between
length sensor and circuit
board.
Angle x is in Pre-calib.
Indicates that angle/length
card is in pre-calibration
mode.
1) In operation mode, the
jumper must be taken out
from ‘
Cal
’ jumper located
on the circuit board.
2) Verify that calibration
value in bits of the
accelerometer is valid.
Angle/length Comm #
The i3500 system does not
receive data from angle sensor.
If ‘‘
time out
’’ delay is reached,
then a communication error
is displayed.
1) The angle/length circuit
board is defective,
2) The Can bus network
cable is broken.
Length x Not calibrated
Length sensor is not
calibrated.
Angle Not calibrated
Angle sensor is not
calibrated.
Angle/length x Dr+
The
5 volts
reference voltage
is
not
valid (if < 4.5 volts or
5.5 volts).
1) The Angle/length circuit
board is defective.
The i3500 system can support up to
5
angle/length interfaces. Activation of
every angle sensor is done in the calibration menu section
‘‘Enable/Disable
I/O’’
.
A)
Angle / Lenght and ATB interface circuit board errors
5.7.2
External Peripherals
59
Telescopic Cranes Pressure Sensing
Instruction Manual
i3500 Troubleshooting