Pipe Freeze Protection and Flow Maintenance Design
buRIED PIPInG
Fig. 15 Typical buried piping system
Use the following for buried water piping and greasy waste lines . note that all connections
must be aboveground and that no splices/tees are allowed . Develop a bill of materials from
the connection kits in this table .
Table 15 Connection kits and Accessories for buried Piping
Catalog number Description
Standard
packaging
usage
Heating cable
allowance
1
RayClic-PC
Power connection and end seal
(RayClic-SB-04 pipe mounting bracket
included)
1
1 per circuit
2 ft (0 .6 m)
FTC-XC
The FTC-XC power connection and end
seal kit is for use with XL-Trace heating
cable that is run through conduit to a junc-
tion box . Materials for one power connec-
tion and end seal is included in the kit .
note:
FTC-XC is required for circuits
requiring 40 A circuit breakers .
1
1 per circuit
2 ft (0 .6 m)
RayClic-Le
Lighted end seal (RayClic-SB-04 pipe
mounting bracket included)
1
Alternate end seal
2 ft (0 .6 m)
RayClic-e
extra end seal
1
Additional end seal 0 .3 ft (0 .1 m)
RTD10CS
Insulation
Conduit
XL-Trace
heating cable
with -CT jacket
Ground
Alternate
power connection
Alternate
end seal
Ground
Wall
RayClic-LE*
RayClic-PC*
Junction box
RayClic-E
end seal
Conduit
Wall
with wall
mounting
bracket
with wall
mounting
bracket
FTC-XC
power
connection
*To protect the heating cable run it inside
Convolex tubing between the conduit and
the RayClic connection kits.
DigiTrace C910
Electronic controller
Conduit for
temperature
sensor