5.5 Cable Terminations
MI industrial wiring cables are typically supplied with
factory installed terminations. These cables are ready to
connect into junction boxes and other equipment as soon
as they are received at the job site.
Where field installed terminations are required, two types
of Pyropak® termination kits are available depending on
the area classification. The Pyropak with epoxy sealing
compound (Figure 22) is used to terminate cables located
in nonhazardous, Division 2, or Division 1 hazardous areas.
The Pyropak with gray sealing compound (Figure 23)
is used to terminate cables located in nonhazardous or
Division 2 hazardous areas.
Prior to installing field terminations, check the cable with
a 500 V megohmmeter to ensure the IR is acceptable
(see Section 6). Follow the instructions supplied with the
Pyropak kits to complete the cable termination.
Cap and
sleeve
assemblies
Gland
connector
Pots
Expoxy sealing
compound
Figure 22: Termination kit with epoxy sealing compound
5 INSTALLATION
30 | nVent.com