Short description

The Safety-Temperature-Limiter type nVent RAYCHEM TCON-SLIM-

01/+x+y is an electronic thermostat monitoring the temperature of 

heating equipment and machinery. The temperature is measured with a 

Pt 100 resistance temperature detector (RTD) according to DIN 43760 / 

IEC 751. The switching point is adjustable with a scale potentimeter. The 

relay is designed for normally closed (nc) operation. If the temperature 

rises and the preset limit is exceeded, the contact opens and remains 

locked. The relay can be reset manually only after the temperature has 

decreased app. 10 K below switching point. The thermostat series 

TCON-SLIM-01/+x+y complies with the higher safety standard according 

DIN 3440 and meets safety category 3 (Safety of machines EN 954-1). If 

DIN approval is recommended only use listed RTD’s.  

Temperature range: 0...200°C, 100...300°C, 200...500°C

Power supply: AC 230 V, DC 24...240 V

Intended use

Intended use according directive 97/23/EG Pressure Devices – safety 

related parts (control equipment) - limiting equipment (release and lock). 

With supply voltage switched on, the TCON-SLIM-01/+x+y operates in 

a changeable lockout mode and the relay must be started by a reset 

(manually with built-in reset button or external reset) to make contact 

(no) close. Applicable within steadily controlled plants. According to DIN 

3440 the function has to be routine-tested periodically.

Operation and set-up

The resistance of a Pt 100 RTD is measured, the signal send to both 

independent electronic channels and compared with the preset limit. 

Every comparator sets a relay. The relay contacts are made in series thus 

the outputs operates as a single change over contact. When temperature 

is below the preset limit and there is no failure in the sensor circuit both 

relays K1 and K2 can pick up and contact 11,14 is closed. The TCON-

SLIM-01/+x+y monitors sensor line interruption (UB) or sensor short 

circuit (KS). The red LED “Sensor” signals a failure in the sensor circuit 

and both relays release. Contact 11,12 is closed for warning/alarm. The 

red LED K1 and LED K2 also signal alarm when temperature exceeds 

the preset limit and both relays K1 and K2 release. The green LED ON/

Ready is not alight and control relay picks up, the contact at terminal 6,7 

is open (break contact, nc). The TCON-SLIM-01/+x+y operates now in 

not changeable safety mode, the relays are locked. When temperature is 

app. 10 K below the limit the control relay (contacts 6/7 close) releases 

and the green LED is alight. The TCON-SLIM-01/+x+y now operates in 

changeable safety mode, the relays can be reset manually with built-in 

reset button or with external contact (make contact, no) at terminal Y1, 

Y2. The internal fuse prevents melting of the relay contacts.

Function overview

• Suitable for one Pt 100 RTD (temperature sensor connected in  

2 wire circuit)

• One failure cannot cause a hazardous function  

(two channel design)

• Sensor monitoring of short circuit or line interruption

• Preset limit can be sealed

• Function indication with LED’s for relays and sensor

• Built-in reset button or external contact, no

• Plug-in electronic, easily mounting and service

Installation – Putting into operation
Important notice! Read carefully!

The device must only be used in compliance with all instructions from 

this instruction manual. In order to handle the device in accordance 

with safety requirements and to ensure its trouble-free operation, the 

fundamental prerequisite is a knowledge of the basic safety information 

and the safety regulations. Only appropriately qualified personnel may 

work on the device. The term „qualified“ means that such personnel are 

familiar with the installation, commissioning and operation of the device 

and that have undergone training or instruction, which is appropriate to 

the activity.

Failure to take note of the wiring diagram and the respective 

explanations, unauthorised modifications or the use of spare parts 

which are not recommended by the manufacturer of the device may 

cause injuries, electric shocks, fire and damage to the device and the 

associated equipment.

Make sure that the device and the associated equipment are switched 

off before assembling/fitting, disassembly, connection or structural 

modifications are carried out.

Connection must only be carried out in compliance with the wiring 

diagram and the respective explanations, which are included in the 

technical data’s.

Mounting and connection

The plug base can be mounted

•  Snapable on 35 mm standard rail according to DIN 50 022

•  wall-mount with 2 x screws M4

When installing the device into the switchgear cabinet, please observe 

the max. admissible temperature. Care for both, sufficient clearance to 

other devices or sources of heat or enough forced draught. Generally 

recommended minimum clearance: 10 mm.
Wiring directly to plug base

•  connect wires as per wiring scheme

•  adjust temperature limit

•   Apply mains voltage to terminals A1 and A2 (DC A1= +, A2= -)

  Before switching on make sure that the supply voltage Us on the 

lateral type plate corresponds with the mains voltage.

•  When device is ready for operation, relay K3 is released (terminals 

6-7 closed); the green LED “Ready/ON” is alight. Red LED’s signal the 

relays K1, K2 are released.

•  Press button “Reset”. Relay K1, K2 pick up and terminals 9,10 close. 

Red LED’s are off.

Attention!  

Do not plug in device alive nor detach it from socket.

Trouble shooting and remedies

•   LED “Ready ON” is not alight! 

Check the supply voltage! Make sure that the supply voltage is 

connected correctly (+/-) to terminals A1/A2 and corresponds with 

the type plate.

•   K3 picks up, red LED UB or short circuit is alight! 

Check the sensor! Make sure, that the Pt 100 sensor is connected to 

terminals 1,2 

and the resistance of RTD is within correct range.

•   K3 picks up, red LED’s K1, K2 are alight, no Reset possible! 

Check the temperature! Make sure, that the adjusted temperature 

limit is higher than the measured temperature. Reset can be done if 

measured temperature is app. 10 K below the preset limit and green 

LED “ On/Ready” is alight.

In case of any other malfunctions, replace device and send it in together 

with a shortdescription of the occurred failure.

Technical Data

Power supply

  Input voltage 

230VAC –10/+10%

  Frequency 

50 Hz

  Internal consumption 

< 3VA

Sensor connection  

2-wire technique, Pt100 (DIN 751) 

     

a = 0.00385

  Max. current 

< 3.15 mA

  Max. voltage 

< 0.85 V in operation,  

     

open source < 15V

  Pre programmed sensor off set  0.5 Ω 

Switching

  Switching OFF in case of  

Over temperature, sensor break, 

     

sensor short or internal error

  Limit temperature range 

User selectable within operating  

     

range of the unit

  Switching hysteresis 

10°K (±25%)

  Reset 

Local by RESET button on the front of  

     

the unit or remote through an external  

   

contact

Relay output

  Contact type 

1 changeover contact (SPDT)

  Contact rating 

Max, 6A at 400 VAC

  Recommended circuit  

 protection 

4A

  Contact life (mech - electr) 

M: 3 x 10

7

 / E: 1 x 10

6

 /230V / 2A

  Approvals 

DIN 3440/VDE 0631

  Electrical insulation 

AC 400V (VDE 0110 GROUP III/2)

  Transformer 

VDE 0551

Enclosure  

  Dimensions (H x B x D) 

82 x 42 x 121 mm

  Terminals 

12 terminals suitable for  

    1,5 mm

2

 cables

  IP rating  

IP 40

  IP rating terminals 

IP 20

  Mounting 

35 mm DIN rail (DIN-EN 50 022) or  

     

wall mounting using 2 pc M4 screws

  Weight 

300 g

Summary of Contents for nvent TCON-SLIM-01 Series

Page 1: ...TCON SLIM 01 x y TCON SLIM 01 0 200 TCON SLIM 01 200 300 TCON SLIM 01 200 500 Safety Temperature Limiter STB Sicherheitstemperaturbegrenzer Limiteur De Température Veiligheidstemperatuurbegrenzer ...

Page 2: ...egulations Only appropriately qualified personnel may work on the device The term qualified means that such personnel are familiar with the installation commissioning and operation of the device and that have undergone training or instruction which is appropriate to the activity Failure to take note of the wiring diagram and the respective explanations unauthorised modifications or the use of spar...

Page 3: ...rt und inbetriebgenommen sowie bestimmungsgemäß bedient wird An dem Gerät dürfen nur Personen arbeit en die mit der Installation Inbetriebnahme und Bedienung vertraut sind und über die ihrer Tätigkeit entsprechende Qualifikation verfügen Sie müssen den Inhalt der Betriebsanleitung die auf dem Gerät angebrachten Hinweise und die einschlägigen Sicherheitsvorschriften für die Errichtung und den Betri...

Page 4: ...naître préalablement les consignes élémentaires et normes de sécurité en vigueur Seul du personnel qualifié est habilité à intervenir sur les équipements Le terme qualifié signifie que le personnel est familier de l installation la mise en service et l utilisation des équipements et a suivi une formation ou une instruction adaptée à l activité concernée Le non respect des schémas de câblage et des...

Page 5: ...n elektrocutie brand en of eventueel onherstelbare schade aan het toestel of de installatie die het bewaakt Indien u vindt dat deze handleiding ontoereikende is stel u dan zo snel mogelijk in verbinding met uw vertrouwde nVent aanspreekpartner voor verdere informatie Vooraleer werkzaamheden uit te voeren aan het toestel vergewist u zich ervan dat het toestel volledig spanningsloos gemaakt is Insta...

Page 6: ...All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates All other trademarks are the property of their respective owners nVent reserves the right to change specifications without notice Raychem IM INSTALL101 TCONSLIM01xy ML 1805 nVent com België Belgique Tel 32 16 21 35 02 Fax 32 16 21 36 04 salesbelux nvent com Česká Republica Tel 420 602 232 969 czechinfo nvent c...

Reviews: