2. The second mounting option is DIN-rail mounting.
For both options see the diagram with ruler on the flip-out cover page.
2.3 Installation of cables and sensors
Tyco Thermal Controls insists on the use of a 30 mA residual current
device and a C-characteristic circuit breaker to provide maximum safety
and protection from fire.
2.3.1 Wiring diagrams
There are three wiring diagrams: C, D and E (see 5.5 Diagrams).
For connection of a single unit: Diagram
pag. 32
F1: Circuit breaker 20 A max. (C-Characteristic).
F2: Residual current device 30 mA.
For multiple unit connection on one phase system: Diagram
pag. 33
F1, F3, F5: Circuit breaker 20 A max. (C-Characteristic).
F2, F4, F6: Residual current device 30 mA
For multiple unit connection on a three phase system: Diagram
pag. 33
F1: Circuit breaker 3 x 20 A max. (C-Characteristic)
F2: Residual current device 3 x 30 mA
Double-pole electrical protection might be needed to comply with local
electrical standards.
2.3.2 Minimum power cable sizing
Fig. 2
C - Characteristic circuit breaker
10A
13A
16A
20A
Minimum cable size 3 x 1,5 mm
2
3 x 1,5 mm
2
3 x 1,5 mm
2
3 x 2,5 mm
2
Use solid core wires for 1,5 mm
2
diameters.
Ensure that the installation is compatible with applicable local electrical
requirements.
E
D
C
Tyco C 9278e HWAT-ECO 22.02.2002 14:12 Page 11
Summary of Contents for HWAT-ECO
Page 2: ...3 148 mm 1 2 A B C Tyco C 9278e HWAT ECO 22 02 2002 14 12 Page 2 ...
Page 28: ...28 Fig 10 Example Fig 11 Tyco C 9278e HWAT ECO 22 02 2002 14 12 Page 28 ...
Page 29: ...29 Fig 12 Tyco C 9278e HWAT ECO 22 02 2002 14 12 Page 29 ...
Page 97: ...Fig 10 Exemple Fig 11 97 Tyco C 9278f HWAT ECO 22 02 2002 14 10 Page 97 ...
Page 98: ...Fig 12 98 Tyco C 9278f HWAT ECO 22 02 2002 14 10 Page 98 ...