Installation Instructions

H910

WinterGard

®

 Splice and Tee Kit with End Seal

Description

The WinterGard

®

 H910 Splice and Tee Kit is for use with WinterGard 

self-regulating heating cables to make splice, tee, and end seal con-

nections. The kit contains materials for one splice and one end seal, or 

one tee connection and one end seal. This kit does not provide a power 

connection; use an H900 or H908 power connection kit for a complete 

installation.

Applications

Use the H910 kit with the following WinterGard heating cables:

H311, H611, H612, H621, and H622. All are designed for pipe

freeze protection in dry locations, but H612 and H622 cables are

designed for both wet and dry areas, as well as for roof and gutter

de-icing. The cable type is printed on the outer jacket of the cable.

Tools Required 

• Diagonal Cutters   

• Needle nose pliers

• Utility knife 

 

• Heat gun or torch

• Crimp tools (Ideal 30-425 and T&B WT112M or WT2000)
• Hammer and nail (for gutter/downspout applications only)

Installation and Support

The minimum installation temperature for this kit is 0°F (–18°C).

See the WinterGard Application and Design Guide (H53585), 

H900, or H908 installation instructions for design information.

For additional technical support call Tyco Thermal Controls at (800) 

545-6258.

R

E

A

B
C
D

E

H

G

F

I

Approvals 

 

Kit Contents:
Item 

Qty 

Description

Insulated bus wire crimps

Uninsulated braid crimps

3  

Cable ties

Mastic strips

Heat-shrinkable cap

Heat-shrinkable tube (6" long, 1" dia.)

Black cloth tape (6" long)

Clamp tie

End seal

WARNING:

This component is an electrical device that must be  

installed correctly to ensure proper operation and to 

prevent shock or fire. Read these important warnings 

and carefully follow all the installation instructions.

•  To minimize the danger of fire from sustained        

electrical arcing if the heating cable is damaged 

or improperly installed, and to comply with the     

requirements of Tyco Thermal Controls, agency      

certifications, and national electrical codes, ground-

fault equipment protection must be used. Arcing may 

not be stopped by conventional circuit breakers.

•  Bus wires will short if they contact each other. Keep 

bus wires separated.

•  Keep components and heating cable ends dry before 

and during installation.

•  The black heating cable core is conductive and can 

short. It must be properly insulated and kept dry.

•  Component approvals and performance are based on 

the use of Tyco Thermal Controls-specified parts only. 

Do not use substitute parts or vinyl electrical tape.

•  Leave these instructions with end user for reference 

and future use.

Summary of Contents for H910

Page 1: ...ional technical support call Tyco Thermal Controls at 800 545 6258 R E A B C D E H G F I Approvals Kit Contents Item Qty Description A 2 Insulated bus wire crimps B 1 Uninsulated braid crimps C 3 Cable ties D 6 Mastic strips E 1 Heat shrinkable cap F 1 Heat shrinkable tube 6 long 1 dia G 1 Black cloth tape 6 long H 1 Clamp tie I 1 End seal WARNING This component is an electrical device that must b...

Page 2: ...hen down outer jacket Bend heating cable to break jacket at score then peel off outer jacket Do not cut braid or inner jacket 2 3 1 At the end of each heating cable section lightly score completely around and down inner jacket Bend heating cable to break jacket at score then peel off inner jacket Do not cut bus wires 4 1 4 1 4 Notch core at the end Twist back and peel bus wires from core 5 For H61...

Page 3: ... paper from mastic strip Wrap a piece of mastic around the outer jacket on each heating cable section Remove release paper from mastic strip Wrap a piece of mastic around the end of each heating cable section and position as shown Pinch the mastic in the center to completely seal the core at the end of each heating cable Carefully align the heating cable sections and place them together Press mast...

Page 4: ...a braid 10 Black tape Fold the crimped braid back against the heating cables Wrap black cloth tape evenly around crimp and heating cables Cover crimp completely Select one bus wire from each cable section and twist the wires together Repeat with remaining bus wires Be careful not to twist together bus wires from the same heating cable Use insulated bus wire crimps and T B crimp tool to crimp each ...

Page 5: ...ompletely Start at end farthest from the cap and work toward the open end Keep heating after tube has shrunk to melt adhesive and mastic inside tube Total heating time should be about 5 minutes Important Additional heat is needed after the tube is shrunk to melt mastic and adhesive inside Immediately after shrinking pinch the end of the tube with needle nose pliers until the end stays sealed this ...

Page 6: ...el and remove exposed braid 3 Cleanly cut off the end of the cable Score down and around outer jacket 1 inch from the end Remove the outer jacket Do not cut or damage inner jacket Firmly push end seal onto the cable at least 1 inch Some gel may ooze out Do not twist or try to remove the end seal during or after insertion Do not reuse an end seal 1 End Seal Installation Instructions for H612 and H6...

Page 7: ... or misuse of the product Specifications are subject to change without notice In addition Tyco Thermal Controls reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification Tyco Raychem and WinterGard are trademarks of Tyco Thermal Controls LLC or its affiliates Canada Tyco Thermal Controls 250 West St T...

Reviews: