Fault Finding
Burner Fault Finding
Burner does not start up
-
Mains switch not on.
-
Blown fuse.
-
Boiler thermostats not made.
-
Fault in control box.
Burner pre-purges and stops
-
Fault in control box.
Burner does not ignite during cycle
-
Fault in control box.
and stops
-
Fault in photo-resistor.
Burner does not ignite
-
Dirty ignition electrodes.
-
Fault at electrodes.
-
Electrodes installed wrongly.
-
Faulty ignition transformer.
-
Blocked nozzle.
-
Nozzle needs replacing.
-
Oil pressure to low.
-
Blocked oil filter.
-
Excessive combustion air for nozzle capacity.
-
Fault in control box.
Burner ignites and then stops
-
Faulty nozzle.
-
Photo-resistor does not ‘see’ flame.
-
Excessive combustion air for nozzle capacity.
-
Fault in control box.
-
Oil pressure to low.
-
Blocked oil filter.
29