background image

    

  

22

             

Manufacturers instructions must NOT be taken in 
any way as overriding statutory obligations.

 

If in doubt on any point please consult Ravenheat.

4.3 

LOCATION OF BOILER

 

 

Siting of Ravenheat HE 25/30/35/40 C combi 
boiler must be as follows. 

 

The  position  of  installation  should  be  within  the 
building, unless otherwise protected by a suitable 
enclosure.

            Adequate space for installation, servicing and 
           air circulation around the boiler must be allowed 

for.

 

Ravenheat 

Ravenheat HE 25/30/35/40 C combi boiler m

 combi boiler must 

be  fitted  on  a  flat  and  vertical  wall  capable  of 
adequately  supporting  the  weight  of  the  boiler 
and any ancillary equipment.

 

The appliance may be fitted on a combustible 
wall. Insulation between the wall and the boiler 
is not necessary, unless required by the local 
authority.

            For electrical safety reasons there must be no 
            access available from the back of the boiler.

            

The boiler must not be fitted outside.

 

LPG  versions  of  this  appliance  shall  not  be 
installed in cellars or basements.

4.4 

CLEARANCES AROUND THE APPLIANCE

            

 

 Side clearance:

             The position of the appliance must provide   
             minimum clearance of 5mm as the side panels
             do not require removing for servicing.
              However, if the option is preferred to remove the
             panels then a minimum clearance of 55 mm is
             required.
                            
             

Top clearance:

             The top clearance should be a minimum of 
             125 mm.

             Bottom clearance:
             

A bottom clearance of 80 mm is required 

             between the appliance and any surface.
             Though 150 mm is preferred whenever
             possible.

             

Front clearance:

             A minimum of 450 mm is required in front of
             the appliance for access during servicing, the
             front clearance can be reduced when installed 
             in a cupboard, to 25 mm from the access door. 

4.5 

IMPORTANT NOTICE

      

For installation into timber framed buildings, 
please refer to the Institute of Gas Engineers    
Document IGE/UP/7.               

             The boiler may be installed in any room or 
             internal space, although particular attention is 

              Regulations applicable in Scotland, with 
              respect to the installation of the combination 
              boiler in a room or internal space containing 
              a bath or shower.
              Where a room sealed appliance is installed
              in a room containing a bath or shower, any
              electrical switch or appliance control, utilising
              mains electricity should be situated so that it
              cannot be touched by a person using a bath
              or shower.              
              A compartment when used to enclose the 
              combination boiler MUST be designed and 
              constructed specifically for this purpose. 
              An existing cupboard, or compartment, may 
              be used provided it is modified accordingly. 
              Samples of the HE 25/30/35/40 C combi boiler 
              have been examined by CERTIGAZ 
              notification body, and are certified to comply 
              with the essential requirements of the gas 
              appliance.
          
             Directive 90/396/EEC, the Low Voltage.
   

Directive  72/23/EEC  and  shows  compliance   
with the Electro Magnetic Compatibility. 

             Directive 89/336/EEC and are therefore 
             permitted to carry the CE Mark.

   

The  appliance  has  been  tested  and  approved 
by  the  WRc  as  meeting  the  requirements  of 
G3 and L of the Building regulations and water 
Bylaws Scheme - Approved Products.

   4.6 

GAS SUPPLY

            

A gas meter is connected to the service pipe 

by the Local Gas Supplier or the Local Gas 
Supplier contractor. An existing meter should 
be checked preferably by the Gas Supplierto 
ensure that the meter is adequate to deal 
with the rate of gas supply required for all 
appliances it serves. Installation pipes should 
be fitted in accordance with BS 6891:2015. 
Pipework from the meter to the boiler must be 
of adequate size 
(22 mm) min to within at least one metre of 
the boiler, (15 mm) min. can then be used 
for remaining pipe work to the appliance. 
A smaller size than the boiler inlet gas 
connection should not be used. The complete 
installation must be tested for soundness as 
described in the above code.

 

 

.

             N.B. 

It is the responsibility of the Gas Installer 

 responsibility of the Gas Installer 

to size the gas installation pipework in 

to size the gas installation pipework in 
accordance with BS 6891:2015. Whilst the 

accordance with BS 6891:2015. Whilst the 
principle of the 1:1 gas valve ensures t

principle of the 1:1 gas valve ensures the 
Ravenheat range

Ravenheat range is able to deliver the full 
output at an inlet pressures as low as 14 
mbar, other gas appliances in the property 
may not be as tolerant.

             When operating pressures are found to be 

below the minimum meter outlet of 19 mbar 
these should be checked to ensure this is 
adequate for correct and safe operation.

Summary of Contents for HE 25 C COMPACT

Page 1: ...for guidance purposes only RAVENHEAT INTERNATIONAL s r l Via Dell Agricoltura 50 37059 Zevio VR IT Tel 045 6051578 Fax 045 6060662 e mail info ravenheat it Instructions for Use Installation and Servic...

Page 2: ...2...

Page 3: ...nless steel plate heat exchanger for super high heat transfer to domestic hot water supply Stainless steel plate heat exchanger for super high heat transfer to domestic hot water supply Built in frost...

Page 4: ...W VXFWLRQ V VWHP ZLWK WZR 7HFKQLFDO GDWD 6 1DW JDV VHSDUDWH UDWHG GLD SLSHV 7HFKQLFDO GDWD 6 3 H KDXVW RQ IODW RU VORSLQJ URRI VXFWLRQ 7HFKQLFDO GDWD 1DW JDV IURP YHUWLFDO ZDOO 7HFKQLFDO GDWD 6 3 KDXV...

Page 5: ...PRYH UHSODFH WKH EXUQHU 7R UHPRYH UHSODFH WKH KHDW H FKDQJHU 7R UHPRYH UHSODFH H SDQVLRQ YHVVHO 7R UHPRYH UHSODFH JDV YDOYH 7R UHPRYH UHSODFH SODWH KHDW H FKDQJHU 7R UHPRYH UHSODFH WKH ZDWHU SUHVVXUH...

Page 6: ...ck that the Central Heating system pressure is not less than 1 bar If it Heating system pressure is not less than 1 bar If it is below this it will be necessary to re pressurise the is below this it w...

Page 7: ...perature External temperature if the external probe is present Fan speed exemple 20 2000ppm Press ESC to esc INFO mode USER PARAMETERS for service people press the ESC and the arrow down buttons toget...

Page 8: ...ulty message message Stop boiler The boiler stops the operating cycle Stop boiler The boiler stops the operating cycle and waits for the disappearance of the cause of and waits for the disappearance o...

Page 9: ...Safety pressure relief valve 12 Water pressure 13 Automaticairvent 14 C H returnsensor 15 Fan 16 Expansionvessel 17 Sparkelectrode 18 Fluetemperaturesensor 19 Mainheatexchanger 20 Sensingelectrode 21...

Page 10: ...heatcutoffthermostat 11 CH ow sensor 12 Gas valve 13 Expansion vessel 14 Automatic air vent 15 Pump 16 Water pressure transducer 17 Safety pressure system 18 Diverter valve motor 19 Plateheatexchanger...

Page 11: ...uction of central heating and domestic hot water combined in one unit It is tted with an automatic domestic hot water priority valve It is possible to select either a summer or It is possible to selec...

Page 12: ...gas hot water heater When DHW is no longer required the burner When DHW is no longer required the burner and pump and fan will immediately turn o and pump and fan will immediately turn o This also ta...

Page 13: ...350 l h D H W ow rate 30 C rise 11 9 l min D H W ow rate 35 C rise 10 2 l min D H W ow rate 40 C rise 8 9 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 6200 rpm...

Page 14: ...D H W ow rate 30 C rise 11 9 l min D H W ow rate 35 C rise 10 2 l min D H W ow rate 40 C rise 8 9 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 6000 rpm 200 Hz m...

Page 15: ...h D H W ow rate 30 C rise 14 0 l min D H W ow rate 35 C rise 12 0 l min D H W ow rate 40 C rise 10 5 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 6600 rpm 220...

Page 16: ...D H W ow rate 30 C rise 14 0 l min D H W ow rate 35 C rise 12 0 l min D H W ow rate 40 C rise 10 5 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 6400 rpm 213 Hz...

Page 17: ...D H W ow rate 40 C rise 12 5 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 7300 rpm 243 Hz min 1200 rpm 40 Hz Qmw Input Net Max 36 0 kW min 4 0 kW D H W Pressur...

Page 18: ...rate 30 C rise 16 7 l min D H W ow rate 35 C rise 14 3 l min D H W ow rate 40 C rise 12 5 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 7100 rpm 236 Hz min 1200...

Page 19: ...rate 30 C rise 18 6 l min D H W ow rate 35 C rise 16 9 l min D H W ow rate 40 C rise 14 0 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 8300 rpm 220 Hz min 1200...

Page 20: ...W ow rate 30 C rise 20 1 l min D H W ow rate 35 C rise 17 3 l min D H W ow rate 40 C rise 15 1 l min 10 C Inlet temperature D H W temperature Max 60 C min 35 C Fan speed D H W Max 8100 rpm 213 Hz min...

Page 21: ...aller on the Gas Safe register www gassaferegister co uk Failure to install appliances correctly could lead to prosecution It is in your own interest and that of your safety to ensure the law is compl...

Page 22: ...a room containing a bath or shower any electrical switch or appliance control utilising mains electricity should be situated so that it cannot be touched by a person using a bath or shower A compartme...

Page 23: ...must be installed in accordance with the recommendations of BS 5440 Part 1 IMPORTANT NOTES For greater ue lengths see alternative ue instructions Flue must be positioned in a place not likely to cause...

Page 24: ...s carried naturally to air release to ensure air is carried naturally to air release points and water flows naturally to drain taps points and water flows naturally to drain taps It should be ensured...

Page 25: ...ontent calculate the total expansion see table 3 and add the total expansion see table 3 and add additional sealed expansion capacity as additional sealed expansion capacity as appropriate Fig 8 In ge...

Page 26: ...uilding Regulations It is recommended that you fit a primary It is recommended that you fit a primary water cleanser to the system We water cleanser to the system We recommend fitting a filter that wi...

Page 27: ...le pole isolator having use of a fused double pole isolator having a contact separation of at least 3 mm in all a contact separation of at least 3 mm in all poles The point of connection to the electr...

Page 28: ...5 5 FLUE TERMINAL POSITION 28...

Page 29: ...cutting joint securing 52 Self cutting joint securing screw screw 57 Elbow header 59 Rubber seal 60 56 Rubber seal 100 60 Fumes sample point 61 Flue exhaust duct 62 Air intake duct 69 Air sample point...

Page 30: ...ig 12a FLUE EXHAUST DEFLECTION BEND Fig 12a Flue exhaust de ection bend are also available These come in both 45 and 90 degree versions These bends t directly onto the ue exhaust terminal to de ect th...

Page 31: ...eal is made with O rings Tighten the two screws on the flue flange to secure the two screws on the flue flange to secure the elbow header in place elbow header in place Fit the terminal rubber wall se...

Page 32: ...the air be installed with the widened end of the air intake pipe and the tapered end of the flue intake pipe and the tapered end of the flue pipe aimed towards the exhaust terminal pipe aimed towards...

Page 33: ...ue bracket is available from Ravenheat and should be used to support the flue length at least every one metre preferably at each joint this bracket should be secured to wall and flue duct SIDE FLUE OU...

Page 34: ...seal 60 60 Fumes sample point 61 STD ue exhaust duct 62 Terminal 65 Flue manifold rubber seal 66 Securing screw 67 Flue temperature sensor 69 Air sample point 127 Terminal Rubber wall seal Fig 16 IN...

Page 35: ...ure that the centre line is vertical and that the flue centre line is virtually below the point at which the flue will exit the roof Ensure that the maximum permissible flue permissible flue length is...

Page 36: ...de Lift the boiler on the wall locating onto the top two fixing bolts Tighten the two bolts using a spanner to secure to the wall Measure the vertical distance between the top of the flue and the bott...

Page 37: ...ocated and lubricate the internal part seal is located and lubricate the internal part of the seal before assembly of the seal before assembly Locate the header gasket on the twin ue Locate the header...

Page 38: ...all g 25 Maximum distance D L L1 39 5 metres Terminal Minimum total length 2 metres NOTE Exhaust ue must slope 1 5 down towards the boiler 25 mm fall per metre Exhaust suction system with two separate...

Page 39: ...ension conjunction with a side horizontal flue extension piece and an inline 135 90 flue bend fig 27 piece and an inline 135 90 flue bend fig 27 Part No Description COL160050 Straight ue header sample...

Page 40: ...TING CONNECTION Fig 29 Before any central heating connections are made to the boiler all system valves should be opened and the system thoroughly flushed out with cold water Connect the central heatin...

Page 41: ...discharged into the household internal drainage system If this is not practicable discharge can be allowed into the external household drains or a purpose designed soak away It is recommended that an...

Page 42: ...onnection to the central heating system until water is heard to flow 5 28 EXTERNAL CONTROLS IMPORTANT Electricity supply must be as specified in clause sect 4 22 When controls external to the applianc...

Page 43: ...E g time E g time clock and thermostat make sure that they clock and thermostat make sure that they are calling for heat are calling for heat Select winter function the winter icon in Select winter fu...

Page 44: ...he valve inlet pressure test point fig 35 with the boiler operating at full rate boiler operating at full rate Check with the Local Gas supplier if the Check with the Local Gas supplier if the pressur...

Page 45: ...it operates at its various setting Close the draw off tap still further The burner should stop when the rate falls below about 2 8 L min 0 61 gals min 6 13 KEEP HOT The boiler comes with an optional k...

Page 46: ...for 5 seconds together item 2 and 3 fig 1 for 5 seconds to enter in USER PARAMETERS mode to enter in USER PARAMETERS mode Use arrow up and arrow down buttons Use arrow up and arrow down buttons item...

Page 47: ...etion of th satisfactory completion of the CPA1 ACS assessment which covers the use of electronic portable combustion gas analysers in accordance with BS 7967 Parts 1 to 4 7 1 BOILER FROST PROTECTION...

Page 48: ...aying water at any remaining debris through the condensate remaining debris through the condensate trap trap Ensure the water is kept away from Ensure the water is kept away from electrical components...

Page 49: ...y a competent person Before replacing any parts the boiler should be isolated from the mains electric supply and the gas should be turned off at the service cock on the boiler After replacing any part...

Page 50: ...Unscrew the four screws that fits the burner door to the heat exchanger and remove it Remove the electrodes sect 8 5 and remove the insulation pad is helpful to use a screwdriver to move the fastenin...

Page 51: ...is re fitted check combustion CO2 and adjust if necessary see section 6 9 8 10 TO REMOVE REPLACE PLATE HEAT EXCHANGER Fig 44 Remove the front and bottom panels fig 39 40 Remove the panel control box...

Page 52: ...crew the nut that fastens the pump to Unscrew the nut that fastens the pump to the CH pipe and remove the pump and the CH pipe and remove the pump and remove the securing clip at the pump remove the s...

Page 53: ...C H FLOW AND RETURN SENSORS Fig 48 RETURN SENSORS Fig 48 Remove the front panel fig 39 Detach the wire connector and remove Detach the wire connector and remove the retaining cli the retaining clip s...

Page 54: ...the front panel fig 39 Remove the front panel fig 39 Remove the panel control box sect Remove the panel control box sect 8 22 and let it fix at the depression 8 22 and let it fix at the depression cha...

Page 55: ...as supply has been purged of air The heating system pressure is at least 1 bar min to 1 5 bar max select winter position on the digital display and set the central heating temperature to maximum sect...

Page 56: ...he summer position on the digital display and setting see section 9 and after selecting the summer position on the digital display and setting the domestic hot water temperature to maximum the domesti...

Page 57: ...11 TEMPLATE DRAWING 57...

Page 58: ...12 SPARE PARTS Fig 56 58...

Page 59: ...Flow detector switch 17 VAL180100 C H valve load 18 GRU180050 Flow manifold 19 OTT150050 Diverter valve by pass 20 SON150050 D H W sensor 21 FOR150150 Diverter valve motor clip 22 MOT150050 Diverter v...

Page 60: ...n HE 25 30 C 43 1 VEN160150 Fan HE 35 40 C 44 GUA110052 Fan burner gasket 46 BRU160100 Burner 46 GUA150050 Sensing spark electrode gasket 47 CAN160100 Sensing electrode 48 CAN160050 Spark electrode 49...

Page 61: ...Accessories concentric flue 80 125 see sect 5 18 Part No Description COL160050 Straight ue header sample point 60 10 PRO110300 Flue Extension 80 125 L1000 RID110050 125 80 to 100 60 Flue reducer CUR1...

Page 62: ...62...

Page 63: ...63...

Page 64: ...r l Via Dell Agricoltura 50 37059 Zevio VR IT Tel 045 6051578 Fax 045 6060662 e mail info ravenheat it Ravenheat reserves the right to make changes and improvements in our products which may a ect th...

Reviews: