As  the  Sara  Insert  Wood  Pellet  Fire

can

 

 

 

be

 

installed  in  new  homes,  it  is  necessary  to  build  a 

compliant cavity that will house the fi re and the frame. 

The front facia of the enclosure must be made of a 

fi reproof rated board (above 80°C) such as (but not 

limited to) Micore, Supalux or Eterpan, and this must 

extend to a minimum of 330mm above the top of the 

fi re.  Within the cavity, there must be a minimum of 

300mm clearance to combustibles above the fi re, and 

a minimum 600mm gap between the top of the fi re 

and the ceiling of the cavity. The cavity also requires 

a minimum of 100cm

2

 ventilation.

WALL WALL WALL WALL WALL WALL WALL WALL

L

N

K

M

Built-in fi re  clearances  don’t  apply  in  a  non-combustible 

cavity.  The above clearance to combustibles on the fl ue 

are  only  applicable  within  the  fi re  envelope.    Clearance 

outside this,  eg at a ceiling/wall thimble reverts to 25mm as 

per ARS fl ue test 05/1185.

If installing a fl oating hearth, ensure suffi cient

clearance is left below the fi re to allow for installation

of the chosen surround.

Exterior of Cavity

D

E

J

H

VENT

F

B

C

A

G

I

J

VENT

Interior of Cavity

Creating the 

 

Cavity

Internal Cavity Dimensions

(A) Width:

3

10 0mm (min)

(B) Depth

:

5

   

9

 

0mm (min)*

(C) Height:

2090

 -

2320

*

*

m

m

 

* Includes 100mm clearance from rear of fl ue 

spigot

.

o

s

l

A  

g

n

i

w

o

ll

a

  r

o

f  

m

m

0

0

1

 

k

c

i

h

t

 

ll

a

w

box

.

**  Dependendent on height at which the support 

frame is set.

Wall Opening

(D) Width:

20

7 mm

(E) Height:

550

 

mm 

Cavity Clearances to Combustibles

(F): from top of 

 re

300mm

(G):  from  top  of 

  re  to  cavity  ceiling

   600mm

(H): from top of opening to 
       

 

       

combustible mantle 

330mm (min)

(I): from side of opening 

210mm (min)

(J): from bottom of opening 

 

300 - 530mm, 

depending on height of support stand.

Additional Clearances to Combustibles

(K): from exhaust spigot to cavity wall

  100mm

(L): from side of 

 re to cavity wall

 

 210mm

(M): hearth depth from front of glass   

150mm

(N): hearth width 

1030mm

Surround Dimensions

Small Black (Flush) 

692mm (w) 

 

x 609mm 

   

(h)

Stainless Steel

m

m

4

1

9

 

 

     

(w) x 830mm (h)

Summary of Contents for Sara

Page 1: ...et Fire Installation Specifications Safety testing of the Ecoteck Sara Insert Wood Pellet Burning Heater to AS NZS ARS 2918 2001 Flue Emissions 2 R 08 1862 ARS R1 08 1862 ARS 5 0 1185 ARS F App 2918 2001 AS NZS to Testing Kit R1 08 1861 09 2082 09 2078 09 2079 09 2080 ...

Page 2: ... both inside and outside the cavity Depending on the circumstances you may also have to consider the use of a hearth and the installation of the support Cavity masonry a into installed typically is Sara The frame Dimensions Sara Insert Built In Heater Refer to Safety Test 08 1861R1 for all clearances to combustible 713 5 610 541 5 112 400 78 590 14 527 5 541 5 177 9 72 9 78 476 196 4 589 5 87 51 2...

Page 3: ... test 05 1185 If installing a floating hearth ensure sufficient clearance is left below the fire to allow for installation of the chosen surround Exterior of Cavity D E J H VENT F B C A G I J VENT Interior of Cavity Creating the Cavity Internal Cavity Dimensions A Width 3 10 0mm min B Depth 590mm min C Height 2090 2320 m m Includes 100mm clearance from rear of flue spigot o s l A g n i w o l l a r o f...

Page 4: ... Includes 100mm clearance from rear of flue spigot box s w o l l a r o f a m m 0 0 1 l l a w s s e n k c i h t d n a If this measurement is less than 500mm a custom surround will be required Ensure that extra depth required at B is also added to the hearth measurement K Built in fire clearances don t apply in a non combustible cavity The above clearance to combustibles on the flue are only applicable...

Page 5: ...h all minimum distance to all combustible surfaces Any modifications to the dimensions shown to be verified by consultation with the relevant Building Consent Authority 4 Ensure there is a minimum of 100cm2 ventilation into the cavity this does not need to be from the outside 5 Installers must ensure adequate vermin proof measures are incorporated into the cavity construction if applicable Ensure pr...

Page 6: ...nclosure 3 Comply with all minimum distance to all combustible surfaces Any modifi cations to the dimensions shown to be verifi ed by consultation with the relevant Building Consent Authority 4 Ensure there is a minimum of 100cm 2 ventilation into the cavity this does not need to be from the outside 5 Installers must ensure adequate vermin proof measures are incorporated into the cavity construction...

Page 7: ...coach screws Thickness of flooring must be 20mm minimum The flooring shall be fixed to the nearest joist with two 8g x 40 screws per hold down anchor Fixing to Timber Floor Framing Minimum 14g x 60 screws 6 3 diameter or M10 x 90 coach screws These shall be fixed a minimum of 40mm into the centre line of the existing floor joists If screws cannot be installed directly into an existing floor joist slid b...

Page 8: ... these precautions Pellet e r i F s n o i t u l o S declines all responsibility 1 The fire must be installed on a floor with sufficient carrying capacity If the existing building does not meet this requirement appropriate measures must be taken i e a load distribution plate 2 Sara must be installed on a non combustible surface This surface must protrude a minimum of 150mm from the front of the closed...

Page 9: ...cavity Depending on the circumstances you may also have to consider the use of a hearth and the installation of a support frame TELEVISION CLEARANCES Television If electrical equipment eg Plasma TV LCD TV or home theatre is to be installed above the wood pellet fire we recommend installing a non combustible mantle below the TV screen or recessing the TV screen into the wall for heat protection 50mm...

Reviews: