Rath 2500 SPRVSR Series Installation & Operation Manual Download Page 9

Page 9

Testing

Once all equipment is connected and power is applied, wait 30 minutes before testing.

1.

 Disconnect the RJ11s from the front of the Supervisor Board.

2.

 The LED above the port will illuminate.

3.

 The system will do a full check before the relay will change state. The duration of this test is determined by the 

    timer jumper on the board plus 90 seconds (ex: If the timer jumper is set to 15 minutes, the relay will change after 

    15 minutes plus 90 seconds).

4.

 To reset, reconnect the RJ11 from the removed device. The red LED above the port will clear.

5.

 After all errored devices are reconnected, the green system status light should illuminate within 3 minutes. 

Typical System Layout

Distribution Module

2500-UPS

Monitor

Fire

Control

Panel

Power Supply/UPS Backup

RP7700104 or RP7701500

2400 Series

Call Box

2400 Series

Call Box

2400 Series

Call Box

Outside 

Phone Line

Communication Failure

Relay Output

Power Failure

Relay Output

To 120vac

Addressable 

Fire

Alarm 

Module

22/24ga Single Pair

Provided

by RATH®

22/24ga Single Pair

Provided

Transformer

 RATH® Supervisor

Command System

360  of Supervision

N56W24720 N. Corporate Circle  •  Sussex, WI 53089

 800-451-1460  •  www.rathcommunications.com

MADE IN THE USA

3 YEAR WARRANTY

05/20

Twisted, Shielded 

Wire Recommended

Summary of Contents for 2500 SPRVSR Series

Page 1: ...pervisor Board 2500 __SPRVSR Installation Operations Manual N56W24720 N Corporate Circle Sussex WI 53089 800 451 1460 www rathcommunications com RP8500SPRVSR Ver 8 07 20 Made in the USA 3 Year Warrant...

Page 2: ...y assist with site preparation installation and maintenance It is our sincere hope that your experience with us has and will continue to surpass your expectations Thank you for your business The RATH...

Page 3: ...ex Ports Can be Used for Outside Phone Lines or Call Stations For 12 16 zone systems one Supervisor Board is included Wire as shown below For 28 36 zone systems two Supervisor Boards are included Wire...

Page 4: ...4 Phones 4 Phones 4 Phones 4 Phones 4 Phones 4 Phones Flex Ports Can be Used for Outside Phone Lines or Call Stations The second through fifth cards will always be used for connecting additional Emerg...

Page 5: ...Phones 4 Phones 4 Phones 4 Phones 4 Phones Flex Ports Can be Used for Outside Phone Lines or Call Stations Note Do not follow the color scheme on the punch down blocks themselves 56 92 Zone Distributi...

Page 6: ...te The numbering pattern continues on all subsequent cards Depending on the number of zones needed some cards will be left empty and will have no connections S01 S04 S05 S08 S09 S12 2019 2020 2033 203...

Page 7: ...use the 110 style punch down tool to punch down the blue blue white pair on to the number 20 punch down block Then take the orange orange white pair and punch it down on to the number 19 punch down bl...

Page 8: ...bracket or to a 19 rack not included Complete System Connections 1 Plug the power transformer into the power source wall outlet or UPS 2 Ensure the LEDs associated with the connected Supervisor ports...

Page 9: ...bove the port will clear 5 After all errored devices are reconnected the green system status light should illuminate within 3 minutes Typical System Layout Distribution Module 2500 UPS Monitor Fire Co...

Reviews: