allowing full physical test of each unit, without activating the site-wide alarm. Call
Points can be triggered manually, and Sensors can be triggered using standard
test equipment such as smoke spray or heat probe.
• Once the System Test is complete, return to the CONNECT unit and press either
R
or
Q
button to complete the test and exit System Test mode.
The test result is indicated as follows:
Pass
Green LED solid illumination
Radio OK, other fault
detected
Red LED flashes followed by Amber LED
group flashes to indicate fault (see ‘Amber
LED Indication’).
No Radio Signal
Amber LED group flashes to indicate fault
(see ‘Amber LED indication’).
• It is important to be aware that, whilst in System Test mode, the WES
3
network
is inactive and a site-wide alarm cannot be triggered from any unit. System Test
mode must be exited from the CONNECT in order to reactivate the network.
Note: Following initial installation, wait for a minimum of 60 minutes before starting
the first system test. During this time, the WES
3
units will self-calibrate to adjust
for background radio noise which may impact the accuracy of the system test.