RAMSET RAM 3000 UL Instruction Manual Download Page 19

17

www.ramsetinc.com

RAMSET

R

AM 3

000 U

L

 - 3100 U

L

 - 3200 U

L

WIRE BOARD CONNECTIONS

JP7 - 

Master/Slave plug: 

1) A 2

B    3) Common    4) 5 VDC

5) 24 VAC.

Used to synchronize the operation between two

gates.  A three-wire, Shielded cable is needed to run
from the A, B, & Common (JP7) of the master P.C.B.
to the A, B, & Common (JP7) of the slave P.C.B. 

JP6 - 

Battery back-up plug: 

1) A 2

B    3) Common    4) 5 VDC

5) 24 VAC.

Use this plug when using optional battery

back-up system, Ramset Keypad. 

1) 24 VDC.

5) Relay Common

2) 24 VAC

6) Fully Closed-N.C.

3) 5 VDC

7-8) Constant/Prewarn

4) Fully Open-N.O.

9-10) E.R.D. Alarm.

If E.R.D. is triggered twice before reaching a

limit, 24 VDC is supplied to sound an alarm (included
with operator).

JP10 - 

Loop Inputs:

1-2

Reverse   3-4) Exit   5-6) Phantom

Use with ILD-24 Loop wires

should be connected to this plug.

JP3 - 

3 Button: 

1) Close    2) Stop   3) Open   4) Common

Used with a 3-button station to open,

stop, and close the gate.  The open and close are
normally open connections and the stop is a nor-
mally closed connection, remove jumper wire when
connecting 3 button station.  Common and stop are
also used with a photo eye used to protect the back-
plane of the operators.

JP9 - 

Input Power: 

1,2) 24 VAC power.

Connection from external transformer to
power Control Board. 

JP4, JP5 & JP8

Reverse, Exit & Phantom

Sensor:

Used  with the Ramset ILD-24 plug-in loop detector.

The Loop wires should be connected into the
“LOOP INPUTS” plug.

Fully Open N.O. (works with relay common) -

Relay rated at 125 VAC, 2 amps.  Normally open
connection.  Open contact occurs until the open
limit is triggered.  When the open limit is
triggered, a closed contact occurs.

Relay Common - Relay rated at 125 VAC, 2 amps.

The common of the Fully Closed N.C. relay and
the Fully Open N.O. relay.

Fully Closed N.C. (works with relay common) -

Relay rated at 125 VAC, 2 amps. Normally
closed connection.  Closed contact occurs until
the closed limit is triggered.  When the closed
limit is triggered, an open contact occurs.

JP2 - 

Relay Connections:

R_Ramset_Ram3000.qxd  8/19/05  4:57 PM  Page 19

Summary of Contents for RAM 3000 UL

Page 1: ...FOR CLASS I II III IV VEHICULAR GATE OPERATORS R_Ramset_Ram3000 qxd 8 19 05 4 56 PM Page 1...

Page 2: ...www ramsetinc com R_Ramset_Ram3000 qxd 8 19 05 4 56 PM Page 2...

Page 3: ...death 1 READ AND FOLLOW ALL INSTRUCTIONS 2 Never let children operate or play with gate controls Keep the remote control away from children 3 Always keep people and objects away from the gate NO ONE S...

Page 4: ...Y DEVICE SUCH AS A PHOTOELECTRIC EYE OR LOOP DETECTOR CHECK THE E R D SENSITIVITY MAKE SURE THAT ALL AREAS AROUND THE GATE ARE SAFE AND SECURE SUCH AS THE FRONT REAR AND TRAVEL AREA COMMUNICATE WITH T...

Page 5: ...ature to prevent unauthorized use f All warning signs and placards must be installed where visible in the area of the gate g For Vehicular Gate Operators utilizing a non contact sensor in accordance w...

Page 6: ...s III A vehicular gate operator or system intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public Re...

Page 7: ...tion 1 4 H R Metal 1 4 H R Metal 1 4 H R Metal Continuous Duty 1 2 Hp 120 Vots AC 3 4 Hp 120 Vots AC 1 Hp 220 Vots AC Motor 4 5 amp 1625 rpm 8 5 amp 1625 rpm 4 5 amp 1625 rpm Power Failure By hand lev...

Page 8: ...be adjusted depending on local soil conditions 1 Construct form for mounting pad according to dimensions shown in Figure 1 and 2 2 Locate mounting pad according to dimensions given in illustration 3...

Page 9: ...LENGTH Figure 5 Figure 3 Note 15 amp wires connected to independent breaker HOOKUP ELECTRICAL POWER Figure 4 Gate travel is adjusted by loosening the limit Cams and adjusting them until proper gate tr...

Page 10: ...com RAMSET RAM 3000 UL 3100 UL 3200 UL SPACE REQUIRED FOR A STANDARD GATE IN THE OPEN POSITION Figure 7 STANDARD INSTALLATION FOR GATES FROM 16 TO 22 IN LENGTH Figure 6 R_Ramset_Ram3000 qxd 8 19 05 4...

Page 11: ...9 www ramsetinc com RAMSET RAM 3000 UL 3100 UL 3200 UL MINIMUM SPACE REQUIRED FOR COMPACT INSTALLATION Figure 8 Figure 9 20 minimum space required between open gate and wall for this compact installa...

Page 12: ...Loops on the ground floor prevents gate from closing when vehicle is in loop area Exit Loops on the ground floor opens gate when vehicle crosses loop area Photoelectric Safety Sensor Photo Eye preven...

Page 13: ...gate Control Board Three pushbuttons are located under the dip switches for operation of the gate see Figure 11 The opening stop and closing buttons can be utilized to set limit switches and verify pr...

Page 14: ...N Relay maintains a closed contact Dip Switch B 3 CONSTANT WARN Constant warning when gate is in motion Sw Function OFF No effect ON Triggers the prewarn relay to maintain a closed contact while gate...

Page 15: ...Function OFF Master mode single gate operation All peripheral devices are to be connected to the master operator ON Slave mode used to synchronize operation between two gates Commands are received fro...

Page 16: ...14 www ramsetinc com RAMSET RAM 3000 UL 3100 UL 3200 UL TERMINAL STRIP CONNECTION Figure 14 R_Ramset_Ram3000 qxd 8 19 05 4 57 PM Page 16...

Page 17: ...detector is cleared Once the detector is cleared the operator will resume normal operation If triggered twice before reaching a limit switch the alarm will sound for 6 minutes and the control board w...

Page 18: ...rol Board is powered by a separate mounted 24 VAC transformer This allows no neces sary board modifications between 110 VAC and 220 VAC single phase applications Some of the functions of the Control B...

Page 19: ...e The open and close are normally open connections and the stop is a nor mally closed connection remove jumper wire when connecting 3 button station Common and stop are also used with a photo eye used...

Page 20: ...42 27 24 65 71 64 30 39 34 37 41 63 40 45 63 35 63 59 29 58 47 50 49 27 25 31 26 26 27 24 66 33 60 53 33 54 38 57 62 61 1 9 3 6 7 8 5 4 2 43 67 44 57 13 13 38 30 24 52 51 28 27 10 57 18 70 22 48 25 1...

Page 21: ...lley 1 1 1 19 50 071 2 1 2 Cast Iron Pulley 1 1 1 20 50 076 4L V Belt 170 1 1 1 21 50 085 35 Limit Switch Chain 1 1 1 22 50 086 40 Driver Chain 26 Links 1 1 1 23 50 091 6 x 1 Machine Screw 2 2 2 24 50...

Page 22: ...3 16 x 3 4 Key Way 4 4 4 58 50 275 1 1 2 UHMW Spacer 1 1 1 59 50 295 8 Self Tap Sheet Metal Screw 2 2 2 60 50 299 Radio Receiver Terminal 1 1 1 61 50 304 120 240 Intelligate Transformer 1 1 1 62 50 31...

Page 23: ...1 Signal blocked 2 Area not suitable for type of Receiver SOLUTION 1 Reset circuit breaker 2 Replace 1 2 amp fuse 3 Return Control Board for repair 1 A for 1 2 hp motors turn dip switch A 4 On B for 3...

Page 24: ...estrians should use a separate entrance 3 Always keep people children and objects away from the gate while the gate is in operation No one should cross the area of a moving gate 4 All opening devices...

Page 25: ...eration No one should cross the area of a moving gate Use the emergency release only when the gate is not moving Make sure when using the foot release or hand crank the circuit breaker for the operato...

Page 26: ...ry System Key Switch Box Ramset Radio Receiver Ramset Remote Control Transmitter ILD 24 Ramset Plug in Loop Detectors Uphill Hinges Uphill Arms To be used under uneven conditions 20 05 50 40 Mounting...

Page 27: ...www ramsetinc com R_Ramset_Ram3000 qxd 8 19 05 4 58 PM Page 27...

Page 28: ...R_Ramset_Ram3000 qxd 8 19 05 4 58 PM Page 28...

Reviews: