Dip Switch "C" 2; Not in use at this time.
Leave in the ‘Off’ position.
Dip Switch "C" 6; “OPEN DELAY”
One second delay on the opening of the gate.
Dip Switch "C" 5; “CLOSE DELAY”
One second delay on the closing of the gate.
DIP SWITCH "C"
Dip Switch "C" 1; “SECURE CLOSE”
Sw. Function:
OFF Normal
Operation
ON
When power is lost, then regained, control board
checks status of the gate. If open and safety
devices are cleared, gate will close automatically.
Dip Switch "C" 3; “RADIO CYCLE”
Sw. Function:
OFF Normal Operation - gate only opens and closes on
the limit switches. If the gate is in travel then it will
always open.
ON
Cycle mode - gate opens and closes on the limit
switches, but if in travel, then it will stop with a first
command and reverse with a second command.
Dip Switch "C" 8; “SLAVE MODE” Master/Slave configuration
Sw. Function:
OFF Master mode - single gate operation. All peripheral
devices are to be connected to the master operator.
ON
Slave mode - used to synchronize operation between
two gates. Commands are received from the master
through a 3-wire, shielded cable.
(Not provided with unit).
Dip Switch "C" 7; “LEFT / RIGHT”
Sw. Function:
OFF Left hand installations - All operators come factory
set for left hand operation.
ON
Right hand installations - Reverses motor & limit
switches without moving any wires.
Dip Switch "C" 4; “ONE PASS”
Sw. Function:
OFF Normal Operation - fully opens and closes
ON
One pass mode - The gate will open until “the
reversing loop” is initially activated and then cleared,
the gate will then close. If the “reversing loop” is
then activated again, before the gate is fully closed,
the gate will stop until the “reversing loop” is cleared,
then continue to close.
WARNING:
When installing or servicing an operator, make sure switch
"C" 1 is ‘Off’. If switch "C" 1 is ‘On’, the gate will move when
power is applied and severe injury may occur.